Dimming Channel 2 functions EBMPIR-DD & -AD only (factory default in brackets): 

 

4.1

 

Light level 

Maintained illuminance level (adjustable between 1 and 999). At 999 the 

output will be always be at maximum.  

 

4.2

 

Presence detection  

Auto switch on with detection, auto off after movement ceases and 

 

(default) 

time delay ends.  

4.3

 

Absence detection

 

Manual switch on, auto off after movement ceases and time delay ends.  

4.4   Switch level on 

(9)

 

Lux level setting to prevent the luminaires being switched on if the 

ambient light level is sufficient (adjustable between 1 and 9). The 

luminaires will always be switched on at level 9. For a higher resolution of 

‗switch level on‘ a scale of 101-199 is available in the ‗Special menu‘. 

4.5   Switch level off 

(9)

 

Lux level setting to switch the luminaires off during occupancy if the 

ambient light level goes above the setting (adjustable between 1 and 9). 

Level 9 will always keep the lights on. This setting can be used for 

―window row switching‖.  For a higher resolution of ‗switch level on‘ a scale 

of 101-199 is available in the ‗Special menu‘. 

4.6 

DSI 

(default) 

Selects DSI dimming (not applicable on EBMPIR-AD) 

4.7 

DALI 

Selects DALI dimming (not applicable on EBMPIR-AD) 

4.8 

Memorise 

(N)

 

If this is set to Yes, the last manual lux level set will be memorised and 

used as the new switch on level. 

4.9 

On value

 (99)

 

Dimming output level when switched on (0-99). 

4.10  Off value 

(0)

 

Dimming output level when switched off (0-99). If a non-zero off value is 

set, then the output will toggle between this value and completely off 

depending on the switch level on and off values. For example, if it is light 

outside, the fittings will be off if there is no occupancy. If it is dark outside, 

they will adopt the preset off value. This feature is only enabled if ‗Min 

value‘ is set to 99. 

4.11  Fade value 

(10)

 

After occupancy ceases, this dimming output level is loaded for the fade 

time (adjustable between 0 and 99).  

4.12  Fade mins 

(0)

 

This is the time period (adjustable between 0 and 99 minutes) that the 

luminaire will be held at the fade value before turning off. A value of 0 

disables the fade function. 

4.13  Max value 

(99)

 

Maximum dimming output level (adjustable between 0 and 99).  

4.14  Min value 

(1)

 

Minimum dimming output level (adjustable between 0 and 99).  

4.15  Speed on 

(40)

 

Determines the dimming response speed after the setup time has 

finished. Measured in 0.1 sec intervals. 

4.16  Speed set 

(5) 

 

Determines the dimming response speed during the set up time. 

Measured in 0.1 sec intervals. If set to 0 will disable dimming for ―Set 

seconds‖ below, used if fittings are required to warm up before dimming. 

4.17  Set seconds 

(120)

 

Determines how long the dimming response set-up period lasts on power-

up or on setting change (adjustable between 1 and 999 seconds). This 

enables the desired lux level to be achieved rapidly when the lights come 

on, or during setup. 

4.18  Burn-in 

(0)

 

Determines how long the output will be at 100% so that lamps ‗burn-

in‘ (adjustable between 1 and 999 hours). The ‘burn-in‘ time is not affected 

by power supply interruptions. To disable burn-in set to 0. 

4.18  DALI on 

(off)

 

Provides a permanent voltage to DALI ballasts when DALI has not been 

implemented correctly in the ballast. Maximum number of ballasts is 5 

unless the relay is disabled then it is 10. This is a Special menu option.

 

 

  User Menu 

DD-LCDHS user menu or UHS handset functions: 

5.1 

Lux up 

Increase light level. Reverts when occupancy cycle complete. 

5.2 

Lux down 

Decrease light level. Reverts when occupancy cycle complete. 

5.3 

Scene up 

Steps up between 6 pre-defined scenes. 

5.4 

Scene down 

Steps down between 6 pre-defined scenes. 

5.5 

Scene# 

Select the individual scene, between 0 and 6. (1 = min. output; 2 = 10%;  

 

 

3 = 25%; 4 = 50%; 5 = 75%; 6 = 100%) 

5.6 

Override on 

Permanently overrides the luminaire output on. 

5.7 

Override off 

Permanently overrides the luminaire output off. 

5.8 

Cancel 

Cancels the on or off override, returning the detector to normal operation.  

5.9 

Set 

If sent before using lux up or lux down, it will set the light level as in 4.1

 

 

Содержание EBMPIR

Страница 1: ...all of which will switch incandescent fluorescent and compact fluorescent lighting The direct dim variant controls DSI or DALI digital dimming ballasts whilst the analogue dim variant controls 1 10V...

Страница 2: ...presence and absence detection Presence detection when movement is detected the load will automatically turn on when the area is no longer occupied the load will automatically switch off after an adj...

Страница 3: ...page 3 Side mounting bracket Flush holder...

Страница 4: ...the inside or outside the PIR lens must have a view outside the luminaire versions with a lux sensor for optimum operation the lens must shielded as much as possible from the light source If flush mou...

Страница 5: ...page 5 Flush mounting Side mounting 32mm...

Страница 6: ...e used for absence detection and dimming up down set switch mode 1 position switch together see section 6 If used with Option B a centre biased momentary switch gives the benefit of having separate sw...

Страница 7: ...IR B feature not available EBMPIR PRM switch level on lux setting determines the ambient light level at which the lights turn on This can be set using the push button adjustment overleaf or the progra...

Страница 8: ...gs EBMPIR PRM 1 flash turns on when very dark 7 flashes turns on regardless of ambient light EBMPIR DD EBMPIR AD 1 flash gives dim output level 7 flashes gives maximum illumi nance Sensitivity 1 flash...

Страница 9: ...centre biased retractive switch will be used to default EBMPIR DD AD control both channels together 2 2 2 2 position switch separate A single centre biased retractive switch will be used to control on...

Страница 10: ...etween 0 and 99 4 12 Fade mins 0 This is the time period adjustable between 0 and 99 minutes that the luminaire will be held at the fade value before turning off A value of 0 disables the fade functio...

Страница 11: ...allow the controller to turn on at higher ambient natural light level If the detection range is smaller than expected check the diagram above Rotating the sensor slightly may improve the range LIGHTS...

Страница 12: ...g power supply suitable for B and PRM EBMPSU DD Direct dim power supply suitable for DD EBMPSU AD Analogue dim power supply suitable for AD Kits complete with sensor head and power supply EBMPIR B C B...

Отзывы: