15 • GL-IPAC-SW8
Product Manual — Doc. 7389C
⑥
SENSORS 1-4 24, 1 - 4, G connects to occupancy sensors. Use 18 - 12 AWG wiring.
SENSORS 5-8 24, 1 - 4, G connects to photocells. Use 18 - 12 AWG wiring.
24 supplies power to the devices and should be daisy chained to all devices in the same
sensor group.
1 - 4 control signal from the connected devices.
G is the common ground to the devices and should be daisy chained to all devices on the
same sensor group.
Occupancy Sensor Wired to SENSORS 1-4 Port
Occupancy sensors can only be wired to the SENSORS 1-4 port.