Cotek CR-21 PLUS Скачать руководство пользователя страница 6

Model 

Setting value range 

24V 

26 VDC ~ 30 VDC 

48V 

52 VDC ~ 60 VDC 

2-4-3 UVP Setting : 

Setting Under Voltage Protection (UVP) and shutdown on   

the inverter operation.    Default= 18 VDC @ 24V Model. 36VDC @ 48V Model 

Model 

Setting value range 

24V 

18 VDC ~ 25 VDC 

48V 

36 VDC ~ 50 VDC 

2-4-4 UVP Recovery : 

When the DC input voltage is below the set UVP value,   

the SR series shuts down; once the input voltage rises above the set UVP   
value, the SR series will automatically restart. 
Default= 25 VDC @ 24V Model. 50VDC @ 48V Model 

Model 

Setting value range 

24V 

23 VDC ~ 27 VDC 

48V 

46 VDC ~ 54 VDC 

2-4-5 UV Alarm : 

Setting Under Voltage (UV) alarm. When the input voltage is   

lower than the set value, the SR series will sound a “beep” to remind you that the unit 
is going to shutdown.    Default= 21 VDC @ 24 V Model. 42 VDC @ 48 V Model 

Model 

Setting value range 

24V 

19 VDC ~ 26 VDC 

48V 

38 VDC ~ 52 VDC 

 

     

2-5    AC Parameter 

     

2-5-1 O/P Voltage : 

Setting the SR series output voltage on the inverter   

                  operation. 1xx = 100V, 110V, 115V or 120V ; 2xx = 200V, 220V, 230V or 240V. 

Model 

Setting value range 

1XX 

97 VAC ~ 127 VAC 

2XX 

194 VAC ~ 254 VAC 

     

2-5-2 O/P Frequency : 

Setting the SR series output frequency on the inverter   

                operation. 1xx = 100V, 110V, 115V or 120V ; 2xx = 200V, 220V, 230V or 240V. 

Model 

Setting value range 

1XX & 2XX 

50 or 60 Hz 

     

2-5-3 Sync Frequency : 

Setting SR series output frequency tolerance range on the       

                inverter operation.    1xx = 100V, 110V, 115V, 120V ; 2xx = 200V, 220V, 230V or 240V. 

Model 

Setting value range 

1XX & 2XX 

0 Hz ~ 3 Hz 

     

2-5-4 AC or DC Mode : 

Default =1, AC Mode is the 1st priority source. 

DC Mode

DC is the 1st priority source, and the AC power is the 2nd priority source. 

AC Mode

AC is the 1st priority source, and the DC power is the 2nd priority source. 

Mode Priority 

SETT<value> 

DC Mode 

AC Mode 

Содержание CR-21 PLUS

Страница 1: ...status or fault messages Pressing buttons allows you to select a menu item or to save a setting once it is displayed on the LCD screen Description Function A UP Scroll up B DOWN Scroll down C ESC Go b...

Страница 2: ...1 2 Mechanical Drawings Unit mm 1 3 Hardware Installation...

Страница 3: ...Setting 2 4 1 OVP Recovery 2 4 2 UVP Setting 2 4 3 UVP Recovery 2 4 4 UV Alarm 2 4 5 AC Parameter 2 5 O P Voltage 2 5 1 O P Frequency 2 5 2 Sync Frequency 2 5 3 AC or DC Mode 2 5 4 AC Sharing 2 5 5 A...

Страница 4: ...e or redundant module failure Over Temperature Temperature is too high BAT Low Alarm Under DC voltage Alarm BAT High Alarm Over DC voltage Alarm Over Load Alarm The system over the rated apacity OLA M...

Страница 5: ...s 2 3 6 Date Time Setting Date yyyy mm dd Time hh mm ss YY year MM month DD date HH hour MM minute SS second 2 3 7 Password Setting 000000 999999 default setting 000000 2 3 8 Output On Off Setting Men...

Страница 6: ...del 42 VDC 48 V Model Model Setting value range 24V 19 VDC 26 VDC 48V 38 VDC 52 VDC 2 5 AC Parameter 2 5 1 O P Voltage Setting the SR series output voltage on the inverter operation 1xx 100V 110V 115V...

Страница 7: ...P setting the SR series transfer to DC mode or shuts down without battery once the input voltage falls below the set AC OVP recovery value the SR series will re operate in AC mode Default 125 VAC 1xx...

Страница 8: ...26 Fan normal 009 DC mode on 027 Fan failure 010 Grid Volt normal 028 Over temperature protection recovery 011 Grid Volt abnormal 029 Over temperature protection 012 Freq normal 030 The Machine was wo...

Отзывы: