NOTICE
The recommended installation wire gauge is 16 AWG (diameter of 1.29mm or cross
sectional area of 1.30mm
2
) for the power supply wires at a length of 300 meters (1000
feet). At the minimum gage (18AWG) for the power supply wires, the maximum wires
length is 150 meters (500 feet) . The recommended installation wire gauge is 18 AWG
(diameter of 1.02mm or cross sectional area of 0.82mm
2
) for the communication wires at a
length of 1200 meters (4000 feet). The cable must be twisted pair and shielded. The EDGE 3-Slot
Expansion Box and the 6-Slot Expansion Box can supply up to 5 amperes to the modules.
WARNING
Installation must only be performed by qualified service personnel.
WARNING
When choosing the supply redundancy option, only one Expansion Box must
supply the Main Controller, and controller groups must be divided by subgroups of
two Expansion Boxes plus one group of three Expansion Boxes if the number of
controller is odd
WARNING
When choosing the no supply redundancy option, do not forget to wire the GND
(GND from 24VDC, green color on diagram block) between each controller.
NOTICE
For the small terminal blocks used for inputs and low voltage outputs, use a
tightening torque from 0.5N*m (4.43lbf*in) to 0.6 N*m (5.2lbf*in) to fasten a wire.
Connecting a Module to the Communication Network
The communication bus enables communication between the EDGE Main Controller and the EDGE mod-
ules (terminal A and terminal B on the Automation network or the Safety network). There are two commu-
nication networks available. One of them serves as a backup network.
1. Locate the terminals
Automation or Safety
on the module you want to connect to the EDGE 3-Slot
or 6-Slot Expansion Box or EDGE 4IN-2V-8DO.
NOTE:
You should always use the
Automation
network, unless you have redundant main controls.
2. Connect the wires from the module to the EDGE 3-Slot or 6-Slot Expansion Boxes or EDGE 4IN-2V-
8DO.
IMPORTANT:
Make sure to connect same identifications together and use the same network from
one side to the other.
IMPORTANT:
The communication network must be installed in a daisy chain topology. Consult the
wiring diagrams to see the maximum cable distance according to the wire gauge.
891–00516
EDGE Wiring Diagram
59
Содержание EDGE 074-11793
Страница 4: ...NOTES 4 891 00516 EDGE Wiring Diagram...
Страница 16: ...Chapter 1 Introduction 16 891 00516 EDGE Wiring Diagram...
Страница 22: ...NOTES 22 891 00516 EDGE Wiring Diagram...
Страница 25: ...NOTES 891 00516 EDGE Wiring Diagram 25...
Страница 26: ...Chapter 2 Wiring Diagrams Figure 2 2 PCB 421 or PCB 420 Connection 26 891 00516 EDGE Wiring Diagram...
Страница 37: ...NOTES 891 00516 EDGE Wiring Diagram 37...
Страница 40: ...Chapter 2 Wiring Diagrams Figure 2 16 0 10V to 0 3 4V Converter Wiring Diagram 40 891 00516 EDGE Wiring Diagram...
Страница 45: ...Chapter 2 Wiring Diagrams Figure 2 25 Inlet Wiring 891 00516 EDGE Wiring Diagram 45...
Страница 46: ...Chapter 2 Wiring Diagrams Figure 2 26 Inlet Failsafe Wiring 46 891 00516 EDGE Wiring Diagram...
Страница 72: ...NOTES 72 891 00516 EDGE Wiring Diagram...
Страница 76: ...NOTES 76 891 00516 EDGE Wiring Diagram...
Страница 79: ...C Extending a cable Best practice using a junction box 891 00516 EDGE Wiring Diagram 79...
Страница 80: ...Appendix C Extending a cable Using of heat shrink tubing 80 891 00516 EDGE Wiring Diagram...