MODBUS Exception Codes

Code

Name

Meaning

01

ILLEGAL FUNCTION

The function code received in the query is not an allowable action for the server 
(or slave).  This may be because the function code is only applicable to newer   
devices, and was not implemented in the unit selected.  It could also indicate that 
the server (or slave) is in the wrong state to process a request of this type, for 
example because it is unconfi gured and is being asked to return register values.

02

ILLEGAL DATA ADDRESS

The data address received in the query is not an allowable address for the 
server (or slave).  More specifi cally, the combination of reference number and 
transfer length is invalid.  For a controller with 100 registers, the PDU addresses 
the  fi rst register as 0, and the last one as 99.  If a request is submittted with a 
starting register address of 96 and a quantity of registers of 4, then this request 
will successfully operate (address-wise at least) on registers 96, 97, 98, 99.  If 
a request is submitted with a starting register address of 96 and a quantity of 
registers of 5, then this request will fail with Exception Code 0x02 “Illegal Data 
Address” since it attempts to operate on registers 96, 97, 98, 99 and 100, and 
there is no register with address 100.

03

ILLEGAL DATA VALUE

A value contained in the query data fi eld is not an allowable value for server 
(or slave).  This indicates a fault in the structure of the remainder of a complex 
request, such as that the implied length is incorrect.  It specifi cally does NOT  
mean that a data item submitted for storage in a register has a value outside the 
expectation of the application program, since the MODBUS protocol is unaware of 
the signifi cance of any particular value of any particular register.

04

SLAVE DEVICE FAILURE

An unrecoverable error occurred while the server (or slave) was attempting to 
perform the requested action.

05

ACKNOWLEDGE

Specialized use in conjunction with programming commands.  The server (or 
slave) has accepted the request and is processing it, but a long duration of time 
will be required to do so.  This response is returned to prevent a timeout error from 
occurring in the client (or master).  The client (or master) can next issue a Poll 
Program Complete message to determine if processing is completed.

06

SLAVE DEVICE BUSY

Specialized use in conjunction with programming commands.  The server (or 
slave) is engaged in processing a long -- duration program command.  The client 
(or master) should re-transmit the message later when the server (or slave) is free.

08

MEMORY PARITY ERROR

Specialized use in conjunction with function codes 20 and 21 and reference type 
6, to indicate that the extended fi le area failed to pass a consistency check.  The 
server (or slave) attempted to read record fi le, but detected a parity error in the 
memory.  The client (or master) can retry the request, but service may be required 
on the server (or slave) device.

0A

GATEWAY PATH UNAVAILABLE

Specialized use in conjunction with gateways, indicates that the gateway was 
unable to allocate an internal communication path from the input port to the 
output port for processing as the request.  Usually means that the gateway is 
misconfi gured or overloaded.

0B

GATEWAY TARGET DEVICE 

FAILED TO RESPOND

Specialized use in conjunction with gateways, indicates that no response was 
obtained from the target device.  Usually means that the device is not present on 
the network.

ModBus Exception Codes

   ModBus Instructions

Содержание Lochinvar 1.5

Страница 1: ...ding this manual the Installation and Operation Manual and the Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or subst...

Страница 2: ...9 Typical Boiler System Wiring 12 13 5 UNIT OPERATION Unit Operation with ModBus Communications 14 17 6 TROUBLESHOOTING 18 21 7 DIAGRAMS Ladder Diagram 22 Wiring Diagram 23 Revision Notes Back Cover A...

Страница 3: ...set to 0 has a value equal to 0 Example To set the address of the ModBus board to 50 dip switches 2 5 and 6 have to be set to the 1 position The address is determined by adding the values of all the...

Страница 4: ...inputs Parity Parity is set by the position of Dip switch 10 0 No Parity 1 Even Parity If No Parity is selected there will be two stop bits otherwise there will be one Data Transmission Mode Many ModB...

Страница 5: ...ostic Registers 11 0B Diagnostic Return Bus Message Count 12 0C Diagnostic Bus Communication Error Count 13 0D Diagnostic Bus Exception Error Count 14 0E Diagnostic Return Slave Message Count 15 0F Di...

Страница 6: ...plication program since the MODBUS protocol is unaware of the significance of any particular value of any particular register 04 SLAVE DEVICE FAILURE An unrecoverable error occurred while the server o...

Страница 7: ...ked Drain Switch 0 1 ON 0 OFF 0 1 1 10008 Flame 1 0 1 ON 0 OFF 0 1 1 10009 Enable 0 1 ON 0 OFF 0 1 1 10010 Tank Thermostat 0 1 ON 0 OFF 0 1 1 10011 Blocked Flue 0 1 ON 0 OFF 0 1 1 10013 Blower Proving...

Страница 8: ...NA 0 65535 1 40003 0 10 Volt Input Rate Command Setpoint Command 0 0 100 1 40004 Tank Setpoint 0 Degrees Celsius 0 87 5 0 5 40005 Tank Temperature 0 Degrees Celsius 20 130 0 1 40006 Outdoor Temperatur...

Страница 9: ...other control signals are being provided the BAS will still need to refresh these inputs at least every 4 minutes Physical Wiring Figure 4 1_Terminal Strip Connections 1 2 3 4 5 6 7 8 9 10 11 12 13 1...

Страница 10: ...CONNECTION BOARD INLET TEMPERATURE SENSOR OUTLET TEMPERATURE HI LIMIT SENSOR FLUE GAS SENSOR LOUVER PROVING SWITCH FLAME SENSOR 1 2 LOW WATER CUTOFF BLOCKED DRAIN SWITCH DISPLAY PANEL PC INTERFACE SMA...

Страница 11: ...CONTACTS SEQUENCER BUILDING MANAGMENT SYSTEM BOILER PUMP CONTACTOR SYSTEM PUMP CONTACTOR HWG PUMP CONTACTOR IGNITOR BLOWERS GAS VALVES BOILER RATE OUTPUT DISPLAY PANEL PC INTERFACE 120V SUPPLY SYSTEM...

Страница 12: ...S COMMUNICATION BOARD MTR01 CONTROLLER Typical Boiler System Wiring Cascade Daisy Chain Connection Modbus RS485 Communication Bus Modbus RS485 Port on Gateway or Building System Physical Configuration...

Страница 13: ...us RS485 Port on Gateway or Building System Physical Configuration Direct Control Cascade Daisy Chain Connection Modbus RS485 Communication Bus Modbus RS485 Port on Gateway or Building System Physical...

Страница 14: ...ly it will provide for fail safe operation should ModBus communication be lost This timer will cause the unit to revert back to internal unit controls should the ModBus communication be interrupted lo...

Страница 15: ...stem DHW with direct control and DHW with remote control DHW with direct control This is the typical installation with a hot water generator in close proximity to the boiler with the tank thermostat o...

Страница 16: ...nsors and thermostat values are only available through the ModBus communication bus To ensure that the Crest boiler can properly respond to a call for hot water generation the following holding regist...

Страница 17: ...decimal value must be determined through linear interpolation of programmable parameters on the BMS Setup Menu BMS temperature set point at low analog input BMS temperature set point at high analog in...

Страница 18: ...ly doing This state should be compared to the command issued and what is expected If the boiler state does not agree with the command issued check communication and configuration Status Codes Input Re...

Страница 19: ...Sensor S7 Short 33 System Supply Temperature Sensor S6 Short 34 Tank Sensor S4 Short 35 Flue Sensor S3 Short 36 Inlet Sensor Short 37 Outlet Sensor S1 Short 38 Temperature Measurement Error 2 39 Temp...

Страница 20: ...Speed Low 231 Small Fan Speed High 232 Flame Failure 1 233 Ignition Failure 236 Flue Damper Open 235 Small Blower Proving Switch Not Open 236 Small Blower Proving Switch Not Closed 238 Air Pressure Sw...

Страница 21: ...ontrol boardandsetaside RemovetheMTR01controlboard see FIG 6 2 5 Replace install the new MTR01 control board 6 Replace the four 4 mounting nuts removed in Step 4 7 Reconnect all three 3 wire harnesses...

Страница 22: ...ENSOR 0 10V 0 10V TANK SENSOR OUTDOOR SENSOR 0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD SHIELD A B CASCADE LARGE CONNECTION BOARD CN6 1 CN3 6 CN3 7 CN3 14 CN3 13 CN3 11 CN3 9 CN3 8 CN3 1 CN3 2 CN3 3 CN3...

Страница 23: ...IL AUX SWITCH 1 AUX SWITCH 2 SHIELD SHIELD A B MODBUS OPTION RATE OUT BOILER PUMP OUT SYSTEM RETURN SENSOR SYSTEM SUPPLY SENSOR 0 10V 0 10V TANK SENSOR OUTDOOR SENSOR 0 10V 0 10V BMS IN SYSTEM PUMP IN...

Страница 24: ...Revision Notes Revision A ECO C08179 initial release Revision B ECO C08542 reflects edits made pages 7 8 and 18 due to changes made by SIT FB MODB Rev B 07 11...

Отзывы: