8.
TANK ON
When “t ON”
(Figure R-7)
appears, place tank on scale, press
, open
valves. Turn ON Recovery Machine (follow manufacturer’s instructions), and
quickly press and release the SVW On/Off button to start recovery.
9.
REMAINING CAPACITY OF TANK
Display will show “r”
(Figure R-8)
indicating recovery in process, alongside
the remaining tank refrigerant weight capacity (until full). Display will count
backwards from remaining tank capacity
CAUTION: OVERFILLING
RECOVERY TANK MAY RESULT IN SERIOUS INJURY
.
10.
TANK FILL LIMIT REACHED (OR EXCEEDED)
While recovering refrigerant, be ready to turn OFF recovery machine
and/or CLOSE valves, while constantly monitoring the display so that
the tank will NOT be overfilled.
Characters will flash if tank overfill has
ocurred and a “negative” symbol will appear next to the “o” symbol,
(Figure R-9)
indicating the tank has been overfilled by the amount
indicated on the display.
10.1
If characters flash, the user may press
once to stop the flashing.
Turn OFF recovery machine and/or CLOSE valves. The user may
change tanks, then press
again to restart recovery tracking.
11.
HOLD FUNCTION
At any point during recovery, pressing
will activate the HOLD function.
During HOLD indicated by “h”
(Figure R-10)
, the remaining tank capacity
will update if the weight is changed, but the net gain will not account for
any additional recovery during hold.
NOTE: Remember to physically stop
recovering refrigerant by pressing the SVW On/Off button while
activating HOLD.
3.
“SV” will appear in upper right corner of CC220EW display if scale
and SVW have made wireless connection.
a.
If the SVW does not connect to the CC220EW:
b.
Press
on the CC220EW control 6 times until “SOL”
appears on the display.
c.
Press
.
d.
The CC220EW will scan for an SVW that powered on. If none
found, “nOnE” will appear.
e.
If an SVW device is located, its ID# will appear on the scale display,
then
press .
f.
After a few seconds, “SV” should appear in the upper right of the
CC220EW
display.
4.
Connect equipment per
DIAGRAM B (RECOVER)
but
DO NOT PLACE TANK ON SCALE AT THIS TIME
5.
Press
to scroll through menu and choose Recover “rEC”.
6.
For tank you will use, press
to input a combined Tank Weight
& Water Capacity Weight both stamped individually on the tank collar
(but use TW + 0.8 X WC for final value to enter), then press
.
• WC = Water Capacity (weight);
• TW = Tank Weight (of empty tank)
7.
TANK OFF
When “t OFF” appears
(Figure R-6)
ensure tank is
NOT
on scale, press
.
CAUTION: DO NOT PLACE TANK ON PLATFORM BEFORE STEP 8. DOING SO COULD LEAD TO OVER-
FILLING THE REFRIGERANT TANK. DANGER - THE RECOVERY TANK CONTAINS LIQUID REFRIGER-
ANT. OVERFILLING OF THE RECOVERY TANK MAY CAUSE A VIOLENT EXPLOSION RESULTING IN
SEVERE INJURY OR EVEN DEATH.
AUTOMATIC RECOVERY (Cont’d)
Fig. R-6
Fig. R-7
Fig. R-8
(Example Weight Shown)
Fig. R-9
(Example Weight Shown)
AUTOMATIC RECOVERY (Cont’d)
Fig. R-10
(Example Weight Shown)
+
+
+
+
+
+
DIAGRAM B (RECOVER)
Yellow
Yellow
Blue
Red
IN
OUT