The above electrical characteristics are based on the results of out going test. Please do
not expose solar module
to sunlight concentrated with mirrors, lenses or similar means. Under normal conditions,
a photovoltaic module
may experience conditions that produce more current and /or voltage than reported at Standard Test Conditions.
Accordingly, the values of Isc and Voc marked on listed modules should be multiplied by a factor of 1.25 when
determining component voltage ratings, conductor capacities, fuse sizes and size of controls connected to the
module output.
Refer to Section 690-8 of the National Electrical Code for an additional multiplying factor of 125
percent (80 percent de-rating) which may be applicable. Installation shall be in accordance with CSA C22.1,
Safety Standard for Electrical Installations, Canadian Electrical Code, Part 1.Any modules all have a serial
number and
a label
,
the date and place of manufacture was marked on the label.
VIII. CAUTION
Never touch the end of output cables with bare hands when the module is irradiated. Cover the surface of
module
by sufficiently thick cloth or something suitable to prevent incident light, and handle the wires with rubber-
gloved
hands not to receive electric shock.
1. Do not wear metallic jewelry which may cause of electric shock during installation.
2. Consult the government office concerned for permit installation and inspection requirement.
3. Install modules and ground frames in accordance with applicable law of each country
4. Product should be installed and maintained by qualified personnel.
5. Do not drop tools or hard objects on the glass of solar module
6. Do not scratch the back film by hard objects
7. When part of solar module is shadowed, hot spot may be caused. Therefore do not shadow cells.
8. Do not pour chemicals on modules when cleaning.
9. Keep modules away from children.
10.Do not disconnect under load.
11.Keep 10cm gap between the roof and the modules for good ventilation.