60
5.4.8 System control parameters
The
“1 SysPara” menu has 6 submenus, including ”1 GridVProtect”, ”2
GridFProtect”, ”3 ON/OFF”, ”4 PowerContr”, ”5 LVRTSet” and ”6
OtherProtect”.
(1)
”1 GridVProtect” and ”2 GridFProtect” menus: Set up the parameters of
grid voltage, frequency protection and recovery, etc, as shown in Table 5-3:
Table 5-3 Parameters of grid voltage and frequency (IEEE-1547)
Parameter name
Description
Setup range (lower limit,
default & upper limit)
GridV.Max1(V)
Threshold value of Level 1
Max. grid voltage
{200.0, 528.0, 552.0}
VMaxTripT1(S)
Threshold value of Level 1
Max. grid trip voltage
{0, 1.00, 600.00}
GridV.Min1(V)
Threshold value of Level 1
Min. grid voltage
{0, 422.4, 480.0}
VMinTripT1(S
)
Threshold value of Level 1
Min. grid trip voltage
{0, 2.00, 600.00}
GridV.Max2(V)
Threshold value of Level 2
Max. grid voltage
{480.0, 576.0, 624.0}
VMaxTripT2(S)
Threshold value of Level 2
Max. grid trip voltage
{0, 0.16, 600.00}
GridV.Min2(V)
Threshold value of Level 2
Min. grid voltage
{240.0, 240.0, 480.0}
VMinTripT2(S)
Threshold value of Level 2
Min. grid trip voltage
{0, 0.16, 600.00}
GridVmaxRecT(V)
Recovery threshold value of {200.0, 518.0, 533.0}
permitted.