C A U T I O N !
1.
Before installation, check that the local distribution conditions, nature of gas and pressure, and
the current state of adjustment of the appliance are compatible.
2.
Follow safety, maintenance, and test firing instructions packaged with Heater.
3.
Refer to model specifications label for gas type.
4.
Check all connections for gas leaks.
5.
Gas supply and regulator must be installed outside building.
6.
The hose assembly should be protected from traffic, building materials, and any contact with hot
surfaces both during and while in storage.
7.
Do not open doors, or move or handle heater while hot, burning, or connected to power supply.
8.
Turn power off before servicing. (Heater may start at any time if power is connected).
9.
Heater is not recommended for heating human living quarters.
10.
Not to be used for heating where flammable liquids and vapors are stored or used.
11.
Inadequate gas volume and (or) pressure will directly influence the combustion efficiency of the
heater. Adequate gas volume and (or) pressure is the responsibility of the installer.
12.
Adequate ventilation must be provided.
13.
Combustion and ventilation air must not be obstructed.
14.
Not for use with duct work other than types provided by manufacturer.
15.
Position heater properly before use. Heater must be level and in accordance with minimum
clearances.
16.
For safety, this heater is equipped with air flow proving switch and manual-reset high limit switch.
17.
Keep temperature of fuel containers below 37.8°C (100°F). Containers must be installed
outside building.
18.
Heater must not be operated for one hour following wash-down.
WARNING
If Connected To A Remote Thermostat
Heater May Start At Any Time!