● Example of Setting
- Read data : Phase 1 Rms Voltage/Rms Current/Apparent power/Active power.
- Input Value : 220V, 1000A, PF 0.5
- Parameter : CT 1 : 1000, Input Frequency 55 ~ 65Hz, Overvoltage threshold 260V, Other is Default(0).
- Overvoltage Threshold = (260V(User Setting Value)-250V(defaultSetting Value))/0.2V.Resolution : 0.2V
- ex) OverCurrent Threshold = 1000A (User Setting CT 1 : 1000)=((1A(User Setting Value)-0.8(default
Setting Value))/0.001)*1000(CT).Resolution : 0.001A
* All of default value is 0
- Step #1
- Set the Parameter
Parameter
Value
CT sensor 1 : x (12 bit)
001111101000(bit) Set CT 1000
Scaling for energy values (3 bit)
000 (bit) Set 1 m Wh/VARh/VAh
Frequency (1 bit)
1 (bit) Set 55~65Hz
Overvoltage Threshold Lx (8 bit)
00110010 (bit) Set 260V
Undervoltage threshold Lx (8 bit)
00000000 (bit) Set 0V(default)
Overcurrent Threshold Lx (8 bit)
00000000 (bit) Set 0.8A(default)
All of Parameter
E8 83 32 00 00 (Byte hex)
- Setp #2
- Set the Control Byte (See Output Image Value)
Bit# 7
Bit# 6
Bit# 5
Bit# 4
Bit# 3
Bit# 2
Bit# 1
Bit# 0
Control Byte #0
RES
Measure Select (Voltage)
CON_ID (Rms Voltage L1-N)
0
0
0
0
0
0
0
0
Control Byte #1
RES
Measure Select (Current)
CON_ID (Rms Current L1-N)
0
0
0
1
0
0
0
0
Control Byte #2
RES
Measure Select (Power)
CON_ID (Apparent Power L1)
0
0
0
2
0
0
0
0
Control Byte #3
RES
Measure Select (Power)
CON_ID (Active Power L1)
0
0
0
2
0
0
1
1