APPENDIX 1 – CP ELECTRONICS SENSOR INITIAL SETUP
Using these tried and tested settings could help to fix any setup errors should the unpair and pair
again process be a little cumbersome. The unit can be checked to see that it functions well with
these FIRST before adjusting to customise for the specific project.
DAYLIGHT CONTROL SETTINGS
Settings
CP Setup
Comments
Mode of operation
Close loop
Light regulation to target
Use full dim range
Yes
This is absolutely necessary for the
light sensor control to function
Min dim level
1%
Avoid restrictions
Change rate
1.0 s
Optimum for test and typical operation
Desired Illuminance
150 lux
Typical for ceiling mount light sensor
expecting around 375lux on the work
plane at a reflectance of 0.6
Tolerance (setting - deviation
allowed)
1%
Tight 1% setting tested - good stability
Sensitivity
90%
This high sensitivity gives best
response and good stability
Tolerance (sensor)
1%
Tight 1% setting tested -good stability
All other settings
[Use dedicated sensors]
[Circadian rhythm] etc.
DISABLE