page 8
Push button adjustment
Time, Lux and Sensitivity
Press and hold either button for at least 5 seconds then release: one of the LED‘s positioned
behind the lens will flash to show which function has been selected.
The LED will flash a number of times (between 1 and 7) to indicate the current setting
(minimum = 1 flash, maximum = 7 flashes).
To change between Time (green), Lux (red) and Sensitivity (yellow) press and release the func-
tion button until the required LED shows.
When the function has been selected press the adjustment button to increase the setting by 1
step. Pressing the button after reaching 7 flashes will return the setting to 1 flash.
Time settings are as follows: 1 flash = 1 minute; 2 flashes = 5 min.; 3 flashes = 10 min.; 4
flashes = 15 min.; 5 flashes = 20 min.; 6 flashes = 25 min.; 7 flashes = 30 min.
Lux settings
EBMPIR-PRM—1 flash turns on when very dark ; 7 flashes turns on regardless of ambient light.
EBMPIR-DD & EBMPIR-AD—1 flash gives dim output level; 7 flashes gives maximum illumi-
nance.
Sensitivity: 1 flash minimum; 7 flashes maximum.
After finishing adjustment, the LED will show the new setting 5 times and then return to opera-
tional mode.
Default settings
Pressing and hold both buttons together: after 3 seconds the green LED lights. Release immedi-
ately to restore the factory settings.
Absence/Presence mode
To check the mode press and hold both buttons together: after 3 seconds the green LED lights—
leave the buttons pressed. After a further 3 seconds the following LEDs will light:
Green/Yellow = Presence Detection mode
Green/Red = Absence detection mode
To accept the current mode release the buttons immediately.
To change the mode keep the buttons pressed for another 5 seconds until the LEDs change, then
release.
Function button
Adjust button
Green LED—time
Red LED—lux
Yellow LED—sensitivity