62
Expert-32T rev.03
TEST MODE
A test mode allows you to simulate temperature changes and verify
controller performance. In test mode, the room temperature probe
inputs are turned off, allowing the user to change the temperature used
by the controller to operate the stages. The controller operates as
before using the new temperature settings. The user can also activate
each output separately.
1
Adjusting Room Temperature
When the room temperature is adjusted, the controller bypasses the
temperature probe inputs and uses the new value as a reference.
Set the function to
TEST
using the
menu select buttons. The room
temperature bypass value is
displayed.
Press the Edit key. The bypass value flashes. Use the arrow keys to
set the bypass value to the desired value. The appropriate outputs
are activated or deactivated immediately following the new tempera-
ture setting.
Room T° bypass:
76.7°F