Table 3

6-Slot Expansion Box and 3-Slot Expansion Box ratings (cont'd.)

Motor/inductive load

10,5 A MAX

Minimum load of 0.2A

Full Load amperage on the motor nameplate is not the
maximum amp. When varying, the amperage might be
higher.

(Nb of Units = Max current rating divided by the max
current of the fan )

LED and CCFL loads

120/208/240Vac; 50/60Hz, 750W/ 920VA MAX

Minimum load of 0.2A / 25W

Ballast load

120Vac; 50/60Hz; 1200W; 10 MAX

208 Vac; 50/60Hz; 1040W; 5A MAX

240Vac; 50/60Hz; 720W; 3A MAX

Minimum load of 0.2A

Inputs

Temperature

Compliant to GSIE temperature probes

Accuracy of ±0.1ºC in a normal operation

Allowable loss of performance in a noisy environment:

Accuracy of ±0.65ºC from initial reading with a fixed resistor of 1% precision used for test-

ing purpose.

Analog 0-5 Volts

Sensor must be able to drive a 2k Ohms load, which means the sensor must drive at least
2.5mA to ensure correct readings.

Accuracy of ±30mV in a normal operation.

Allowable loss of performance in a noisy environment:

Accuracy of ±80mV from initial reading with a voltage source of 1% precision used for test-
ing purpose.

Analog 4-20mA

Sensor must be able to drive a 120 Ohms load

Maximum rating: 20.8mA, 2.5V

Accuracy of ±0.2mA in a normal operation.

Allowable loss of performance in a noisy environment:

Accuracy of ±0.4mA from initial reading with a current source of 1% precision used for test-
ing purpose.

Dry contact

Close contact resistance must be lower than 200 Ohms

Open contact resistance must be higher than 100k Ohms

Water meter, Pulse
speed

Max 100Hz, pulse width minimum of 3.2ms

Max 100 Ohms (close contact) and min. 100k Ohms (open contact) including the value of

the wire resistance

Содержание 891-00516

Страница 1: ...re complete information on the product please refer to the manual on the USB key provided with your EDGE manual or go to the following web sites http www automatedproduction com en apmanuals php http...

Страница 2: ......

Страница 3: ...to 10 C 32 to 50 F Non condensing 10 to 30 C 50 to 86 F 95 3 Non condensing 30 to 40 C 86 to 104 F 95 3 Non condensing IP rating IEC 60529 54 Nema Rating Nema 250 12 Flame Rating UL94 5VA V 0 Flame Ra...

Страница 4: ...t 15966 grams 35 2 lbs Clearance around the enclosure Top 300mm 12 inches Bottom 300mm 12 inches Hinge Side 250mm 10 inches Latch Side 180mm 7 inches Table 3 6 Slot Expansion Box and 3 Slot Expansion...

Страница 5: ...iplied by its service factor For example 10A 2 5 A 1 5 SF 2 7 relay can drive up 2 fans NC normally closed contact Resistive loads electric heating element 120 208 240Vac 10A MAX NC normally closed co...

Страница 6: ...n used for test ing purpose Analog 0 5 Volts Sensor must be able to drive a 2k Ohms load which means the sensor must drive at least 2 5mA to ensure correct readings Accuracy of 30mV in a normal operat...

Страница 7: ...f 1 precision used for testing purpose Auxiliary outputs 0 10 VDC outputs 0 10VDC accuracy 1 means 0 1V output impedance 50 Ohms Max current per output 20mA for each output 24 VDC outputs 24 VDC 50 mA...

Страница 8: ...Flame Rating IEC 60695 or IEC 60707 FV 0 IK rating degree of mechanical protec tion impact IEC 62262 08...

Страница 9: ...20 C Nominal OA Shield DCR 1 8 1000ft 20 C Nominal Attenuation Max dB 100ft 0 13 125 kHz 0 25 500 kHz 0 36 1 MHz Number of Twists 2 4 Twists foot min Table 2 DC Power cables Item Description Wire gau...

Страница 10: ...d for Communication 1 pair 15AWG twisted shielded for Power Table 3 Other Low voltage cables Item Description Cable type Twisted and shielded Minimum gauge 1 mm2 18 AWG Maximum sensor cable length 150...

Страница 11: ...rlock option Output interlock option Pit fans X X X Sidewall fans X X X Stir fans X X X Tunnel fans X X Heaters X X X X X Brooders X Ceiling inlets X X potentio meter Wall inlets X X potentio meter Na...

Страница 12: ...please refer to the manual on the USB key provided with your EDGE manual or go to the following web sites AP website http www automatedproduction com en apmanuals php Cumberland website http www cumb...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ...ly followed in all cases Authorities having jurisdiction should be consulted before installations are made 1004 E Illinois St Assumption IL 62510 0020 Phone 1 217 226 4421 Fax 1 217 226 4420 www gsiag...

Отзывы: