background image

infiNET™ SWITCHES 

 

 

• 

Wallboxes: Devices mount in standard 
wallboxes. For easy installation, Crestron 
recommends using 3 ½” deep wallboxes. Several 
devices can be installed in one wall box 
(multigang). This requires the removal of side 
sections (refer to diagram on page 4) and the 
derating of the switching device. For a smooth 
appearance, one-piece multigang faceplates (not 
supplied) can be installed. 

Derating Information for Incandescent, Tungsten Halogen, 
and Electronic Low Voltage Applications 

Part Number

No Side 

Removed 

One Side 

Removed 

Two 

Sides 

Removed 

-SW1RF/ 

-SW4RF 

1000W  

700W 

550W 

-SWS1RF/ 

-SWS4RF 

1000W  

700W 

550W 

-SLVS1RF 

No Derating Necessary 

• 

Other Switch Devices: Mechanical 3- or 4-way 
switches will not work with the -SW1RF,  
-SW4RF, -SWS1RF, -SWS4RF, and -SLVS1RF. 

Derating Information for Magnetic Low Voltage and 
Neon/Cold Cathode Applications

*

 

Part Number 

No Side 

Removed 

One Side 

Removed 

Two Sides 

Removed 

-SW1RF/ 

-SW4RF 

1000VA/ 

750W 

700VA/ 

500W 

550VA/ 

400W 

-SWS1RF/ 

-SWS4RF 

1000VA/ 

750W 

700VA/ 

500W 

550VA/ 

400W 

-SLVS1RF 

No Derating Necessary 

• 

Spacing: If mounting one device above another, 
leave at least 4 ½” vertical space between them. 

Multigang Installations 

In multigang installations, several controls are grouped 
horizontally in one wallbox. For a smooth appearance, 
one-piece multigang faceplates (not supplied) can be 
installed. 

*  VA ratings are for input power to the transformer. If you do not 

know the input power requirement of the transformer, use the bulb’s 
wattage rating to determine proper rating. 

1.  When combining controls in a wallbox, remove 

inner side sections prior to wiring (refer to the 
following figure). 

Derating Information for Fluorescent/HID Applications 

Part 

Number 

No Side 

Removed 

One Side 

Removed 

Two Sides 

Removed 

-SW1RF/ 

-SW4RF 

8A 5.5A 

4.5A 

-SWS1RF/ 

-SWS4RF 

8A 

5.5A 

4.5A 

-SLVS1RF 

No Derating Necessary 

Inner Sections of Multiganged Switches  
(CLW-SW4RF Shown)  

REMOVE INNER SECTIONS

DO NOT REMOVE OUTER SECTIONS

RUN

SET

OFF

RUN

SET

OFF

 

Derating Information for Ceiling Fans 

Part 

Number 

No Side 

Removed 

One Side 

Removed 

Two Sides 

Removed 

-SW1RF/ 

-SW4RF 

3A 3A 3A 

-SWS1RF/ 

-SWS4RF 

3A 

3A 

3A 

-SLVS1RF 

No Derating Necessary 

2.  To remove a side section, bend the side section 

back and forth with a pair of pliers until the 
section breaks off from the mounting plate. Use a 
file or sandpaper to remove any excess metal. 

The load capacity must also be derated. The 
following charts provide derating information for 
various applications. 

4  

  infiNET™ Wall Box Switch :  CLW-SW1/4RF, SWS1/4RF, & SLVS1RF 

Installation Guide - DOC. 6293A 

Содержание infiNET CLW-SLVS1RF

Страница 1: ...ve unit that when used in conjunction with the SWS1RF or the SWS4RF acts as an additional switch control point in a multi switch single circuit application It does not connect to a Cresnet system and cannot be used without a SWS1RF or SWS4RF The SLVS1RF does not have a mode selection switch It will emulate the RUN mode of the SWS1RF even if connected to a SWS4RF unless the mode selection switch of...

Страница 2: ... the latest Crestron Product Catalog for a complete list of 2 Series control systems 4 Refer to Derating Charts for Multigang Installations on page 4 Physical view of CLW SW1RF SWS1RF clockwise from top Top Side and Front 5 VA ratings are for input power to the transformer If you do not know the input power requirement of the transformer use the bulb s wattage rating to determine proper rating 1 7...

Страница 3: ...ide and Front Industry Canada Statement The term IC before the certification registration number only signifies that the Industry Canada technical specifications were met IC 5683A CWD1011 1 75 in 4 45 cm 3 81 in 9 68 cm 4 13 in 10 48 cm 3 28 in 8 32 cm 1 88 in 4 77 cm 2 70 in 6 86 cm 1 50 in 3 81 cm Important Notes Read before installation Codes Install in accordance with all local and national el...

Страница 4: ...ng installations several controls are grouped horizontally in one wallbox For a smooth appearance one piece multigang faceplates not supplied can be installed VA ratings are for input power to the transformer If you do not know the input power requirement of the transformer use the bulb s wattage rating to determine proper rating 1 When combining controls in a wallbox remove inner side sections pr...

Страница 5: ...uit breaker 2 Wire the switches as shown in Figure 3 on page 8 NOTE Do not connect the BLUE Slave wire to the Black Hot or RED Load wires NOTE The RED Load and BLACK Hot wires are 14 AWG The BLUE Slave and WHITE Neutral wires are 18 AWG The GREEN Ground wire is 16 AWG When installing a SWXRF or a SWSXRF without a slave follow the instructions in Wiring a SW S XRF No Slaves below If wiring a SWSXRF...

Страница 6: ...witch s mode selection switch shown in the following diagrams to the RUN position and perform either of the following steps depending on the switch model Parts of CLW SW1RF SWS1RF Button Mode Selection Switch RUN SET OFF Parts of CLW SW4RF SWS4RF Button 2 Mode Selection Switch Button 4 Button 3 Button 1 RUN SET OFF Testing a SW1RF and SWS1RF With the mode selection switch in the RUN position tap t...

Страница 7: ...are not covered Further Inquiries This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the dealer s warranty if any If you cannot locate specific information or have questions after reviewing this guide please take advantage of Crestron s award winning customer service team by ...

Страница 8: ...LW SWS1RF shown To continue a circuit past a switched light fixture to one or more duplex receptacles connect the switch as shown in the following diagram Figure 2 Adding a Duplex Receptacle Past a Switched Light Fixture Master Slave Installation Figure 3 Wiring a CLW SWSXRF CLW SWS4RF shown with a CLW SLVS1RF 8 infiNET Wall Box Switch CLW SW1 4RF SWS1 4RF SLVS1RF Installation Guide DOC 6293A ...

Отзывы: