SECTION 2: 

ON GRID MOUNTING - CONTINUOUS ROW RECESSED MOUNTING

CAUTION: 

Ceiling contractor must provide 

an uninterrupted, continuous rough opening 
utilizing 

tee grids

 spaced 4” center to center. 

Length of opening should be determined from 

Figure 7 on next page.

 Tee grids and luminaire 

must be secured to structure above to support 
weight of luminaire.

CAUTION:

 Do not attempt to assemble 

luminaire rows on the ground and then lift 
into position. This may create stress at the 
connection points and may result in damage 
and/or mechanical failure.

CAUTION: 

Do not connect power in a run until 

all of run is installed, wire harnesses connected, 
and luminaire joints completed.

STEP 1: 

Remove lens and LED/reflector tray and set 
aside in order of run placement for reinstalling 
later. To remove lens, carefully slide a plastic 
card or putty knife between the lens and 
extrusion towards the end of the luminaire. 
Using the plastic card or putty knife, push the 
lens inward until the lens come free. 

 

After 

removing the lens, remove the Philips head 

reflector screws, remove the LED Reflector Tray, 
and disconnect the LED harness. Set lens and 
LED Reflector tray aside. See 

Figure 1 and 2.

STEP 2:

Locate and install End Cap Kits. Install End Cap 
with (4) #6 screws from end cap kit. The end 
cap has to be trimmed, the amount depends on 
the run length. Each notch corresponds to the 
successive Trim Length section in the chart on 
the next page (See 

Figure 7

). In order to install 

the end cap on the male end of the luminaire, 
replace the male joiner bracket with the female 
joiner bracket and remove the alignment pins. 
See 

Figure 4 and 6.

 

STEP 3:

Lay the first luminaire Right-Hand End 
of the Row into the grid per 

Figure 7

 grid 

requirements.

STEP 4:

Position second luminaire in row such that it aligns 

with joint end (male end) of first luminaire. Attach 

using customer supplied hardware to structure 

above. Connect the second luminaire to the first 

luminaire as shown in 

Figure 5 and 6

. Plug wire 

harness together and push excess wire into 

luminaire wiring chamber, ensure that wires are 
not pinched.

 

STEP 5:

Push luminaires tightly together while making 

sure the alignment pins slide into the interior 

tracks of each luminaire and span the luminaire 

joint. Secure joint by tightening supplied keps 

locknuts on threaded studs of male joiner 

bracket. Attach safety wires to luminaire safety 

wire bracket and structure above as shown in 

Figure 5 and 6

.

STEP 6:

Continue to install and assemble row following 

steps 1-5 above. Using one of the 7/8" dia. 

holes on the End unit (Left-Hand End of Run) 

luminaire, install conduit connector and make 

electrical connections per Section 5 “Electrical 

Connections”. 

STEP 7:

Replace LED trays and lens that was removed in 

Step 1 above, ensure that no wires are pinched.

4

5

6

End Cap

End Cap

LED Tray

Lens

Safety Wires

Safety Wires 

(Supplied by Others)

Safety Wires Brackets

Alignment Pins

Male End

Female End

Male End

Female End

End Plate Cap (After 

Trimming Has Been Done)

(4) #6 Screws

7/8" Plugged Hole 

for Conduit Entry

5/8" Plugged Hole for 

Threaded Rod Attachment 

(Off-Grid Mounting ONLY)

Содержание Stylus Series

Страница 1: ...icien qualifié 3 SUITABLE FOR CONTINUOUS ROW MOUNTING PEUT ÊTRE MONTÉ EN RANGÉE CONTINUE 4 Suitable for Damp Locations Convient aux emplacements humides 5 MIN 90C SUPPLY CONDUCTORS LES FILS D ALIMENTATION 90C MIN 6 INHERENTLY PROTECTED 7 TYPE IC VAPOR BARRIER MUST BE SUITABLE FOR 90C TYPE IC LE PARE VAPEUR DOIT CONVENIR POUR 90 C PROTECTION INHERENTE 8 Make sure the equipment is properly grounded ...

Страница 2: ...ire Using the plastic card or putty knife push the lens inward until the lens comes free See Figure 1 and 2 STEP 2 After removing the lens remove the Philips head reflector screws remove the LED Reflector Tray and disconnect the LED harness Set lens and LED Reflector tray aside See Figure 1 STEP 3 Attach customer supplied support cables to luminaire and structure above as shown in Figure 1 STEP 4 ...

Страница 3: ...alled with threaded rod to structure above by others and should be installed accordance with these instructions Plugged holes for threaded rod attachment are located 4in from both ends of each luminaire 23 25 0 19 Endcap Thickness 0 19 47 25 71 25 95 25 119 25 143 25 0 19 Endcap Thickness 0 19 Endcap Thickness 0 19 Endcap Thickness 0 19 Endcap Thickness 0 19 Endcap Thickness 0 19 Endcap Thickness ...

Страница 4: ... 7 In order to install the end cap on the male end of the luminaire replace the male joiner bracket with the female joiner bracket and remove the alignment pins See Figure 4 and 6 STEP 3 Lay the first luminaire Right Hand End of the Row into the grid per Figure 7 grid requirements STEP 4 Position second luminaire in row such that it aligns with joint end male end of first luminaire Attach using cu...

Страница 5: ...7 8 7 8 8 9 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 50 52 54 56 58 60 26 28 30 32 34 36 38 40 42 44 46 48 62 64 66 68 70 72 Trim Length for Endcaps in For On Grid Mounting ONLY Continous Row Length in End Cap to End Cap LUMINAIRE ROW LAYOUT EXAMPLE OF A THREE UNIT 20 24 CAN BE MOUNTED IN OTHER CONFIGURATIONS 7 86 7 8 86 7 8 38 7 8 237 1 16 End Cap to End Cap 236 1 16 Aperture 284...

Страница 6: ...8 STEP 2 Using one of the 7 8 dia holes on the end of the fixture install conduit connector See Figure 8 STEP 3 Install fixture from below into ceiling opening Attach customer supplied threaded rods to luminaire through 5 8 mounting holes located on the top of the housing and to the structure above as shown in Figure 8 Confirm that fixture is pulled up firm to ceiling line STEP 4 Make electrical c...

Страница 7: ...s located on the top of the housing and to the structure above as shown in Figure 7 and 8 Confirm that fixture is pulled up firm to ceiling line STEP 3 Position second luminaire in row such that it aligns with joint end male end of first luminaire Attach customer supplied supports to fixture through mounting holes located on the top of the housing and to the structure above as shown in Figure 11 C...

Страница 8: ...supply dimming negative lead If dimming is not being used ensure to cap off the grey lead GREEN LINE BLACK GROUND GREEN NEUTRAL WHITE DIM GREY DIM VIOLET VIOLET GREY CORD SUPPLY WIRING LUMINAIRE NEUTRAL OR HOT 2 LINE OR HOT 1 FCC NOTICE CAUTION Changes or modifications not expressly approved could void your authority to use this equipment This device complies with part 15 of the FCC Rules Operatio...

Отзывы: