Temperature Probes:

NTC
The control is shipped with an NTC (Negative Temperature 
Coefficient) sensor, with a cable length of 7½ feet. Cable 
length can be extended up to 400 feet by appropriately splic-
ing and adding additional cable (22 AWG or larger diameter) 

PTC
The control may be connected to an existing PTC (Positive 
Temperature Coefficient) sensor. Make sure the PTC sensor 
meets the specifications tables below. Failure to do so will 
result in temperature inaccuracies. The PTC input may not be 

NTC TEMPERATURE VERSUS RESISTANCE TABLES

PTC TEMPERATURE VERSUS RESISTANCE TABLES

as needed – polarity is not important. When extending cable 
length, verify temperature accuracy and use the menu Ambi-
ent Temperature Offset (OFS) settings to compensate accord-
ingly if required.

extended more than 50 feet, and the wire gauge should be 
18 AWG wire or larger diameter. Be sure the probe attached 
matches the resistance vs. temperature tables or temperature 
inaccuracies may occur.

SPECIFICATIONS 

Temperature

 (°F)        (°C)

Resistance

(K

)

-40

-40

328.29

-31

-35

236.83

-22

-30

172.90

-13

-25

127.65

-4

-20

95.23

5

-15

71.74

14

-10

54.56

23

-5

41.85

32

0

32.37

41

5

25.23

Temperature

(°F)         (°C)

Resistance

(K

)

50

10

19.82

59

15

15.67

68

20

12.48

77

25

10.00

86

30

8.07

95

35

6.55

104

40

5.34

113

45

4.38

122

50

3.61

131

55

2.99

Temperature

(°F)        (°C)

Resistance

(K

)

140

60

2.49

149

65

2.09

158

70

1.76

167

75

1.48

176

80

1.26

185

85

1.07

194

90

0.92

203

95

0.79

212

100

0.68

221

105

0.59

Temperature

 (°F)        (°C)

Resistance

(K

)

-40

-40

613

-31

-35

640

-22

-30

668

-13

-25

697

-4

-20

727

5

-15

758

14

-10

789

23

-5

822

32

0

855

41

5

889

Temperature

(°F)         (°C)

Resistance

(K

)

50

10

924

59

15

960

68

20

997

77

25

1035

86

30

1074

95

35

1113

104

40

1153

113

45

1194

122

50

1236

131

55

1279

Temperature

(°F)        (°C)

Resistance

(K

)

140

60

1323

149

65

1368

158

70

1413

167

75

1459

176

80

1506

185

85

1554

194

90

1602

203

95

1652

212

100

1702

221

105

1753

Load Output Relay:  

 

Ratings (Maximum):

 

120VAC  208VAC  240VAC

Full Load Amps NC & Load 

16 A 

9.2 A 

8 A

Locked Rotor Amps NC & Load 

96 A 

55.2 A  48 A

Non-Inductive Amps NC & Load 

16 A 

16 A 

16 A

Horsepower NC & Load 

 

1 hp 

1 hp 

1 hp

24 VAC NC & Load 

100 VA, 30 VAC Max (Class 2)

Pilot Duty NC & Load 

125 VA, 24 to 240 VAC

•  Minimum Load Rating: 1 Amp @ 24 VAC  
•  Note: the above minimum current/voltage is specified 

   to assure proper operation.

NOTE: For use on single phase circuits only.

Alarm Relay Ratings (Maximum):   
N.O. contact: 1 Amp, 5 to 24 V, AC or DC

Operating Ambient Ratings (Control Enclosure):
Operating Temperature: 

-29°F to 140°F (-34° to 60°C)

Storage Shipping Ambient Ratings:
Storage Temperature: 

-40°F to 185°F (-40° to 85°C)

Operating Humidity: 

0 to 95% Relative Humidity, 

 

                             Non-Condensing

Maximum Dew Point:  

85°F (29°C)

Temperature Set-Point Range:
Set-Point Range:  -40° to 220°F (-40° to 104°C)
Differential Range: 

1 to 30 (Degrees F or Degrees C)

Case:
NEMA 1 Enclosure, Flammability Rating: UL94VO

Downloaded from 

www.Manualslib.com

manuals search engine

Содержание RS7300E

Страница 1: ...ETAIN THIS MANUAL CONSERVEZ CE MANUEL UL 391 UL 726 CSA B366 1 OWNER S MANUAL EPA QUALIFIED RS7300E RS7400E Mailing PO Box 1237 Shipping 2716 Crescent Dr International Falls MN 56649 Ph 866 361 7355 F...

Страница 2: ...2...

Страница 3: ...ol Panel 24 Start Up Operation Filling Water Jacket 25 Firing the Furnace 25 Starting a Wood Fire 25 Daily Fueling Firing 26 Safety 26 Power Failure 26 Maintenance Maintenance Cleaning 27 Daily Weekly...

Страница 4: ...4...

Страница 5: ...furnaces are often used to heat residential homes garages shops barns businesses greenhouses swimming pools spas domestic hot water radiant in floor heat and snow melt applications RS7300E RS7400E Est...

Страница 6: ...6...

Страница 7: ...e lighter fluids chemicals or oils 5 Furnace Sizing The size of a furnace should be large enough to provide sufficient heat with out constant reloading Targeted burn times are around 12 hours an adequ...

Страница 8: ...8...

Страница 9: ...v burnwise How to Use a Moisture Meter Video http www youtube com watch v jM2WGgRcnm0 EPA offers tips on how to properly use a moisture meter to test firewood before using in a wood burning stove or f...

Страница 10: ...10...

Страница 11: ...as softwood or hardwood The pines spruces and firs are common softwoods and the oaks elms birches and maples are the common hardwoods Softwoods burn rapidly and are more resinous than the hardwoods th...

Страница 12: ...ure Load fuel carefully to avoid injury to hands fingers and other body parts that may come in contact with the unit s loading door opening Cleaning of the heat exchanger flue pipe chimney and draft i...

Страница 13: ...ovider to ensure that installation is in compliance to regulations and all terms have been met Blocks or Concrete Pad Inspect the ground conditions that you intend to install your furnace on If the ar...

Страница 14: ...royalstoves com Greentech Manufacturing Inc 2716 Crescent Dr International Falls MN 56649 RS7300E 51 RS7400E 52 5 RS7300E 72 RS7400E 80 5 6 6 RS7300E 12 RS7400E 14 25 RS7300E 12 RS7400E 14 25 4 4 FRON...

Страница 15: ...mney piping it is recommenced by many chimney suppliers to brace every eight feet Also recommended by the chimney manufacture that the height of the pipping does not exceed a total of forty 40 ft When...

Страница 16: ...ttom of trench and cover with 6 of gravel or dirt At this point a water barrier is required Several methods are possible but the most important factor is if ground water comes in contact with your hea...

Страница 17: ...re is an air conditioning evaporator coil in the plenum install the water to air coil after the a c coil If the central heating system is a hot water boiler system a water to water heat exchanger is n...

Страница 18: ...event damage from loss of circulation due to electrical power failure The Crown Royal Stove shall be installed without changing the function of the controls or rewiring the original boiler A wiring in...

Страница 19: ...rom outdoor wood furnace Run thermostat wire from the strap on Aquastat to R and G of fan control center Run 115V power to white and black wire of fan center coil Break one wire of gas boiler Aquastat...

Страница 20: ...arge or too small it must be altered to fit the heat exchanger properly After installation of the add on water to air exchanger the air flow must be increased to fuel the furnaces electric furnaces an...

Страница 21: ...re in the hot water heater If installed on the hot side the hot water heater needs to be turned off and the hot water heater is now a reservoir BRAZED PLATE INSTALLATION Wood Stove Inlet water line fr...

Страница 22: ...22 Water to Air Exchanger Ball Valve Fitting Water to Air Exchanger Boiler Drain WATER TO AIR SETUP INSTALLATION...

Страница 23: ...es com Greentech Manufacturing Inc 2716 Crescent Dr International Falls MN 56649 Electronic Temperature Controls Blower Capacitor 3 Way Switch Limit Switch Thermo Well Solenoid Damper Door Rope High T...

Страница 24: ...using the controls The aqua stat powers the inducer draft blower to maintain the desired water temperature The aqua stat is set at 160 F at the factory which means the inducer will run until the water...

Страница 25: ...is reached 180F On this initial start up the water jacket will reach what is called the dew point This creates sweat inside the fire box which may last a couple of days and is normal Condensation wil...

Страница 26: ...should never be filled with excess wood so that the flue gas exit is blocked or impeded in any way Burning wood generates carbon monoxide and if the flue gas exit is blocked the carbon monoxide can b...

Страница 27: ...firebox Before refueling firebox perform weekly maintenance Use extreme caution when opening and cleaning doors these areas will still be hot CLEAN VERTICAL AND HORIZONAL HEAT EXCHANGERS Simply slide...

Страница 28: ...nd add water if low until excess flows from the overflow pipe located in front of the chimney Annually Maintenance Lubricate fan and solenoid shaft Check fan and solenoid to ensure proper air velocity...

Страница 29: ...nd ash removal periods the ash pan and loading doors should never be left open This unit should never be left unattended with any of the doors left open CREOSOTE FORMATION REMOVAL When wood is burned...

Страница 30: ...led 3 Check that the solenoid damper plate is opening and closing without hang ups 4 Check that the flexible air duct is connected to the blower and the bottom elbow of the furnace 5 Check that the te...

