2.4 Operation
2.4.1 Installing and Operating the 2412-x08
1.
Install the 2412-x08 in the equipment rack.
2.
Connect 100-240 ±10% VAC, 47 - 63 Hz to the AC input. (Dual, redundant AC inputs,
if redundant power, Option R) on the back panel (Figure 2.2).
3.
Be sure the POWER LEDs, DS6, A (and B if redundant) are ON. (Figure 2.3).
4.
Connect a -35 to 0 dBm, 50-200 MHz signal to INPUTS, J1, J5, J7 and J9. (Figure 2.2).
5.
Connect OUTPUTS J2, J6, J8 and J10 (Figure 2.2) to the desired equipment.
6.
Select Automatic Gain Control (AGC) or Manual Gain Control (MGC) using switches S2 and
S3 for each of the individual channels. (Figure 2.2).
7.
If in AGC mode, select the Gain for each of the individual channels using the
Front Panel Switches, S2/S3. (May also be set via Remote interface.) (Figure 2.2).
8.
If in MGC mode, adjust output to desired output level for each of the individual channels
using the Front Panel Switches, S2/S3. (May also be set via Remote interface.) (Figure 2.2).
9.
AC Fuse - The fuse is a 5 mm X 20 mm, 2 amp slow blow (Type T) and is inserted in the far slot
in the drawer below the AC input (Dual, redundant AC inputs if redundant power, Option R) as
shown in Figure 2.4. There is a spare fuse in the near slot. If a fuse continues to open, the power
supply is most likely defective.
AC Fuse - 2 amp slow blow (Type T),
5 mm X 20 mm
FUSE DRAWER
SPARE FUSE
~
INPUT
100-240± 10%VAC
47-63 Hz
2A MAX
FUSE
TYPE T 2A GDC
250 VOLT
FOR 100 - 240 V~
~
FIGURE 2.4 Fuse Location and Spare Fuse
2412-408 Manual, Rev. 0
Page 12
09/04/12