cGas Detector Analog Transmitter - Operation Manual
When finished pressed ENTER and then ENTER again to exit.
7.11 Test Analog Output
Testing the analog output allows you to determine if the installation was
successful. The test forces the cGas Detector to output a predetermined signal
to the controller or DDC/BAS to test that the correct signal is being transmitted
and the controller responds as configured (ie. if analog output is configured for
VFD control, the fans operate as expected).
From the main display, press ENTER.
Enter passcode 0001 using the UP button and ENTER button.
Enter Password
0001
Press ENTER to access the Test Menu.
Test Menu
Press Enter
In the Test AO menu, the default entry is 4 mA. Press ENTER.
Test AO
4.0 mA
Enter the preferred output value between 0 and 30 mA by using the UP, DOWN
and ENTER buttons, or to continue with 4 mA press ENTER to the end.
Test AO
>14.0 mA
When finished, press ENTER and then again to Confirm Y.
Confirm?
>14.0 mA
N
>Y
Test AO
14.0 mA
The test will start as soon as you press ENTER to confirm and will remain in the
test mode as long as the Test AO screen remains untouched. To stop the test,
press the UP or DOWN button. To test another analog output value repeat the
process by pressing ENTER.