Table 3
6-Slot Expansion Box and 3-Slot Expansion Box ratings (cont'd.)
240Vac; 5A MAX
Minimum load of 0.2A
NO (Normally Opened) contact - DC load
24Vdc; 5A MAX. ( Current reading not available in DC).
Minimum load of 0.2A
NO (normally opened) contact - LED and CCFL loads
120/208/240Vac, 750W; 920VA MAX
Minimum load of 0.2A / 25W
NO (normally opened) contact – Ballast loads
120/208/240Vac, 6A MAX
Minimum load of 0.2A
NC (Normally Closed) contact - Motor/inductive load
10 A MAX
Minimum load of 0.2A
(Nb of Units = Max current rating divided by the max
current of the fan multiplied by its service factor)
For example, 10A / (2.5 A * 1.5 SF) = 2.7; relay can
drive up 2 fans
NC (normally closed) contact - Resistive loads (electric
heating element)
120/208/240Vac, 10A MAX
NC (normally closed) contact - Tungsten load
120/208/240Vac; 3A MAX
Minimum load of 0.2A
NC (normally closed) contact - DC load
24Vdc; 5A MAX (Current reading is not available in DC)
Minimum load of 0.2A
NC (normally closed) contact - LED and CCFL loads
120/208/240Vac; 750W; 920VA MAX
Minimum load of 0.2A / 25W
NC (normally closed) contact – Ballast load
120/208/240Vac; 3A MAX
Minimum load of 0.2A
Variable outputs modules (SSR)
Resistive loads (heat lamps, heat mats, incandescent
light)
120 VAC; 2000W; 16.66A; 50/60Hz
208 VAC; 2000W; 9.61A; 50/60Hz
240 VAC; 2000W ; 8.33A; 50/60Hz
Minimum load of 0.2A