25 • GL-IPAC-SW8
Product Manual — Doc. 7389C
Internally Connected Occupancy Sensors
To configure:
1. From the Occ Sensr List screen, highlight an internal sensor using ▼ and ▲.
2. Press Test to enter the Internal Sensor Test screen.
3. Press Type to define one of the available states:
l
Active Hi (Default)
l
Active Lo
l
Normally Open (N/O)
l
Normally Closed (N/C)
Status shows the current sensor state (Active or Inactive) based on the chosen type.
4. Press OK to save the setting and return to the Occ Sensor List screen.
Internal Sensor Test Screen
Cresnet Connected Occupancy Sensors
NOTE: Internal sensors, wired directly to the GL-IPAC-SW8, do not need to be discovered.
External Cresnet sensors range from B0.1 through B9.1.
To configure:
1. Highlight the external sensor from the Occ Sensr List screen and then press Find to set IDs
for Cresnet occupancy sensors. Three options to find the sensors are presented:
l
Set ID using IR Remote allows the sensor to be found using an IR remote. This
requires a direct view of the sensor, but does not require physical access to the
sensor.
l
Find by pressing test button allows the sensor to be found by pressing the button on
the inside of the sensor. This requires the sensor to be physically accessible, which
may require a ladder or step stool.
l
Find by serial number allows the sensor to be found by entering the serial number of
the sensor. The sensor's serial number must be recorded prior to installation.
Содержание Green Light GL-IPAC-SW8
Страница 1: ...GL IPAC SW8 Crestron Green Light Integrated Switching System Product Manual Crestron Electronics Inc ...
Страница 4: ...Troubleshooting 41 iv Contents Product Manual Doc 7389C ...
Страница 5: ...v Contents Product Manual Doc 7389C ...
Страница 44: ...This page is intentionally left blank Product Manual Doc 7389C GL IPAC SW8 44 ...