USER MENU OPERATION SETTINGS:

The control has user Menu settings that will determine how 
the control operates. The unit is shipped with factory de-
fault settings. The user must change any of the settings as 
required for the application. To reset all settings to factory 
defaults, press and hold all 3 buttons simultaneously (

, and   buttons) for approximately 5 seconds.  

To view Menu items, press and hold 

 for 5 seconds. 

The unit will display the first Menu item on the left side of the 
display. The right side of the display indicates the Menu item 
settings. To change the setting, momentarily press the   or 

 key.

A momentary press of the 

 key advances the display to 

the next Menu item, and continues, till the last menu item is 
displayed. Pressing the key one more time with the 

last

 menu 

item, (aL) displayed returns the control to the operating mode.

USER MENU 

Each press of 

 results in forward movement to the next 

Menu item. If you need to change an item “passed”, you 
must repeatedly press 

, return to the operating mode, 

then press and hold 

 for 5 seconds to re-enter the Menu 

mode. Then repeatedly, momentarily press 

 until the 

desired Menu item is again displayed.
To store any changes made to any Menu items, the Menu 
must be exited by pressing 

 when the last item is 

displayed. If no buttons are pressed for ten minutes while in 
the menu, the control will return to operating mode and any 
changes that were made will be lost.
The following table shows the menu items, default settings 
and optional settings.

NOTE:

 The Heat/ Cool switch (SW1) MUST be in the proper 

position BEFORE setting options.

Menu

Item

Description

Factory

Default

Options

Press   or 

to select

Comments

CF

Temperature Scale

F

C or F

Selects temperature display in Fahrenheit or Celsius

dFF

Differential

5

1 to 30

Selects the range between Cut In and Cut Out.

SP

Set Point Mode
Cool
Heat

Cl

CO

CO or CI
CI or CO

Selects how the set point temperature will operate the 
load terminal. CI indicates the setpoint temperature 
will be the Cut In temperature. CO indicates the 
temperature will be the Cut Out temperature. See 
Operation section.

SOF

Sensor Operation Failure
Cool
Heat

1
0

0 or 1

None

Cooling - Selects the operation of the Control Load 
relay in the event of a sensor failure in Cool mode. 1 
(default) will cause the load contacts of the relay to 
close and remain closed if the sensor either opens or 
shorts. 0 causes the load contacts of the relay to open 
and remain open.
Heating has no optional selection. Sensor failure
in Heating will result in the relay contacts opening.

dL

Display Light

Off

On or Off

Selects the LCD display light Off or On. With this 
selected Off, the display light will illuminate any time a 
keypad button is pressed to provide better viewing in 
low lighting conditions, and go off after 10 seconds. If 
On is selected, the display light will be On continuously.

ASd

Anti Short-Cycle Delay

Cool

1

Heat

0

0 to 12

Selects the minimum time (in minutes) that the load 
contacts will remain open after a cycle before closing 
again. This will prevent the compressor or other load 
from being damaged by cycling too soon. A blinking 
Snowflake or Flame icon indicates that the control has 
a demand to energize the load, but is waiting for the 
delay time to elapse. A setting of 0 indicates no time 
and the feature is disabled. SW1 must be set to the 
proper position before checking this setting.

LP

Lock Front Panel Keypad

Off

On or Off

When selected Off, the keypad can be used as normal. 
When selected On, prevents unauthorized access to 
the control settings by locking out all keys. To unlock 
the control when it is locked, press and hold the Menu 
key for 5 seconds.

OFS

Ambient Temperature
Offset

0

-4, -3, -2, -1, 0,

1, 2, 3, 4

This control is calibrated at the factory, but the “sensed" 
temperature may read different because of mount-
ing/installation, or other factors. This item allows the 
displayed temperature to be shifted the number of 
degrees set to compensate for this difference

52

Содержание RS7300MP

Страница 1: ...RETAIN THIS MANUAL CONSERVEZ CE MANUEL UL 391 UL 726 CSA B366 1 Mailing PO Box 1237 Shipping 2716 Crescent Dr International Falls MN 56649 Ph 866 361 7355 Fax 218 283 5786 Web www crownroyalstoves co...

Страница 2: ......

Страница 3: ...NTS 21 CONTROL PANEL 23 START UP OPERATION 24 FILLING WATER JACKET 24 FIRING THE FURNACE 24 DAILY FUELING FIREING 25 SAFETY 25 POWER FAILURE 25 STARTING A COAL FIRE 26 MAINTENACE 27 DAILY WEEKLY MONTH...

Страница 4: ......

