- 48 -
V - SETTINGS OF THE INSTALLATION TYPES
The outside sensor is necessary and
must be connected to the LMU (terminal
X10-06).
The QAA 73 room sensor is required to
access the settings and to adjust them
(§ 3 - page 50).
The boiler’s standard setup is used for the connec-
tion of:
- a Radiator circuit (CC1) controlled by the boi-
ler’s LMU,
- an Under-floor heating circuit (CC2) by using the
clip-in 2nd circuit kit (the HydrSystem setting
must be modified via the QAA73 - refer to table
fig. 56 - page 49).
1 - SINGLE CIRCUIT
Note:
- In the case of a single circuit (CC1) either a radia-
tor circuit or an under floor heating circuit
- However if the boiler directly supplies an under
floor heating circuit:
• The QAA 73 settings need changing in accor-
dance with the table above.
• For recommendations refer to section § 5.3 -
page 42 - chapter IV - INSTALLATION.
Necessary accessories
.
!
LMU
D
T
H
I-
86-
0
B3
TKS
CC 1
QAA 73*
QAC 34
Q
VS
BS
Fig. 55
FACTORY SETTINGS QAA73
QAA 73 SETTINGS TO CHANGE
Function
Radiator circuit (CC1)
Under-floor heating circuit (CC1)
line QAA73
Value
line QAA73
Value
Slope
70
15
70
8
Tmax
72
80°C
72
50°C
Parallel shift
73
0
73
0
Room influence
75
CC1
75
CC1
Accessories list
Reference
A room temperature sensor (QAA 73)
REG 73