CPS SVW Скачать руководство пользователя страница 7

12

13

8.

 

TANK ON

  When “t ON” 

(Figure R-7)

 appears, place tank on scale, press 

, open

  valves. Turn ON Recovery Machine (follow manufacturer’s instructions), and
  quickly press and release the SVW On/Off button to start recovery.

9.

  

REMAINING CAPACITY OF TANK

  Display will show “r” 

(Figure R-8)

 indicating recovery in process, alongside

  the remaining tank refrigerant weight capacity (until full). Display will count
  backwards from remaining tank capacity 

CAUTION: OVERFILLING

  RECOVERY TANK MAY RESULT IN SERIOUS INJURY

.

10.

 

TANK FILL LIMIT REACHED (OR EXCEEDED)

  While recovering refrigerant, be ready to turn OFF recovery machine
  and/or CLOSE valves, while constantly monitoring the display so that
  the tank will NOT be overfilled.

 Characters will flash if tank overfill has

 ocurred and a “negative” symbol will appear next to the “o” symbol,
 

(Figure R-9)

 indicating the tank has been overfilled by the amount

  indicated on the display.

10.1 

If characters flash, the user may press 

 once to stop the flashing.

    Turn OFF recovery machine and/or CLOSE valves.  The user may
    change tanks, then press 

 again to restart recovery tracking.

11.

 

HOLD FUNCTION

  At any point during recovery, pressing 

 will activate the HOLD function.

  During HOLD indicated by “h” 

(Figure R-10)

, the remaining tank capacity

  will update if the weight is changed, but the net gain will not account for
  any additional recovery during hold. 

NOTE: Remember to physically stop

  recovering refrigerant by pressing the SVW On/Off button while

  activating HOLD.

3. 

“SV” will appear in upper right corner of CC220EW display if scale

  and SVW have made wireless connection.
 

a.

  If the SVW does not connect to the CC220EW: 

 

b.

 Press 

 on the CC220EW control 6 times until “SOL”

    appears on the display.
 

c.

 Press 

.

 

d.

  The CC220EW will scan for an SVW that powered on. If none

    found, “nOnE” will appear. 
 

e.

  If an SVW device is located, its ID# will appear on the scale display,

  then 

press  . 

 

f.

  After a few seconds, “SV” should appear in the upper right of the

  CC220EW 

display.

4.

  Connect equipment per 

DIAGRAM B (RECOVER)

 but 

DO NOT PLACE TANK ON SCALE AT THIS TIME

5.

 Press 

 to scroll through menu and choose Recover “rEC”.

6.

  For tank you will use, press

 

 to input a combined Tank Weight

  & Water Capacity Weight both stamped individually on the tank collar
  (but use TW + 0.8 X WC for final value to enter), then press 

 .

•  WC = Water Capacity (weight); 
•  TW = Tank Weight (of empty tank)

7.

 

TANK OFF

  When “t OFF” appears 

(Figure R-6)

 ensure tank is 

NOT

 on scale, press 

.

CAUTION: DO NOT PLACE TANK ON PLATFORM BEFORE STEP 8. DOING SO COULD LEAD TO OVER-
FILLING THE REFRIGERANT TANK. DANGER - THE RECOVERY TANK CONTAINS LIQUID REFRIGER-
ANT. OVERFILLING OF THE RECOVERY TANK MAY CAUSE A VIOLENT EXPLOSION RESULTING IN 

SEVERE INJURY OR EVEN DEATH.

AUTOMATIC RECOVERY (Cont’d)

Fig. R-6

Fig. R-7

Fig. R-8

(Example Weight Shown)

Fig. R-9

(Example Weight Shown)

AUTOMATIC RECOVERY (Cont’d)

Fig. R-10

(Example Weight Shown)

+

+

+

+

+

+

DIAGRAM B (RECOVER)

Yellow

Yellow

Blue

Red

IN

OUT

Содержание SVW

Страница 1: ...arge Recover Evacuate With Precision Download App Now CPS Link OWNER S MANUAL English Latest updates www cpsproducts com TO BE OPERATED BY QUALIFIED PERSONNEL ONLY Patented Wireless Technology Patent 9 043 161 Version 4 3 or higher ...

Страница 2: ...VIEW 5 Charge Recovery or Evacuation 5 Automatic Charge Or Recovery 5 SVW KEY FEATURES 6 ADDITIONAL FEATURES IF SVW PAIRED TO A MOBILE DEVICE SVW CPS Link App 6 SVW LAYOUT 6 SVW SPECIFICATIONS 7 SVW QUICK START INSTRUCTIONS 8 CC220EW SCALE QUICK START INSTRUCTIONS 8 ABBREVIATIONS ON CC220EW SCALE DISPLAY 9 AUTOMATIC CHARGE SVW CC220EW Scale 10 AUTOMATIC RECOVERY SVW CC220EW Scale 11 AUTOMATIC OPER...

Страница 3: ...rant being recovered and constantly monitor the scale display CAUTION Mixing of different refrigerants will cause your recovered supply of refrigerant to become contaminated CAUTION Read and follow manufacturer s instructions when using equipment referenced in this manual CAUTION During refrigerant charging and recovery the user must monitor the weight shown on the scale and or mobile device displ...

Страница 4: ...ntil LED turns OFF Release button Cycle Solenoid ON OFF While SVW ON Press and release pulse the button Auto Power Off ENABLED SVW turns OFF after set period of inactivity default 10 mins Auto Power Off DISABLED Disable via APP Charge Recover Alarms In CC220EW control and mobile device Transmission Range Line Of Sight Up to 150 feet Frequency Range 2400 to 2480 MHz Power Source 9V Alkaline Include...

Страница 5: ...rocess o Tank overfilled n Net gain of one or more tanks Charge or Recover h Hold pause refrigerant tracking Err Scale Malfunction All Modes OL Overload Reduce load immediately SV SVW wireless connection to CC220EW Scale CC220EW SCALE QUICK START INSTRUCTIONS Cont d 1 For charge or recovery procedures reference manufacturer s instructions for using required equipment 2 Remove scale from storage ca...

Страница 6: ...ystem removed from the refrigerant tank DIAGRAM A CHARGE Fig C 4 Example Weight Shown 9 During charging screen characters will eventually flash at an increasing rate showing that the programmed charge amount is closer to being reached HOLD Pressing while charging will PAUSE charge and the tracked amount allowing the user to tighten hoses change tanks if necessary but continue later without losing ...

Страница 7: ...ecovery during hold NOTE Remember to physically stop recovering refrigerant by pressing the SVW On Off button while activating HOLD 3 SV will appear in upper right corner of CC220EW display if scale and SVW have made wireless connection a If the SVW does not connect to the CC220EW b Press on the CC220EW control 6 times until SOL appears on the display c Press d The CC220EW will scan for an SVW tha...

Страница 8: ... show the net gain indicated by n Figure R 11 The recovery feature will track the net gain during the recovery session except during Hold including even after overfill is reached so that the exact total net gain will be known 13 IF RECOVERING REFRIGERANT INTO MORE THAN ONE TANK If recovering refrigerant into more than one tank of the same capacity without reaching overfill press the SVW button onc...

Страница 9: ...age Units Etc Selection will apply to all CPS wireless devices used Specific Device Settings Select settings that apply to a specific CPS wireless device Tools Screen My Customers Add or change customer information My Jobs Access information from previous jobs Tank Tracker Manage data related to your inventory of refrigerant tanks Data Logging Access data logged by other CPS wireless products SCRE...

Страница 10: ...ill be viewed on the scale s control Follow QUICK START Instructions on page 17 Follow QUICK START Instructions on page 17 Follow on screen instructions Note 1 Not all screens in the RECOVERY sequence are shown above 2 This operation can also be performed using the scale with corded control display AUTOMATIC RECOVERY 3 4 Exit app when done RECOVER in process 5 5 7 6 3 If mobile device loses connec...

Страница 11: ...ion can still be viewed on the scale s control Follow on screen instructions AUTOMATIC RECOVERY Using Tank Tracker Place known RECOVERY TANK on scale and select its description 3 4 7 6 Note 1 Not all screens in the RECOVERY sequence are shown above 2 This operation can also be performed using the scale with corded control display 3 If mobile device loses connection with CC220EW recover numerical i...

Страница 12: ... equipment should fail during the guarantee period it will be repaired or replaced at our option at no charge This guarantee does not apply to equipment that has been altered misused or solely in need of field service mainte nance All repaired equipment will carry an independent 90 day warranty This repair policy does not include equipment that is determined to be beyond economical repair WARRANTY...

Страница 13: ...www cpsproducts com 73 795 Rev A ...

Отзывы: