![Crompton Tyco Electronics SWITCHBOARD INTEGRA 1540 Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/crompton/tyco-electronics-switchboard-integra-1540/tyco-electronics-switchboard-integra-1540_installation-and-operating-instructions-manual_2687149004.webp)
1 Introduction
The Crompton Switchboard 1540 is a panel mounted self contained measuring, display and
communication device.
This system will measure display and communicate up to 31 electrical parameters, integrating
high accuracy measurement technology with the simplicity and visibility of 7 segment LED
displays.
All voltage and current measurements are True RMS for accurate
measurement of distorted waveforms over a wide measuring
range. The Integra 1540 has excellent harmonic handling for true
power measurement.
Available in the following configurations:
3 Phase 3 Wire Unbalanced
3 Phase 4 Wire Unbalanced
The Integra 1540 front panel has two push buttons, referred to as
“keys”. The two keys take the user through the menu structure
with ease and simplicity, to display and configure to their
individual requirements.
The parameters available are shown in the table below.
1
Integra 1540 Measured Quantity
Units of measurement
System Voltage
Volts
System Current (Average)
Amps
Average % Total Harmonic Distortion (THD) of System Voltage
% of Total RMS
and Current
Voltage L-N (4 wire only)
Volts
% Total Harmonic Distortion (THD) of voltage
% of Total RMS
Voltage L-L (calculated in 4 wire)
Volts
Current in 3 Phases
Amps
% Total Harmonic Distortion (THD) of Current
% of Total RMS
Neutral Current (4 wire only)
Amps
Frequency
Hz
Power Factor
Active Power
kW,
see note 1
Reactive Power
kVAr,
see note 1
Apparent Power
kVA
Active Energy
kW.h
Reactive Energy
kVAr.h
Total System Current Demand
Admd
Total System Active Power Demand
kWdmd
Maximum Total System Current Demand
Admd
Maximum Total System Active Power Demand
kWdmd
Note 1. All power related measurements are importing only unless connected as exporting unit.