Страница 5: ...ondary combustion along with shaker grates and a removable ash pan for quick and easy cleaning For the best corrosion resistance and heat transfer possible our Crown Royal firebox and outer drum is a...

Страница 6: ...6...

Страница 7: ...chemicals or oils 5 Furnace Sizing The size of a furnace should be large enough to provide sufficient heat without constant reloading Targeted burn times are around 12 hours an adequately sized furna...

Страница 8: ...8...

Страница 9: ...ng and or ash removal doors open Do not store fuel or other combustible materials within marked installation clearances Inspect and clean flues and chimney regularly CAUTIONS Hot Surfaces Keep childre...

Страница 10: ...vider to ensure that installation is in compliance to regulations and all terms have been met Blocks or Concrete Pad Inspect the ground conditions that you intend to install your furnace on If the are...

Страница 11: ...CONCRETE PAD DIMENSIONS 7300MP 7400MP A 49 56 B 62 73 C 13 5 15 D 13 5 15 E 6 5 6 25 F 6 5 6 25 11...

Страница 12: ...enced by many chimney suppliers to brace every eight feet The chimney manufacture also recommends that the height of the piping does not exceed a total of forty 40 ft When installing chimney please re...

Страница 13: ...hods are possible but the most important factor is if ground water comes in contact with your heating lines it will be the greatest heat loss to your system A minimum of R10 insulation value is recomm...

Страница 14: ...he a c coil If the central heating system is a hot water boiler system a water to water heat exchanger is needed The water from an open system will contaminate the closed system if the waters are mixe...

Страница 15: ...oyal Stove shall be installed without changing the function of the controls or rewiring the original boiler A wiring interconnection is permitted The electrical system of both boilers shall be powered...

Страница 16: ...ol center Run 115V power to white and black wire of fan center coil Break one wire of gas boiler Aqua stat Hook one side of wire to brown wire of fan control center contact Hook other side of gas boil...

Страница 17: ...er installation of the add on water to air exchanger the air flow must be increased to fuel the furnaces electric furnaces and electric gas furnaces Methods of doing this are BELT DRIVE SYSTEM Blower...

Страница 18: ...18...

Страница 19: ...er heater needs to be turned off and the hot water heater is now a reservoir DOMESTIC SIDE BOILER SIDE WITH BYBASS PART NUMBER DESCRIPTION PX4 12NL PEX X MALE ADAPTER NO LEAD 15 002 BALL VALVE NO LEAD...

Страница 20: ...PART NUMBER DESCRIPTION 10 007 1 1 4 COPPER ADAPTER C X FEMALE 15 003 1 BALL VALVE FIP X FIP PX4 16 1 PEX X MALE ADAPTER 107 144 MALE BOILER DRAIN MNPT 13 129 1 X BRASS HEX BUSHING 10 046 1 COPPER FIT...

Страница 21: ...licone Covered Door Rope High Temperature Silicone 2 Way Rocker Switch Crown Royal Grate Crown Royal Frame Water Level Indicator Ash Pans 490055MP RS7300MP 490049MP RS7400MP 490043 Upper Blower Damper...

Страница 22: ...22...

Страница 23: ...ays put the switch in the fan position after refueling COMBUSTION FAN CONTROL CONTROL PANEL The aqua stat powers the inducer draft blower to maintain the desired water temperature The aqua stat is set...

Страница 24: ...to remove any air from the system CAUTION do not fire furnace until it is filled with water Allow furnace to run for two days and check water levels and fittings for leaks If all is okay you now shou...

Страница 25: ...excessive creosote and result in more fuel being consumed SAFETY Whenever the loading door is to be opened it should always be cracked slightly to allow oxygen to enter and burn off any combustion ga...

Страница 26: ...s burning hot Keep the draft controls fully open to establish a hot fire quickly Wait until the hardwood has burned long enough to start breaking off into hot coals Add more hardwood if needed When th...

Страница 27: ...until excess flows from the overflow pipe located in front of the chimney Annually Maintenance Lubricate fan solenoid shaft and shaker grate Check fan and solenoid to ensure proper air velocity is ha...

Страница 28: ...rming creosote which clings to the interiors of the stove Creosote vapors condense in the relatively cool chimney of a slow burning fire as a result creosote accumulates on the flue lining When creoso...

Страница 29: ...s properly closed and the gasket is completely sealed Check that the solenoid damper plate is opening and closing without hang ups Check that the flexible air duct is connected to the blower and the b...

Страница 30: ...30...

Страница 31: ...ne Neut Blue Red to Blower D C B A A B C D 1 2 3 4 5 6 7 8 8 7 6 5 4 3 2 1 DO NOT SCALE DRAWING 1 UNLESS OTHERWISE SPECIFIED REV DWG NO B SIZE TITLE Q A MFG APPR ENG APPR CHECKED DRAWN DIMENSIONS ARE...

Страница 32: ...32...

Страница 33: ...in sheltered area insufficient wind to disperse smoke C Furnace sizing Similar to other heating appliances furnace should be properly sized based on the estimated heat loss of the served structure II...

Страница 34: ...ps properly b Combustion blower wheel spins properly c Blower runs at proper speed verify voltage to blower motor 2 Combustion blower tube not restricted by debris creosote ash etc 3 Flame baffle flue...

Страница 35: ...f the wood either too high or too low will affect the amount of visible smoke Wood with a low moisture content less than 10 will burn relatively quicker resulting in some of the fuel going up the chim...

Страница 36: ...it is loaded B Furnace Size The size of a furnace should be large enough to provide sufficient heat without constant reloading If the target burn time is 12 hours an adequately sized furnace will pro...

Страница 37: ...ce with the state and local codes as well as surroundings including neighbors These areas along with the Best Burn Practices for Outdoor Furnaces can greatly help in providing clean safe heat from all...

Страница 38: ...38...

Страница 39: ...toves are backed with a 20 Year Limited Warranty To retain warranty on Crown Royal Stoves it is required to use recommended treatment and submit annual samples for testing Failure to maintain treatmen...

Страница 40: ...s are provided on all samples within 4 6 weeks If testing results are unsatisfactory recommendations of additional treatment will be given These recommendations will need to be preformed and a retest...

Страница 41: ...and submit annual water samples will result in a voided warranty Annually add of the required amount of treatment yearly this will keep levels balanced Follow directions for collection of water sample...

Страница 42: ...to 4 glasses of water but do not induce vomiting If vomiting occurs give fluids again GET IMMEDIATE MEDICAL ATTENTION DO NOT GIVE ANYTHING BY MOUTH TO AN UNCONSCIOUS OR CONVULSING PERSON NOTE TO PHYSI...

Страница 43: ...ay occur from or during the operation of the furnace or damage incurred due to any heating system failure These furnaces are not intended to be the only source of heat therefore it is recommended that...

Страница 44: ...44...

Страница 45: ...ke sure the stove is registered in original owners name verify mandatory chemical was added to the system and yearly test results were sent in and came back satisfactory After approved you find a loca...

Страница 46: ...________ ________________________________________________________________ ________________________________________________________________ Repairs Required ____________________________________________...

Страница 47: ...Please mark the affected area of the stove on the diagram below 47...

Страница 48: ...48...

Страница 49: ...plications which range from refrigeration to heating due to the wide temperature range of the control stated above Typical applications include walk in freezers beverage coolers supermarket display ca...

Страница 50: ...REFER TO PAGE 6 STATUS INDICATOR LED LIT WHEN CONTROLLED LOAD IS ENERGIZED ON SEE NOTE TEMPERATURE UP BUTTON TEMPERATURE DOWN BUTTON MENU BUTTON PRESS TO ENTER MENU MODE REFER TO PAGES 4 5 SW1 Refrige...

Страница 51: ...tional connection to customer alarm equipment Binary Input Gold Plated Contacts 24 VAC Block not used TH Thermostat Hot TR Thermostat Return NTC Temperature Sensor PTC Temperature Sensor Fig 3 Line Vo...

Страница 52: ...ow the set point temperature will operate the load terminal CI indicates the setpoint temperature will be the Cut In temperature CO indicates the temperature will be the Cut Out temperature See Operat...

Страница 53: ...et Point SP Cut In Differential 5 Setpoint temperature 40 Temperature Range 40 Setpoint Cut Out 45 SW1 Cool Set Point SP Cut Out Differential 5 Setpoint temperature 40 Temperature Range HEAT To use as...

Страница 54: ...hould be given to these events to prevent a false alarm If the control set back feature is used to change the setpoint the delay period set in AL should consider the time it takes for the system to re...

Страница 55: ...sistance K 140 60 2 49 149 65 2 09 158 70 1 76 167 75 1 48 176 80 1 26 185 85 1 07 194 90 0 92 203 95 0 79 212 100 0 68 221 105 0 59 Temperature F C Resistance K 40 40 613 31 35 640 22 30 668 13 25 69...

Страница 56: ...ine 1 888 725 9797 www white rodgers com www emerson com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co TROUBLESHOOTING Temp...

Страница 57: ......

Страница 58: ...OWNER S MANUAL...

Отзывы: