AUTOMATIC CHARGE

The SVW is excellent for charging precise amounts of refrigerant.  

1. 

For initial set-up of the SVW and CC220EW, follow the QUICK START Instructions on pages 8-9.

2.

  Activate the SVW first, then the CC220EW.

3. 

“SV” will appear in upper right corner of CC220EW display if Scale and SVW have made wireless connection.

 

a.

  If the SVW does not connect to the CC220EW: 

 

b.

 Press 

 on the CC220EW control 6 times until “SOL”

    appears on the display.
 

c.

 Press 

.

 

d.

  The CC220EW will scan for an SVW that is powered on. If none

    found, “nOnE” will appear. 
 

e.

  If an SVW device is located, its ID# will appear on the scale display,

  then 

press  . 

 

f.

  After a few seconds, “SV” should appear in the upper right of the

  CC220EW 

display.

4.

  Place refrigerant tank on scale

5.

  Connect equipment per 

DIAGRAM A

.

6.

 Press 

 to scroll through the menu and choose CHARGE “CHg”.

7.

 Use 

  

 to input desired weight (charge amount), then

 press

(Figure C-4)

8.

  Open tank and manifold valves, then press and quickly release

  the SVW 

 button. The charge (tracking) session will begin.

  The display will show a small “c”indicating “charge” and how
  much refrigerant has been charged into your system (removed
  from the refrigerant tank).

DIAGRAM A (CHARGE)

Fig. C-4

(Example Weight Shown)

9.

  During charging, screen characters will eventually flash at an increasing rate, showing that the

  programmed charge amount is closer to being reached.

• 

HOLD

 - Pressing 

 while charging will PAUSE charge, and the tracked amount, allowing the 

user to tighten hoses, change tanks if necessary, but continue later without losing track of the NET 
amount charged.

• 

SET/RESET

 - Pressing 

 during charge operation will stop/cancel the charge. The normal 

WEIGH Mode will resume.

• 

GO/HOLD

 - After any adjustments are made, charging and the accumulated

   amount being tracked can be resumed by pressing 

.

10.

 

When programmed charge amount (weight) has been reached, the

  screen will flash a large “F” (FINAL) (Figure C-7) and the control will
  “beep”.

11.

 Press 

 to end session.

12.

 SHUT DOWN - When CHARGE function done, Press and hold SVW 

  button until GREEN light turns OFF, close valves, remove cylinder from
  platform. Press 

 to turn scale OFF.

The SVW is excellent for recovering a specified amount of refrigerant and helps prevent overfilling 
recovery tanks.

1. 

For initial set-up of the SVW and CC220EW, follow the QUICK START Instructions on pages 8-9.

2.

  Activate the SVW first, then the CC220EW.

AUTOMATIC CHARGE (Cont’d)

Fig. C-7

(Example Weight Shown)

AUTOMATIC RECOVERY

Yellow

Blue

Red

IN

OUT

Содержание SVW

Страница 1: ...arge Recover Evacuate With Precision Download App Now CPS Link OWNER S MANUAL English Latest updates www cpsproducts com TO BE OPERATED BY QUALIFIED PERSONNEL ONLY Patented Wireless Technology Patent 9 043 161 Version 4 3 or higher ...

Страница 2: ...VIEW 5 Charge Recovery or Evacuation 5 Automatic Charge Or Recovery 5 SVW KEY FEATURES 6 ADDITIONAL FEATURES IF SVW PAIRED TO A MOBILE DEVICE SVW CPS Link App 6 SVW LAYOUT 6 SVW SPECIFICATIONS 7 SVW QUICK START INSTRUCTIONS 8 CC220EW SCALE QUICK START INSTRUCTIONS 8 ABBREVIATIONS ON CC220EW SCALE DISPLAY 9 AUTOMATIC CHARGE SVW CC220EW Scale 10 AUTOMATIC RECOVERY SVW CC220EW Scale 11 AUTOMATIC OPER...

Страница 3: ...rant being recovered and constantly monitor the scale display CAUTION Mixing of different refrigerants will cause your recovered supply of refrigerant to become contaminated CAUTION Read and follow manufacturer s instructions when using equipment referenced in this manual CAUTION During refrigerant charging and recovery the user must monitor the weight shown on the scale and or mobile device displ...

Страница 4: ...ntil LED turns OFF Release button Cycle Solenoid ON OFF While SVW ON Press and release pulse the button Auto Power Off ENABLED SVW turns OFF after set period of inactivity default 10 mins Auto Power Off DISABLED Disable via APP Charge Recover Alarms In CC220EW control and mobile device Transmission Range Line Of Sight Up to 150 feet Frequency Range 2400 to 2480 MHz Power Source 9V Alkaline Include...

Страница 5: ...rocess o Tank overfilled n Net gain of one or more tanks Charge or Recover h Hold pause refrigerant tracking Err Scale Malfunction All Modes OL Overload Reduce load immediately SV SVW wireless connection to CC220EW Scale CC220EW SCALE QUICK START INSTRUCTIONS Cont d 1 For charge or recovery procedures reference manufacturer s instructions for using required equipment 2 Remove scale from storage ca...

Страница 6: ...ystem removed from the refrigerant tank DIAGRAM A CHARGE Fig C 4 Example Weight Shown 9 During charging screen characters will eventually flash at an increasing rate showing that the programmed charge amount is closer to being reached HOLD Pressing while charging will PAUSE charge and the tracked amount allowing the user to tighten hoses change tanks if necessary but continue later without losing ...

Страница 7: ...ecovery during hold NOTE Remember to physically stop recovering refrigerant by pressing the SVW On Off button while activating HOLD 3 SV will appear in upper right corner of CC220EW display if scale and SVW have made wireless connection a If the SVW does not connect to the CC220EW b Press on the CC220EW control 6 times until SOL appears on the display c Press d The CC220EW will scan for an SVW tha...

Страница 8: ... show the net gain indicated by n Figure R 11 The recovery feature will track the net gain during the recovery session except during Hold including even after overfill is reached so that the exact total net gain will be known 13 IF RECOVERING REFRIGERANT INTO MORE THAN ONE TANK If recovering refrigerant into more than one tank of the same capacity without reaching overfill press the SVW button onc...

Страница 9: ...age Units Etc Selection will apply to all CPS wireless devices used Specific Device Settings Select settings that apply to a specific CPS wireless device Tools Screen My Customers Add or change customer information My Jobs Access information from previous jobs Tank Tracker Manage data related to your inventory of refrigerant tanks Data Logging Access data logged by other CPS wireless products SCRE...

Страница 10: ...ill be viewed on the scale s control Follow QUICK START Instructions on page 17 Follow QUICK START Instructions on page 17 Follow on screen instructions Note 1 Not all screens in the RECOVERY sequence are shown above 2 This operation can also be performed using the scale with corded control display AUTOMATIC RECOVERY 3 4 Exit app when done RECOVER in process 5 5 7 6 3 If mobile device loses connec...

Страница 11: ...ion can still be viewed on the scale s control Follow on screen instructions AUTOMATIC RECOVERY Using Tank Tracker Place known RECOVERY TANK on scale and select its description 3 4 7 6 Note 1 Not all screens in the RECOVERY sequence are shown above 2 This operation can also be performed using the scale with corded control display 3 If mobile device loses connection with CC220EW recover numerical i...

Страница 12: ... equipment should fail during the guarantee period it will be repaired or replaced at our option at no charge This guarantee does not apply to equipment that has been altered misused or solely in need of field service mainte nance All repaired equipment will carry an independent 90 day warranty This repair policy does not include equipment that is determined to be beyond economical repair WARRANTY...

Страница 13: ...www cpsproducts com 73 795 Rev A ...

Отзывы: