Problem Solving
Troubleshooting
The following table provides corrective action for possible trouble situations. If
further assistance is required, please contact a Crestron customer service
representative.
APAD Troubleshooting
TROUBLE
POSSIBLE
CAUSE(S)
CORRECTIVE ACTION
Project cannot be
uploaded to keypad:
1. Screen is black.
APAD is powered
down.
Verify that power is supplied to
the APAD.
2. Communications
error.
Incorrect COM port
specified.
Verify upload preferences is set
to the COM port being used to
communicate to the control
system.
Incorrect NET ID
setting.
Verify that panel NET ID matches
the NET ID specified during
upload. Refer to "Uploading and
Upgrading" in this guide.
3. Checking panel
type error.
Problem with cable
between control
system and APAD.
Check the cable for errors or poor
connections.
Wrong screens
appear on LCD.
Screens were not
uploaded.
Upload screens as described in
the help files found in VT Pro-e.
LCD is dark or too
light.
LCD brightness or
contrast is improperly
set.
Hold down any of the soft buttons
for more than 10 seconds as
power is applied. The LCD
brightness and contrast are set to
their default values.
Check Network Wiring
Use the Right Wire
In order to ensure optimum performance over the full range of your installation
topology, Crestron Certified Wire, and only Crestron Certified Wire, may be used.
Failure to do so may incur additional charges if support is required to identify
performance deficiencies because of using improper wire.
Calculate Power
CAUTION:
Use only Crestron power supplies for Crestron equipment. Failure to do
so could cause equipment damage or void the Crestron warranty.
CAUTION:
Provide sufficient power to the system. Insufficient power can lead to
unpredictable results or damage to the equipment. Please use the Crestron Power
Calculator to help calculate how much power is needed for the system
(
http://www.crestron.com/calculators
).
When calculating the length of wire for a particular Cresnet run, the wire gauge and
the Cresnet power usage of each network unit to be connected must be taken into
consideration. Use Crestron Certified Wire only. If Cresnet units are to be daisy-
chained on the run, the Cresnet power usage of each network unit to be daisy-chained
must be added together to determine the Cresnet power usage of the entire chain. If
the unit is a home-run from a Crestron system power supply network port, the Cresnet
Operations & Installation Guide – DOC. 6455
Wall Mount LCD Controller: APAD
•
19