Installation
】
【
】
A. On a concrete stand
【
】
B. On brackets on the wall
The refrigerant piping and signal cable between indoor
and outdoor unit should go through the wall by using a
wall sleeve.
The hole should lean to outside a little bit(
≥
8 degrees),
to avoid rain water or condensate water flow back to
the indoor.
Please add rubber absorber under the outdoor unit, to reduce the vibration.
Weather
shielter
Wall sleeve
2
Installation
1
33
1.The unit must be located on a flat,solid,preferably cemented surface.
2.When installing the unit,introduce a tilt of 1cm/m for rain water evacuation.
3.When installing the unit in harsh climatic conditions,sub-zero temperature ,snow,humidity..,
it is recommended to raise the unit off the ground by about 50cm.
4.It is recommended to have a base with following size for these units:
5.Rubber vibration absorbing mountings are recommended.
6.When sitting he unit, take care to leave sufficient free
space all around it for carrying out maintenance.
≥
50cm
A: If needs to hang the outdoor unit on the wall, please do as followings:
1.Adjust the location of the wall
according to the distance between two feet of the unit.
2.Fix the
on the wall with expansion bolts.
3.Place the outdoor unit on the
. A
4.Fix the unit to the bracket.
brackets
brackets
brackets
Vibration absorbers are recommended to reduce
vibration and noise.
Bolt
Vibration absorber
Nut
Gasket
1
2
3
4
4. Installation Of The Outdoor Unit