
115
CTC EcoZenith i550 Pro
For the installer
Primary flow sensor (B1, B2, B3).
(B3) Optional primary flow sensor for CTC EcoComfort
(cooling).
The sensors sense the outgoing temperature to the radiators. Each sensor
is equipped with a 2 metre connecting cable. If the cable is too short, extra
length can be joined to it.
Secure the primary flow sensor to the pipe using straps or similar. Most
important is the position of the tip of the sensor as this is the part that
detects the temperature. The sensor must be insulated to prevent the
ambient temperature from affecting the measurement. For optimum function,
use contact paste.
(B1) Sensor, primary flow to radiator system 1
Position: on the primary flow to heating system 1.
The sensor is connected to the PCB in positions G13 and G14.
Sensor type: NTC 22k
(B2) Sensor, primary flow to radiator system 2. Optional primary flow
sensor for CTC EcoComfort (cooling), accessory.
Position: on the primary flow to heating system 2 after radiator pump G2.
For cooling, on the primary flow
The sensor is connected to the circuit card in positions G15 and G16.
Sensor type: NTC 22k
(B3) Sensor, primary flow to radiator system 3
Position: on the primary flow to heating system 3 after radiator pump G3.
The sensor is connected to expansion card X3 in positions 13 and 14.
Sensor type: NTC 22k
Other sensors
(B5) Sensor, upper tank
(factory fitted)
Placement: in the tank’s uppermost sensor pipe.
The sensor is connected to the circuit card in positions G63 and G64
Sensor type: NTC 22k
(B6) Sensor, lower tank
(factory fitted)
Placement: in the tank’s middle sensor pipe.
The sensor is connected to the circuit card in positions G65 and G66
Sensor type: NTC 22k
(B7) Return sensor heating system
Position: on the return pipe from the heating system.
The sensor is connected to the PCB in positions G31 and G32.
Sensor type: NTC 22k
(B8) Flue gas sensor
Position: in a sensor pipe or on the flue gas jacket surface on the wood boiler.
The sensor is connected to the PCB in positions G35 and G36.
Sensor type: NTC 3.3k
(B9) Sensor, wood boiler
Position: in a sensor pipe or jacket surface on the wood boiler.
The sensor is connected to the PCB in positions G61 and G62.
Sensor type: NTC 22k
(B10) Sensor, external boiler out
Position: on the primary flow pipe of the boiler.
The sensor is connected to the PCB in positions G71 and G72.
Содержание EcoZenith i550 Pro
Страница 1: ...162 105 20 1 2013 06 13 Installation and Maintenance Manual CTC EcoZenith i550 Pro...
Страница 95: ...97 CTC EcoZenith i550 Pro For the installer...
Страница 97: ...99 CTC EcoZenith i550 Pro For the installer 6725 7 1 6 1 287 322 7 36 1 7 5 1 1 D E...
Страница 120: ...122 CTC EcoZenith i550 Pro For the installer 20 Wiring diagram main card 3x400V...
Страница 121: ...123 CTC EcoZenith i550 Pro For the installer...
Страница 122: ...124 CTC EcoZenith i550 Pro For the installer 21 Wiring diagram main card 1x230V...
Страница 123: ...125 CTC EcoZenith i550 Pro For the installer...
Страница 124: ...126 CTC EcoZenith i550 Pro For the installer 22 Wiring diagram for expansion card...