9
Test procedure
Walk Test
After tuning the sensitivity, connect 12Vdc power to the system.
Allow 2 minutes warm-up time.
Make sure that the protected area is cleared of all people.
Cross the middle part of the protected area.
An alarm signal should be received in the control unit for 3 Sec.
NOTE:
Walk Test procedure should be conducted, at least once
a year, to confirm proper operation and coverage of the
detector.
Remote Test
Apply 5-30 Volts from control unit to the terminal marked TEST (on the transmitter
unit).
An alarm signal should be received in the control unit for 3 Sec.
NOTE:
During regular operation it is recommended to conduct
remote test every day to confirm proper operation of all
system.