background image

Technical Information • Installation Instructions 

Oil

Issued March 2018

Right reserved to effect technical
changes in the interest of product im
provement !

R20 /  R30

GB 

Содержание Giersch R20 Series

Страница 1: ...Technical Information Installation Instructions Oil Issued March 2018 Right reserved to effect technical changes in the interest of product im provement R20 R30 GB...

Страница 2: ...p 6 Function 7 Control unit 7 Flame monitor with Flame detector QRB 8 Air volume adjustment 9 Servomotor 10 Oil control optional 11 Startup 13 Table of settings R20 13 Table of settings R30 14 Design...

Страница 3: ...ally operated shut off valve for separating the burner must be installed It must be easily accessible Filter and venting device Upstream of the burner a filter must be installed to prevent the ingress...

Страница 4: ...al data R20 WLE R20 V WLE R20 AE WLE R20 ZS L WLE R30 AE WLE R30 Z L WLE Burner output in kW 36 166 36 77 36 166 95 273 Boiler output in kW 33 153 31 71 33 153 87 251 Fuel oil Type EL to DIN51603 Meth...

Страница 5: ...cordance with the wiring diagram HEED LOCAL REGULATIONS Protect the electrical feed line with a 10 A fuse Use flexible cable For the key to the circuitry symbols see Page 24 Connecting the oil The tab...

Страница 6: ...setting 10 and 20 bar The pump pressure can be set for the relevant output see Table of settings Pages 13 14 To do so Remove the sealing plug Screw in the pressure gauge and adjust the pump pressure b...

Страница 7: ...on followed by lockout at the end of TSA Safety and switching functions If a flame failure occurs during operation the fuel feed shuts off immediately and the system tries a restart with pre aeration...

Страница 8: ...not sufficient The LED of the KLC flame detector lights up continuously for approx 3 sec then flashes The control unit switches to lockout mode when the safety interval expires Important note the saf...

Страница 9: ...e purpo se of presetting Readjustment is required in any case in relation to the installation After adjustment of the optimal combustion values the two lock nuts have to be tightened No burner operati...

Страница 10: ...eadjusted the burner refasten the servomotor hood and set the switch on the lower part of the control unit to the position 2nd stage Version L single stage with automatic economy device On version L b...

Страница 11: ...ion the number of burner startups the bur ner operating hours etc and in addition warns if the oil throughput drops below the preset target value e g blocked nozzle Through early detection and elimina...

Страница 12: ...utput nozzle change change in pump pressure etc the target value as specified above has to be redefined The old target value is thereby overwritten Service function If the oil flow is reduced by more...

Страница 13: ...5 19 75 69 1 35 45 S 13 6 3 20 85 78 1 50 45 S 13 7 2 22 95 87 1 75 45 S 13 8 0 23 110 101 2 00 45 S 13 9 3 26 125 115 2 25 45 S 13 10 6 29 140 129 2 50 45 S 13 11 8 32 150 138 2 75 45 S 13 12 7 39 1...

Страница 14: ...5 S 20 10 12 9 9 7 48 52 47 50 0 105 60 40 2 5 5 Burner output Boiler output where k 92 Nozzle size Nozzle spray angle Oil pump pressure Oil throughput Nozzle stem position dimension A Nozzle stem pos...

Страница 15: ...ing for motor 10 37 50 11586 14 Solenoid valve for BFP 57 90 10919 15 Oil pump BFP 21 LG with connection parts 47 90 10834 Filter insert for BFP pump 59 90 50470 16 Gasket 13 x 18 x 2 50 37 50 11293 1...

Страница 16: ...90 12582 16 Oil pump AT 245 with connection parts 47 90 12645 17 Gasket 13 x 18 x 2 50 37 50 11293 18 Hose stem ND 6 dia 1 4 10 37 50 11348 19 Oil hose ND 6 1200 mm long 2 47 90 11347 20 Gasket 10 x...

Страница 17: ...50 11586 13 Solenoid valve for Oil pump AS AT and ALE 47 90 12582 14 Oil pump AT245 with connection parts 47 90 12645 Pump filter kit for AS AT pump with seal 47 90 23325 15 Gasket 13 x 18 x 2 50 37...

Страница 18: ...pump AS AT and ALE 47 90 12582 15 Oil pump AT245 with connection parts 47 90 12645 Pump filter kit for AS AT pump with seal 47 90 23325 16 Gasket AL 13 x 18 x 2 50 37 50 11293 17 Hose stem ND 6 dia 1...

Страница 19: ...or exact adjustment and stabilization of the smokestack draught we recommend the in stallation of a draught limiter By this means any draught fluctuations are equalized moisture in the smokestack is l...

Страница 20: ...tion in ser vice position Release quick release locks and detach base plate Suspend base plate with retaining buttons in cross recesses of housing Control dimensions for the ignition electrode The ign...

Страница 21: ...21 E 04 2000 G 26 03 18 Service instructions dimensions Wiring diagram R20 R20 R20 AE SP_1 932 SP_1 933...

Страница 22: ...22 E 04 2000 G 26 03 18 Service instructions dimensions R20 V R20 ZS L SP_1 934 SP_1 935...

Страница 23: ...GXQJ HWULHEVOHXFKWH 5 9HQWLO 6WXIH 02 3 3 6 1 7 7 5 6 5 1 6 57 9 K 0 0 a 5 5 5 5 6 6 6 RLOHU 9 K 5 5 6 5 SP_1 938 ODWW 6HLWH 02 5 HDUE 8UVSU 63B OXFNDL DWXP DWXP UVHW W GXUFK 02 02 5 bQGHUXQJ HSU UVDW...

Страница 24: ...tage P12 Ext time meter 2nd stage P21 Time meter optional Q1 Main heating switch Q2 Safety switch S1 Control unit LMO S3 Switch 1st 2nd stage S9 OC oil control optional T3 Ignition transformer X11 Plu...

Страница 25: ...ky Nozzle soiled or defective Solenoid valve defective Filter in solenoid valve blocked External light source Coupling motor pump defective Oil preheater blocked Mains voltage more than 15 under rated...

Страница 26: ...ng kW Feuerraumwiderstand mbar 40 80 120 160 2 6 1 0 1 4 1 6 5 4 3 2 1 Durchsatz kg h R20 AE Brennerleistung kW Feuerraumwiderstand mbar 40 80 120 160 2 6 1 0 1 4 1 6 5 4 3 2 1 Durchsatz kg h R20 Z Br...