2-3-3 Baud rate : 

Default setting

4800 

Setting Menu 

SETT<value> 

RS-485 

Baud rate 

 

1200 

2400 

4800 

9600 

19200 

2-3-4 

Dry contact C setting : 

Default =1, Setting range = 0~2, default=1. 

Setting Menu 

SETT <value> 

Description 

Dry C setting   

Disable 

Disable 

DRY C for Major 

Selectable extra alarm to 

go with Major   

DRY C for Minor 

Selectable extra alarm to 

go with Minor alarm 

2-3-5 

Alarm Setting:

 

Default =1 

Setting Menu 

SETT <value> 

Description 

Alarm Setting 

Normal 

Normal 

Mute 

Mute all alarms 

One time 

Silent warning for current 

status 

2-3-6 

Date Time Setting:

 Date yyyy-mm-dd      Time hh-mm-ss 

             

YY :year    MM :month    DD :date    HH :hour    MM :minute    SS :second 

2-3-7 

Password Setting: 

000000~999999, default setting:000000 

2-3-8

     

Output On/Off: 

Setting Menu 

SETT <value> 

Description 

Output On/Off 

On 

Turn on the output 

Off 

Turn off the output 

 

 

2-4    Bat Parameter 

2-4-1 OVP Setting : 

Set the Over Voltage Protection (OVP) and shutdown.             

         

Default = 34 VDC @ 24V Model. 68 VDC @ 48V Model 

Model 

Setting value range 

24V 

30 VDC ~ 34 VDC 

48V 

60 VDC ~ 68 VDC 

 
2-4-2 OVP Recovery : 

When the DC input voltage is higher than the OVP         

setting, the SR series shuts down; once the input voltage falls below the set OVP 
value, the SR series will automatically restart. 
Default = 28 VDC @ 24V Model. 56 VDC @ 48V Model 

Содержание CR-21 PLUS

Страница 1: ...status or fault messages Pressing buttons allows you to select a menu item or to save a setting once it is displayed on the LCD screen Description Function A UP Scroll up B DOWN Scroll down C ESC Go b...

Страница 2: ...1 2 Mechanical Drawings Unit mm 1 3 Hardware Installation...

Страница 3: ...Setting 2 4 1 OVP Recovery 2 4 2 UVP Setting 2 4 3 UVP Recovery 2 4 4 UV Alarm 2 4 5 AC Parameter 2 5 O P Voltage 2 5 1 O P Frequency 2 5 2 Sync Frequency 2 5 3 AC or DC Mode 2 5 4 AC Sharing 2 5 5 A...

Страница 4: ...e or redundant module failure Over Temperature Temperature is too high BAT Low Alarm Under DC voltage Alarm BAT High Alarm Over DC voltage Alarm Over Load Alarm The system over the rated apacity OLA M...

Страница 5: ...s 2 3 6 Date Time Setting Date yyyy mm dd Time hh mm ss YY year MM month DD date HH hour MM minute SS second 2 3 7 Password Setting 000000 999999 default setting 000000 2 3 8 Output On Off Setting Men...

Страница 6: ...del 42 VDC 48 V Model Model Setting value range 24V 19 VDC 26 VDC 48V 38 VDC 52 VDC 2 5 AC Parameter 2 5 1 O P Voltage Setting the SR series output voltage on the inverter operation 1xx 100V 110V 115V...

Страница 7: ...P setting the SR series transfer to DC mode or shuts down without battery once the input voltage falls below the set AC OVP recovery value the SR series will re operate in AC mode Default 125 VAC 1xx...

Страница 8: ...26 Fan normal 009 DC mode on 027 Fan failure 010 Grid Volt normal 028 Over temperature protection recovery 011 Grid Volt abnormal 029 Over temperature protection 012 Freq normal 030 The Machine was wo...

Отзывы: