65
PFCurvePF1
(-0.800, 1.000, 0.800)
See Figure 5-17
PFCurveP2(%)
(0, 100.0%, 100.0%)
See Figure 5-17
PFCurvePF2
(-0.800, -0.900, 0.800)
See Figure 5-17
PFCurvTripV(V)
(480.0, 480.0, 528.0)
PF curve trip
voltage
PFCurveReV(V)
(422.4, 432.0, 480.0)
PF curve revocation
voltage
Q(U)
QuCurveU1(V)
(480.0, 518.4, 528.0)
See Figure 5-18
QuCurveQ1(%)
(-100.0%, 0.0%, 100.0%)
See Figure 5-18
QuCurveU2(V)
(480.0, 528.0, 528.0)
See Figure 5-18
QuCurveQ2(%)
(-100.0%, -50.0%,
100.0%)
See Figure 5-18
QuCurveU1i(V)
(422.4, 441.6, 480.0)
See Figure 5-18
QuCurveQ1i(%)
(-100.0%, 0.0%, 100.0%)
See Figure 5-18
QuCurveU2i(V)
(422.4, 432.0, 480.0)
See Figure 5-18
QuCurveQ2i(%)
(-100.0%, 50.0%,
100.0%)
See Figure 5-18
QuCurvTripP(%)
(5.0%, 20.0%, 100.0%)
Qu curve trip power
QuCurveReP(%)
(5.0%, 5.0%, 100.0%)
Qu curve revocation
power
3.
“FreqDeratCtrl” menu: Set up the parameters of over-frequency active
power deraring.
(4)
”5 LVRTSet” menu: set up the parameters of LVRT.
INSTRUCTION:
The
“FreqDeratCtrl” function is not available for the IEEE-1547 grid
standard.