TEMPERATURE SENSOR ELECTRICAL RATINGS

Volts

Continuous 

Amperes

Inrush 

Amperes

110-120

3.00

30.0

220-240

1.50

15.0

440-480

0.75

7.5

B-4.4) Moisture Sensors:

 

A normally open (N/O) set of moisture probes are is installed 

in the pump seal chamber, which can be used detect 

any moisture present in the seal chamber and/or motor 

chamber. A 330 K-Ohm, 1 watt test resistor is mounted 

between the probes to allow for verification that the moisture 

sensor circuit is in-tact using a multi-meter. The moisture 

sensors MUST be connected to moisture detector control 

in the control panel. The normally closed (N/C) contact of 

the moisture detector MUST be connected in series with 

the control circuit of the motor contactor. Wiring must be 

provided from the moisture detector sensor probe leads of 

the motor designated W1 and W2. In the event of moisture 

detection, the pump should be pulled and the source of the 

failure located and repaired. 

IF MOISTURE DETECTION 

HAS OCCURRED, SCHEDULE MAINTENANCE AS SOON 

AS POSSIBLE!

B-4.5) Control Panel and Electrical System:

 

The control panel and the electrical system MUST be 

properly designed and wired to include at least, but not

limited to the following;

 

a. Proper grounding per NEC. 

 

b. A temperature sensing circuit (See Fig. 4) 

 

c. A moisture detection circuit with continuity test

 

    circuit  (See Fig. 4) 

 

d. A level control system. 

 

e. A main power manual disconnect and lock out. 

 

f.  A motor starter and overload system.

B-5) When Used with a Variable Speed Drive:

Maximum turndown should not exceed 2:1. Drive should be 

set to operate in constant torque mode. 

It is advisable that all three phase control panels be 

purchased from the factory.

If a panel is to be supplied locally, it is recommended that 

the Crane Pumps & Systems Pump Monitor Relay (P/N 

134667) be used to perform the control circuit functions for 

the Temperature and Moisture Sensor Monitoring described 

in sections B4.3 and B4.4. The Pump Monitor Relay was 

designed to perform these functions in a compact module 

that can be base or panel mounted and is resistant to noise 

issues found with some VFD’s. Indicator lights on the front 

display notify the operator in the event of a fault condition 

for either temperature, moisture or both. Normally open and 

normally closed contacts are flexible to accommodate nearly 

any wiring scenario and the moisture sensor sensitivity can 

be adjusted to prevent nuisance alarms.

SECTION: C START-UP OPERATION

C-1) Check Voltage and Phase:

 

Before operating pump, compare the voltage and phase 

information stamped on the pump’s identification plate to the 

available power.

C-2) Check Pump Rotation:

 

Before putting pump into service for the first time, the motor 

rotation must be checked. Improper motor rotation can result 

in poor pump performance and can damage the motor and/

or pump. To check the rotation, suspend the pump freely, 

momentarily apply power and observe the “kickback”. 

“Kickback” should always be in a counter-clockwise direction 

as viewed from the top of the pump motor housing and will 

always be in the opposite direction of the rotation arrows 

cast in the pump volute.

C-2.1) Incorrect Rotation for Three-Phase Pumps:

 

In the event that the rotation is incorrect for a three-phase 

installation, interchange any two power cable leads at 

the control box. Recheck the “kickback” rotation again by 

momentarily applying power.

C-2.2) Test Procedure For Moisture Sensor Control:

 

With a moisture detection control, a normally open push 

button is typically provided as a means of checking the 

moisture sensing components. When the push button is 

depressed, the probes will be shorted simulating water. 

While being held, the seal leakage indicating lamp will be 

illuminated to indicate (A) power is supplied to the control, 

(B) the control is operative, and (C) wiring to the moisture 

sensing probes in the pump is intact. This procedure should 

be performed periodically to confirm integrity of the circuit.

C-3) Start-Up Report:

 

Included at the end of this manual is one start-up report 

sheet, this sheet is to be completed as applicable. Return 

a copy to Barnes and store the second in the control panel 

or with the pump manual. It is important to record this data 

at initial start-up since it will be useful to refer to should 

servicing the pump be required in the future.

C-3.1) Identification Plate:

 

Record the numbers from the pump’s identification plate on 

the START-UP REPORT provided at the end of the manual 

for future reference.

Содержание 4SHD

Страница 1: ...223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 138551 Rev K 32 Frame 4SHM Monovane Pumps 75HP 1750RPM 4SHD Dual Vane Pumps 75 100HP 1750RPM 6SHV Vortex Pumps 75 100HP 1750RPM 50 75HP 1150RPM 40HP 870RPM 6SHM Monovane Pumps 75 100HP 1750RPM 6SHD Dual Vane Pumps 75 100HP 1750RPM 8SHVV Vortex Pumps 50 100HP 1150RPM 40 50HP 870RPM 8SHDU Dual Vane Pumps 75HP 1750RPM 8SHTM Tri Vane Pum...

Страница 2: ...MMENDED MINIMUM SUCTION CLEARANCE Fig 8 16 CROSS SECTIONS Fig 9 10 17 EXPLODED VIEW Fig 11 18 PARTS LISTS 19 31 WARRANTY 33 RETURNED GOODS POLICY 34 WARRANTY REGISTRATION 34 START UP REPORT 35 36 Other brand and product names are trademarks or registered trademarks of their respective holders Barnes is a registered trademark of Crane Pumps Systems Inc 1995 1997 1998 1 2004 4 05 1 06 3 06 9 06 12 0...

Страница 3: ...ar eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety devices in place Always replace safety devices that have been removed during service or repair Secure the pump in its operating position so it can not tip over fall or slide DO NOT exceed manufacturers recommendation for maximum performance as this cou...

Страница 4: ... in Piqua Ohio telephone 937 778 8947 or Crane Pumps Systems Canada in Brampton Ontario 905 457 6223 SECTION B INSTALLATION B 1 Location These self contained pumping units are recommended for use in a sump lift station or basin This pump is designed for submerged continuous duty 15 minutes duty in air at nameplate horsepower pumping sewage effluent wastewater or other nonexplosive or noncorrosive ...

Страница 5: ...rd assembly o ring onto the cord assembly as shown in Figure 2 Align the hole in the cord assembly with the alignment pin in the motor cap Lower the cord assembly into the bore of the motor cap taking care to keep the pins aligned Push the cord assembly into the motor housing until fully engaged Install the four 12mm socket head cap scews through the cord assembly into the motor cap Slowly tighten...

Страница 6: ...0 H 76 4 1 15 84 0 400 0 6 4 18 4 130 6SHVT50056 50 0 575 3 60 1150 H 61 2 1 15 67 2 320 0 6 4 18 4 189 6SHVT60046 60 0 460 3 60 1150 F 86 7 1 15 96 8 400 0 2 4 18 4 130 6SHVT60056 60 0 575 3 60 1150 F 69 4 1 15 77 4 320 0 6 4 18 4 189 6SHVT75046 75 0 460 3 60 1150 H 109 3 1 15 119 5 612 0 2 4 18 4 077 6SHVT75056 75 0 575 3 60 1150 H 87 4 1 15 95 6 489 6 2 4 18 4 113 6SHVT100046 100 0 460 3 60 115...

Страница 7: ... F 69 4 1 15 77 4 320 0 6 4 18 4 189 8SHVV75046 75 0 460 3 60 1150 H 109 3 1 15 119 5 612 0 2 4 18 4 077 8SHVV75056 75 0 575 3 60 1150 H 87 4 1 15 95 6 489 6 2 4 18 4 113 8SHVV100046 100 0 460 3 60 1150 E 135 0 1 0 135 0 612 0 2 4 18 4 077 8SHVV100056 100 0 575 3 60 1150 E 108 0 1 0 108 0 489 6 2 4 18 4 113 8SHVV40048 40 0 460 3 60 870 F 62 2 1 15 69 4 275 0 6 4 18 4 166 8SHVV40058 40 0 575 3 60 8...

Страница 8: ...0 460 3 60 1750 F 169 4 1 15 191 5 800 0 1 0 4 18 4 049 8SHTM125054 125 0 575 3 60 1750 F 135 6 1 15 153 2 640 0 2 4 18 4 065 8SHTM150044 150 0 460 3 60 1750 D 187 0 1 0 187 0 800 0 1 0 4 18 4 049 8SHTM150054 150 0 575 3 60 1750 D 159 5 1 0 159 5 640 0 1 0 4 18 4 065 8SHTM50046 50 0 460 3 60 1150 H 76 4 1 15 84 0 400 0 6 4 18 4 130 8SHTM50056 50 0 575 3 60 1150 H 61 2 1 15 67 2 320 0 6 4 18 4 189 ...

Страница 9: ...0 E 108 0 1 0 108 0 489 6 2 4 18 4 113 10SHDX40048 40 0 460 3 60 870 F 62 2 1 15 69 4 275 0 6 4 18 4 166 10SHDX40058 40 0 575 3 60 870 F 49 8 1 15 55 5 220 0 8 4 18 4 226 10SHDX50048 50 0 460 3 60 870 D 74 5 1 15 84 9 275 0 6 4 18 4 166 10SHDX50058 50 0 575 3 60 870 D 59 0 1 15 67 4 220 0 8 4 18 4 226 10SHTB 10SHTB50046 50 460 3 60 1150 H 76 4 1 15 84 0 400 0 6 4 18 4 0 13 10SHTB50056 50 575 3 60 ...

Страница 10: ...symbol An external ground screw is provided on the side of the motor cap which can be used for supplemental bonding connection where local codes permit or require such connection THREE PHASE 460 575 VOLT AC Power Cable Motor Lead ID Green Ground Green Black 1 Red 2 White 3 MOISTURE AND TEMPERATURE SENSORS MOISTURE AND TEMPERATURE SENSORS Control Cable Control Cable Lead ID Lead ID Black P1 Tempera...

Страница 11: ...UST be connected in series with the pilot circuit of the magnetic motor controller located in the control panel so that the thermostat will open the circuit before dangerous temperatures are reached A manual momentary start switch is required to prevent the automatic restarting of the motor when the thermostat resets refer to Figure 4 In the event of an over temperature condition the source of thi...

Страница 12: ... display notify the operator in the event of a fault condition for either temperature moisture or both Normally open and normally closed contacts are flexible to accommodate nearly any wiring scenario and the moisture sensor sensitivity can be adjusted to prevent nuisance alarms SECTION C START UP OPERATION C 1 Check Voltage and Phase Before operating pump compare the voltage and phase information...

Страница 13: ...amination using an oil tester with a range to 30 Kilovolts breakdown 3 If oil is found to be clean and uncontaminated measure above 15 KV breakdown refill the seal chamber as per section E 1 2 4 If oil is found to be dirty or contaminated or measures below 15 KV breakdown the pump must be carefully inspected for leaks at the shaft seal before refilling with oil To locate the leak perform a pressur...

Страница 14: ...eal If replacing seal remove stationary from mounting plate by prying out with flat screw driver E 3 2 Reassembly Lightly oil DO NOT use grease outer surface of stationary member Press stationary member firmly into mounting plate using a seal pusher aligning seal with pin nothing but the seal pusher is to come in contact with seal face See Fig 6 Make sure the stationary member is in straight and t...

Страница 15: ...F 3 MODEL NUMBER This designation consists of numbers and letters which represent the discharge size series horsepower motor phase and voltage speed and pump design This number is used for ordering and obtaining information F 4 SERIAL NUMBER The serial number block will consist of a six digit number which is specific to each pump and may be preceded by an alpha character which indicates the plant ...

Страница 16: ...eller for freedom of operation security and condition Clean impeller and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so that the suction is always flooded Clean vent hole 10 Check rotation If power supply is three phase reverse any two of three power supply leads to ensure proper impeller rotation 11 Repair fixtures as...

Страница 17: ...LEARANCE BASED ON HYDRAULIC INSTITUTE STANDARD 9 8 2 3 2 2 FIGURE 8 MODEL NUMBER DIM A INCHES MM 3SHVC 3XSHVC 3 00 76 2 3SHVR 3XSHVR 3SHVRA 3XSHVRA 3 50 88 9 3SHMPA 3XSHMPA 4SHMS 4XSHMS 3 75 95 3 4SHDF 4XSHDF 4SHVA 4XSHVA 4 00 101 6 4SHVB 4XSHVB 4SHVBA 4XSHVBA 4 25 108 4SHMC 4XSHMC 4SHDG 4XSHDG 4SHMD 4XSHMD 4 75 120 7 6SHVL 6XSHVL 5 25 133 4 6SHDO 6XSHDO 5 50 139 7 4SHMB 4XSHMB 6 00 152 4 4SHME 4X...

Страница 18: ...18 FIGURE 9 SH Pump Series CROSS SECTIONS FIGURE 10 SH Vortex SH Enclosed ...

Страница 19: ...19 SH Enclosed Pump Series EXPLODED VIEWS FIGURE 11 ...

Страница 20: ...r Impeller 75 X 2 44 18 8 SS 9 1 M 6614 O Ring 465 18 0 ID Buna N 9 1 125857 360 O Ring M3 x 360 70 DURO Buna N 9 1 125857 295 O Ring M3 x 295 70 DURO Buna N 9 1 018386 O Ring 276 10 98 ID Buna N 9 1 2 31003 281 O Ring 281 14 98 ID Buna N 9 1 2 31003 282 O Ring 282 15 96 ID Buna N 10 1 See Table Volute Cast Iron 11 2 See Table Volute Wear Ring as required Bronze 11A 2 See Table ƒ Impeller Wear Rin...

Страница 21: ...sale Oil Cooling Oil SH 32 Frame PARTS LIST SH Pump Plug and Play Removeable Cord Assemblies Part No Length feet Cord Size Max Amps Cord O D 138317XF 50 8 4 18 4 59 0 1 12in 02in 28 4mm 5mm 138317XJ 75 8 4 18 4 59 0 1 12in 02in 28 4mm 5mm 138317XL 100 8 4 18 4 59 0 1 12in 02in 28 4mm 5mm 138318XF 50 6 4 18 4 79 0 1 14in 03in 28 9mm 8mm 138318XJ 75 6 4 18 4 79 0 1 14in 03in 28 9mm 8mm 138318XL 100 ...

Страница 22: ...1 370 140595 N A 125857 360 6SHVT 465mm 138109 140145 138051 465 140596 N A M 6614 6SHMN 370mm Not Available in 32 Frame 6SHMH 370mm 6SHMJ 370mm 130830 138603 138051 370 140595 130833 125857 360 6SHDO 305mm Not Available in 32 Frame 6SHDK 370mm 130830 138604 138051 370 140595 130834 125857 360 8SHVV 465mm 138107 140147 138051 465 140596 N A M 6614 8SHDU 305mm 138108 140148 138051 305 140597 138999...

Страница 23: ...8928TH 143368TH 325mm 12 80in 138928TJ 143368TJ 320mm 12 60in 138928TK 143368TK 315mm 12 40in 138928TL 143368TL 310mm 12 20in 138928TM 143368TM 305mm 12 01in 138928TN 143368TN 300mm 11 81in 138928TP 143368TP 295mm 11 61in 138928TR 143368TR 290mm 11 42in 138928TS 143368TS 285mm 11 22in 138928TT 143368TT 280mm 11 02in 138928TU 143368TU 275mm 10 83in 138928TV 143368TV 270mm 10 63in 138928TW 143368TW ...

Страница 24: ... 143372TG 330mm 12 99in 138932TH 143372TH 325mm 12 80in 138932TJ 143372TJ 320mm 12 60in 138932TK 143372TK 315mm 12 40in 138932TL 143372TL 310mm 12 20in 138932TM 143372TM 305mm 12 01in 138932TN 143372TN 300mm 11 81in 138932TP 143372TP 295mm 11 61in 138932TR 143372TR 290mm 11 42in 138932TS 143372TS 285mm 11 22in 138932TT 143372TT 280mm 11 02in 138932TU 143372TU 275mm 10 83in 138932TV 143372TV 270mm ...

Страница 25: ...P 143294TP 380mm 14 96in 138101TQ 143294TQ 375mm 14 76in 138101TR 143294TR 370mm 14 57in 138101TS 143294TS 365mm 14 37in 138101TT 143294TT 360mm 14 17in 138101TU 143294TU 355mm 13 98in 138101TV 143294TV 350mm 13 78in 138101TW 143294TW 345mm 13 58in 138101TX 143294TX 340mm 13 39in 138101TY 143294TY 335mm 13 19in 138101TZ 143294TZ 330mm 12 99in 138101UA 143294UA 325mm 12 80in 138101UB 143294UB 320mm...

Страница 26: ...Part No Nihard Part No 305mm 12 00in 138102 KIT 143293 300mm 11 81in 138102TA KIT 143293TA 295mm 11 61in 138102TB KIT 143293TB 290mm 11 42in 138102TC KIT 143293TC 285mm 11 22in 138102TD KIT 143293TD 280mm 11 02in 138102TE KIT 143293TE 275mm 10 82in 138102TF KIT 143293TF 270mm 10 63in 138102TG KIT 143293TG 265mm 10 43in 138102TH KIT 143293TH 260mm 10 24in 138102TJ KIT 143293TJ 255mm 10 04in 138102T...

Страница 27: ...l Bearing Lower Ball Bearing Wavy Spring Washer Retaining Rings Volute Kit includes Wear Ring if required pressed Volute painted Seal Plate Kit includes Spring Pin Pipe Plug Seal Plate painted Hardware Kit includes Socket Head Cap Screws for Motor Cap Impeller Bolt and Washer Set Socket Head Cap Screws for Upper Seal Plate and Bearing Bracket Socket Head Cap Screws for Motor Leads Socket Head Cap ...

Страница 28: ... 3 15 80 3SHVR 125506 3 15 80 3SHVRA 125506 3 15 80 3SHMPA 125506 3 15 80 4SHMS 125506 3 15 80 4SHDF 125506 3 15 80 4SHVA 125506 3 15 80 4SHVB 125506 3 15 80 4SHVBA 125506 3 15 80 4SHMC 125506 3 15 80 4SHDG 125506 3 15 80 4SHMD 125506B 6 50 165 6SHVL 125506 3 15 80 6SHDO 125506B 6 50 165 4SHMB 125506B 6 50 165 4SHME 125506B 6 50 165 4SHMEA 125506B 6 50 165 4SHDI 125506B 6 50 165 6SHMN 125506B 6 50...

Страница 29: ...H 50056 140260 140261 SH 60046 140264 140265 SH 60056 140266 140267 SH 75046 140270 140271 SH 75056 140274 140275 SH 100046 140278 140279 SH 100056 140285 140286 Example Model No Rotor Kit Part No Stator Motor Housing Kit Part No 4SHVB30092 131980 132056 Rotor Kit includes Rotor Retaining Ring Stator Motor Housing Kit includes Motor Housing painted Stator Dowel Pin Replaces Pin Spring Pipe Plug 87...

Страница 30: ...0 140601 140611 140604 125506B SEE TABLE ON PAGES 23 26 140152 32 6SHVT50056 140260 140261 140607 140145 140596 140609 138613 140620 140601 140611 140604 125506B 140152 32 6SHVT60046 140264 140265 140607 140145 140596 140609 138613 140620 140601 140611 140604 125506B 140152 32 6SHVT60056 140266 140267 140607 140145 140596 140609 138613 140620 140601 140611 140604 125506B 140152 32 6SHVT75046 14027...

Страница 31: ...40147 140596 140609 138613 140620 140601 140611 140604 125506C 140152 32 8SHVV40058 140254 140255 140607 140147 140596 140609 138613 140620 140601 140611 140604 125506C 140152 32 8SHVV50048 140258 140259 140607 140147 140596 140609 138613 140620 140601 140611 140604 125506C 140152 32 8SHVV50058 140262 140263 140607 140147 140596 140609 138613 140620 140601 140611 140604 125506C 140152 32 8SHDU7504...

Страница 32: ...01 140611 140604 125506C 140152 32 8SHTM40048 140252 140253 140607 138607 140595 140609 138613 140620 140601 140611 140604 125506C 140152 32 8SHTM40058 140254 140255 140607 138607 140595 140609 138613 140620 140601 140611 140604 125506C 140152 32 10SHDW50046 140256 140257 140614 140613 140615 140616 140617 140618 140607 138149 140595 140609 138613 140620 140601 140611 140604 125506C SEE TABLE ON P...

Страница 33: ...0SHTB60046 140264 140265 140607 143928 140596 140609 138613 140620 140601 140611 140604 125506C 140152 32 10SHTB60056 140266 140267 140607 143928 140596 140609 138613 140620 140601 140611 140604 125506C 140152 32 10SHTB75046 140270 140271 140607 143928 140596 140609 138613 140620 140601 140611 140604 125506C 140152 32 10SHTB75056 140274 140275 140607 143928 140596 140609 138613 140620 140601 14061...

Страница 34: ...Notes ...

Страница 35: ...support any Warranty claims This Warranty shall not apply to any product or part of product which has been subject to misuses negligence accident operation outside of our published hydraulic curve parameters used in a manner contrary to printed Instructions or damaged due to a defective power supply improper electrical protection excessive abrasive wear or faulty installation or repair THE SOLE AN...

Страница 36: ... Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty To complete the Warranty Registration Form go to http www cranepumps com ProductRegistration If you have a claim under the provision of the warranty contact your local Crane Pumps Systems Inc Distributor IMPORTANT WARRANTY INFORMATION W...

Страница 37: ...__ Type _________________________________ Number and size of short circuit device s ___________ Amp rating ___________________ Overload Type _____________ Size ______________ Amp rating ___________________ Do protection devices comply with pump and motor Amp rating YES___ NO___ Are all electrical and panel entry connections tight YES___ NO___ Is the interior of the panel dry YES___ NO___ Liquid le...

Страница 38: ...controls installed away from turbulence YES___ NO___ Is level control operating properly YES___ NO___ Is pump fully submerged during operation YES___ NO___ Follow up Corrective Action Required YES___ NO___ Additional Comments ____________________________________________________________________________ ____________________________________________________________________________ ____________________...

Отзывы: