25
FnIO G-Series
Copyright(C) CREVIS Co.,Ltd S82-31-899-4599 URL: www.crevis.co.kr
- Setp #3
- Check the Status Byte, When Status Byte and Control Byte are same, the Process value is updated.
Bit# 7
Bit# 6
Bit# 5
Bit# 4
Bit# 3
Bit# 2
Bit# 1
Bit# 0
Status Byte #0
RES
Measure Select (Voltage)
CON_ID (Rms Voltage L1-N)
0
0
0
0
0
0
0
0
Status Byte #0
RES
Measure Select (Current)
CON_ID (Rms Current L1-N)
0
0
0
1
0
0
0
0
Status Byte #0
RES
Measure Select (Power)
CON_ID (Apparent Power L1)
0
0
0
2
0
0
0
0
Status Byte #0
RES
Measure Select (Power)
CON_ID (Active Power L1)
0
0
0
2
0
0
1
1
- Step #4
- Check the Process value
Process value #0 (Rms Voltage)
000055F0 (Dword hex) 22000 (Dec) 220V
Process value #0 (Rms Current)
000F4240 (Dword hex) 1000000 (Dec) 1000A
Process value #0 (Apparent power)
014FB180 (Dword hex) 22000000(Dec) 220kVA
Process value #0 (Active power)
00A7D8C0 (Dword hex) 11000000(Dec) 110kW