Страница 31: ...31...

Страница 32: ...32...

Страница 33: ...Load Line Neut D C B A A B C D 1 2 3 4 5 6 7 8 8 7 6 5 4 3 2 1 DO NOT SCALE DRAWING 1 UNLESS OTHERWISE SPECIFIED REV DWG NO B SIZE TITLE Q A MFG APPR ENG APPR CHECKED DRAWN DIMENSIONS ARE IN INCHES T...

Страница 34: ...34...

Страница 35: ...ed in sheltered area insufficient wind to disperse smoke C Furnace sizing Similar to other heating appliances furnace should be properly sized based on the estimated heat loss of the served structure...

Страница 36: ...tops properly b Combustion blower wheel spins properly c Blower runs at proper speed verify voltage to blower motor 2 Combustion blower tube not restricted by debris creosote ash etc 3 Flame baffle fl...

Страница 37: ...of the wood either too high or too low will affect the amount of visible smoke Wood with a low moisture content less than 10 will burn relatively quicker resulting in some of the fuel going up the ch...

Страница 38: ...ER it is loaded B Furnace Size The size of a furnace should be large enough to provide sufficient heat without constant reloading If the target burn time is 12 hours an adequately sized furnace will p...

Страница 39: ...tched to the heat load so that cold starts and overfilling are avoided Chimney height should be in accordance with the state and local codes as well as surroundings including neighbors These areas alo...

Страница 40: ...40...

Страница 41: ...allon s of authorized treatment Crown Royal Stoves are backed with a 20 Year Limited Warranty To retain warranty on Crown Royal Stoves it is required to use recommended treatment and submit annual sam...

Страница 42: ...e Information Form Testing facility analyzes the conductivity PH and nitrate levels of water sample Testing results are provided on all samples within 4 6 weeks If testing results are unsatisfactory r...

Страница 43: ...aintain treatment recommendation levels and submit annual water samples will result in a voided warranty Annually add of the required amount of treatment yearly this will keep levels balanced Follow d...

Страница 44: ...clothing and shoes GET IMMEDIATE MEDICAL ATTENTION INGESTION Give 3 to 4 glasses of water but do not induce vomiting If vomiting occurs give fluids again GET IMMEDIATE MEDICAL ATTENTION DO NOT GIVE AN...

Страница 45: ...eration of the furnace or damage incurred due to any heating system failure These furnaces are not intended to be the only source of heat therefore it is recom mended that a back up system is in place...

Страница 46: ...46...

Страница 47: ...nt in by customer we make sure the stove is registered in original owners name verify mandatory chemical was added to the system and yearly test results were sent in and came back satisfactory when ap...

Страница 48: ...48 Warranty Claim Form Have you turned in a warranty claim before YES or NO If yes is the leak in the same place Yes or No Additional Notes or Comments Repair Required...

Страница 49: ...m refrigeration to heating due to the wide temperature range of the control stated above Typical applications include walk in freezers beverage coolers supermarket display cases for flowers produce me...

Страница 50: ...ICATOR LED LIT WHEN CONTROLLED LOAD IS ENERGIZED ON SEE NOTE TEMPERATURE UP BUTTON TEMPERATURE DOWN BUTTON MENU BUTTON PRESS TO ENTER MENU MODE REFER TO PAGES 4 5 SW1 Refrigeration Cool Heating Heat S...

Страница 51: ...omer alarm equipment Binary Input Gold Plated Contacts 24 VAC Block not used TH Thermostat Hot TR Thermostat Return NTC Temperature Sensor PTC Temperature Sensor Fig 3 Line Voltage Application Power S...

Страница 52: ...ure will operate the load terminal CI indicates the setpoint temperature will be the Cut In temperature CO indicates the temperature will be the Cut Out temperature See Operation section SOF Sensor Op...

Страница 53: ...ential 5 Setpoint temperature 40 Temperature Range 40 Setpoint Cut Out 45 SW1 Cool Set Point SP Cut Out Differential 5 Setpoint temperature 40 Temperature Range HEAT To use as a Heating control SW1 mu...

Страница 54: ...ents to prevent a false alarm If the control set back feature is used to change the setpoint the delay period set in AL should consider the time it takes for the system to reach the set back temperatu...

Страница 55: ...9 65 2 09 158 70 1 76 167 75 1 48 176 80 1 26 185 85 1 07 194 90 0 92 203 95 0 79 212 100 0 68 221 105 0 59 Temperature F C Resistance K 40 40 613 31 35 640 22 30 668 13 25 697 4 20 727 5 15 758 14 10...

Страница 56: ...te rodgers com www emerson com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co TROUBLESHOOTING Temperature differential is wi...

Страница 57: ...57...

Страница 58: ...OWNER S MANUAL...

Отзывы: