background image

1/2" DIA. 

THRU HOLE

SUPPLIED NUT

SMALL

BUSHING

SUPPLIED TEST SWITCH/

INDICATOR LIGHT

TY-WRAP

SW INDICATOR

LARGE 

BUSHING

PLASTIC

TUBE

SW INDICATOR

PLASTIC

TUBE

LARGE

BUSHING

EM DRIVER

 SMALL

BUSHING

SW LEADS

TIE WRAP

7/8" DIA THRU

      HOLE

BALLAST

CHANNEL

 COVER

 FIXTURE

DIFFUSER 

    LENS

93071446

ILLUSTRATION 2

ILLUSTRATION 1

93071446

93071446

ILLUSTRATION 3

TY-WRAP

UL SWITCH

COVER

UL SWITCH

COVER

Mounting Height: This product meets or exceeds the NFPA minimum light 
requirements with all loads, down to the smallest rated lamp load, at heights 
up to 25.8ft. Many factors influence emergency illumination levels, such as the 
lamp load selected, luminare design, and environmental factors, therefore end 
use verification is necessary. For installations where the attached luminaire 
is mounted at heights greater then 25.8ft, the level of illumination must be 
measured in the end application to ensure the requirements of NFPA 101 and 
local codes are satisfied.

WIRING

Step 5.  Select correct wiring diagram to connect the emergency driver to the LED load, AC LED driver and Switch. Make sure all connections are in accordance  

with the National Electrical Code and any local regulations.

Step 6.  Install the labels “CAUTION” & “STATUS” in a visible location (see illustration 4).

Step 7.  After installation is complete, supply AC power to the emergency ballast and join the converter battery connector.

Step 8.  At this point, power should be connected to both the AC driver and the emergency driver, and the charging indicator light should illuminate indicating  

the battery is charging.

Step 9.  A short-term discharge test may be conducted after the emergency ballast has been charged for one hour.

Step 10.  Charge for 24 hours before conducting a long-term discharge test. Refer to “Operation” section below

Note: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required.

          The emergency ballast must be fed from the same branch circuit as the AC ballast.

EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT

TYPICAL SCHEMATICS ONLY. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS

ILLUSTRATION 4

EM DRIVER

LED mtg plt

(lens not shown)

TYPICAL LED

   LIGHTING 

    FIXTURE

  SWITCH 

INDICATOR

"CAUTION"

   LABEL

"STATUS"

  LABEL

93071865

RED
RED
WHT/RED
BLACK
VIOLET (+)
BROWN (-)

WHITE

WHT/BLK

BLUE

YEL/BLK

YELLOW

LED (+)

LED (-)

AC DRIVER (-)
AC DRIVER (+)

BLACK
WHITE

 

PLD7

EM LED 

DRIVER

LED LOAD

AC DRIVER

HOT

COMMON

VIOLET (+)
BROWN (-)

WALL SW

CONVERTER BATTERY CONN.

TEST SW/LED INDICATOR

EMERGENCY BACK-UP & AC DRIVER

RED
RED
WHT/RED
BLACK
VIOLET (+)
BROWN (-)

WHITE

WHT/BLK

BLUE

YEL/BLK

YELLOW

LED (+)

LED (-)

AC DRIVER (-)
AC DRIVER (+)

BLACK
WHITE

PLD10

EM LED

DRIVER

LED LOAD

AC DRIVER

HOT

COMMON

VIOLET (+)
BROWN (-)

WALL SW

CONVERTER BATTERY CONN.

TEST SW/LED INDICATOR

RED
RED

WHT/RED

BLACK
VIOLET (+)
BROWN (-)

WHITE

WHT/BLK

BLUE

YEL/BLK

YELLOW

LED (+)

LED (-)

AC DRIVER (-)

AC DRIVER (+)

SW 1

WHITE

 

PLD7

EM LED 

DRIVER

LED LOAD

AC DRIVER

HOT

COMMON

VIOLET (+)
BROWN (-)

CONVERTER BATTERY CONN.

TEST SW/LED INDICATOR

AC DRIVER (-)

AC DRIVER (+)

LINE 1

LINE 2

HOT

SW 2

EMERGENCY BACK-UP & AC DRIVER

EMERGENCY BACK-UP, AC DRIVER

 AND STEP DIMMING