cGas Detector Analog Transmitter - Operation Manual
8.2 Read from Sensor
During this process, the main board reads from the smart sensor board and
uploads the calibration and configuration information stored in the smart
sensor board, saving the information and overwriting the existing calibration
and configuration information for that sensor in the main board.
With the unit powered ON, from the main display, press ENTER.
Enter passcode 3022 using the UP button and ENTER buttons.
Enter Password
3022
Press ENTER to access the Config Menu.
Config Menu
Press Enter
In the Selected Channel menu, confirm the desired channel is showing.
Selected Channel
CH1 CO2
Press the UP button to find Read From Sensor. Press ENTER.
Read from Sensor
CH1 (Left)
Read from Sensor
>YES
Press the UP button to change from NO to YES and press ENTER to select.
The system will Read the new calibration information to the main board. Press
ENTER to exit.
8.3 Write to Sensor
This process forces an upload of the calibration and configuration information
that is stored in the main board to the sensor smart board. Every time a change
is made on the cGas Detector, the main circuit board saves the change to the
smart sensor board automatically. However, there may be instances when you
may want to force save the changes to the smart sensor board, such as if the
memory of the smart sensor board gets corrupted.