Crestron
CEN-ERFGW-POE
Extended Range Wireless Gateway
NOTE:
All Crestron certified Cresnet wiring must consist of two
twisted pairs. One twisted pair is the +24V conductor and the GND
conductor and the other twisted pair is the Y conductor and the Z
conductor.
Strip and Tin
Wire
When daisy chaining Cresnet units, strip the ends of the wires carefully
to avoid nicking the conductors. Twist together the ends of the wires
that share a pin on the network connector and tin the twisted connection.
Apply solder only to the ends of the twisted wires. Avoid tinning too far
up the wires or the end becomes brittle. Insert the tinned connection into
the Cresnet connector and tighten the retaining screw. Repeat the
procedure for the other three conductors.
Add Hubs
Use of a Cresnet Hub/Repeater (CNXHUB) is advised whenever the
number of Cresnet devices on a network exceeds 20 or when the
combined total length of Cresnet cable exceeds 3000 feet (914 meters).
Reference Documents
The latest version of all documents mentioned within the guide can be
obtained from the Crestron Web site (
).
List of Related Reference Documents
DOCUMENT TITLE
2-Series Control Systems Reference Guide
Crestron e-Control Reference Guide
Further Inquiries
To locate specific information or resolve questions after reviewing this
guide, contact Crestron's True Blue Support at 1-888-CRESTRON
[1-888-273-7876] or refer to the listing of Crestron worldwide offices on
the Crestron Web site (
) for assistance within a
particular geographic region.
To post a question about Crestron products, log onto the Online Help
section of the Crestron Web site (
). First-
time users must establish a user account to fully benefit from all available
features.
Operations & Installation Guide – DOC. 7158A
Wireless Gateway: CEN-ERFGW-POE
•
29
Содержание CEN-ERFGW-POE
Страница 1: ...Crestron CEN ERFGW POE ExtendedRangeRFWirelessGateway Operations Installation Guide...
Страница 4: ......