7.  Detection Patterns

 

8.  Fault Finding 

LOAD DOES NOT COME ON 

 
 
Check to see if the live supply to the circuit is good. 
Strap across the 

and 

LIVE OUT 

terminal to turn 

the load on. 
 
If the supply and wiring are good, check the LUX 
level setting. Increase the LUX level setting to allow 
the controller to turn on at higher ambient natural 
light level. 
 
If the detection range is smaller than expected, 
check the diagram above. Rotating the sensor 
slightly may improve the range. 

 

LIGHTS DO NOT GO OFF 

 
Ensure that the area is left unoccupied for longer 
than the selected timer setting. 
 
Make sure that the sensor is not adjacent to circulat-
ing air, heaters or lamps. 
 
If the unit ―false triggers‖ reduce the sensitivity using 
the sensitivity settings (see section 5 and 6). 

 

 

Содержание EBMPIR

Страница 1: ...all of which will switch incandescent fluorescent and compact fluorescent lighting The direct dim variant controls DSI or DALI digital dimming ballasts whilst the analogue dim variant controls 1 10V...

Страница 2: ...presence and absence detection Presence detection when movement is detected the load will automatically turn on when the area is no longer occupied the load will automatically switch off after an adj...

Страница 3: ...page 3 Side mounting bracket Flush holder...

Страница 4: ...the inside or outside the PIR lens must have a view outside the luminaire versions with a lux sensor for optimum operation the lens must shielded as much as possible from the light source If flush mou...

Страница 5: ...page 5 Flush mounting Side mounting 32mm...

Страница 6: ...e used for absence detection and dimming up down set switch mode 1 position switch together see section 6 If used with Option B a centre biased momentary switch gives the benefit of having separate sw...

Страница 7: ...IR B feature not available EBMPIR PRM switch level on lux setting determines the ambient light level at which the lights turn on This can be set using the push button adjustment overleaf or the progra...

Страница 8: ...gs EBMPIR PRM 1 flash turns on when very dark 7 flashes turns on regardless of ambient light EBMPIR DD EBMPIR AD 1 flash gives dim output level 7 flashes gives maximum illumi nance Sensitivity 1 flash...

Страница 9: ...centre biased retractive switch will be used to default EBMPIR DD AD control both channels together 2 2 2 2 position switch separate A single centre biased retractive switch will be used to control on...

Страница 10: ...etween 0 and 99 4 12 Fade mins 0 This is the time period adjustable between 0 and 99 minutes that the luminaire will be held at the fade value before turning off A value of 0 disables the fade functio...

Страница 11: ...allow the controller to turn on at higher ambient natural light level If the detection range is smaller than expected check the diagram above Rotating the sensor slightly may improve the range LIGHTS...

Страница 12: ...g power supply suitable for B and PRM EBMPSU DD Direct dim power supply suitable for DD EBMPSU AD Analogue dim power supply suitable for AD Kits complete with sensor head and power supply EBMPIR B C B...