INSTALLATION  INSTRUCTIONS 

 

Connective Tube and Drainage 

 

Installation 

 

1. Run the drain hose sloping downward.

 

  Do not install the drain hose as 

 

illustrated in Fig.7. 

 

2. When connecting extension drain hose,

 

  insulate the connecting part of extension 

 

drain hose with a shield pipe, do not let

 

the drain hose slack. 

 

Refrigerant Tube Installation 

 

IMPORTANT:

  

The unit can only use right-hand piping  
or right rear piping as shown in

 

Fig.8. 

 

1. Remove the cover for right-hand piping first. 

 

2. For the right rear piping, install the piping as 
    shown in fig. 8 

 

3. Fix the end of the connective pipe. (Refer

 

  to Tightening Connection in 

 

REFRIGERANT PIPING CONNECTION) 

 

Indoor unit installation 

 

1. Pass the piping through the hole in the

 

  wall. 

 

2. Put the upper claw at the back of the

 

  indoor unit on the upper hook of the 

 

installation plate, move the indoor unit

 

from side to side to see that it is securely

 

hooked (see Fig.9 & Fig.10). 

 

3. Piping can easily be made by lifting the

 

  indoor unit with a cushioning material 

 

between the indoor unit and the wall. 
Remove material after it is not needed.

 

 

 

4. Push the lower part of the indoor unit up

 

  on the wall, then move the indoor unit 

 

from side to side, up and down to check

 

if it is hooked securely. 

 

Do not block water flow by a rise. 

 

Right-hand piping 

 

Fig.8 

 

Upper Hook 

 

Lower Hook 

 

Fig.9 

 

 

Do not put the end of

 

drain hose into water. 

 

Fig.7 

 

Right rear piping 

 

Cushioning

 

material 

 

Fig.10 

 

Содержание ACDC12

Страница 1: ...installing air conditioners we recommend you hire a professional installer The person who installs the system must do all work in compliance with local building and electrical codes Are there any rest...

Страница 2: ...helpful hints on how to install and test the air conditioner properly CAUTION Contact an authorized service technician for repair or maintenance of this unit Only allow a qualified person to install t...

Страница 3: ...se installation instructions Use a dedicated circuit If electrical circuit capacity or electrical work is not proper it can cause electrical shock or fire 6 Use the specified cable and connect tightly...

Страница 4: ...awning is built over the outdoor unit it must be done in a way that does not block air flow to the unit Keep the spaces indicated by arrows from wall or other obstacles Do not place animals and plants...

Страница 5: ...tapping Screw B ST2 9X10 Optional 2 9 Remote controller holder parts 1 CAUTION Use a stud finder to locate studs to prevent unnecessary damage to the wall A minimum pipe run of 3 meters is required t...

Страница 6: ...ng points on the installation plate The installation plate is different according to the models Dimensions are in mm unless otherwise stated Drill a hole in the wall 1 Determine hole positions accordi...

Страница 7: ...Connection in REFRIGERANT PIPING CONNECTION Indoor unit installation 1 Pass the piping through the hole in the wall 2 Put the upper claw at the back of the indoor unit on the upper hook of the instal...

Страница 8: ...tallation Install the outdoor unit on a rigid base to prevent increasing noise level and vibration Determine the air outlet direction where the discharged air is not blocked In the case that the insta...

Страница 9: ...in joint Base pan hole of outdoor unit Refrigerant Tube Connection 1 Flaring work Main cause for refrigerant leakage is due to defect in the flaring work Carry out correct flaring work using the follo...

Страница 10: ...essive torque can break the nut Electrical Work Fig 20 Electric safety regulations for the initial Installation 1 If there is an unsafe power supply the technician should refuse to install the air con...

Страница 11: ...e panel Fig 23 Then lift it upward 3 Release the coupler plugs connected with the front display panel as shown in Fig 24 4 After taking down the front panel remove the electrical box cover by loosenin...

Страница 12: ...bles to the terminals as identified with their respective locations see figure 27 3 Secure the cable onto the control board with the cord clamp 4 To prevent the ingress of water form a loop of the con...

Страница 13: ...e place for future reference care and maintenance and in case of sale or disposal of the module at the end of its useful life General Installing solar photovoltaic systems may require specialized skil...

Страница 14: ...llowing paragraph Do not attempt to disassemble the module and do not remove any attached nameplates or components Fig 30 Do not apply paint or adhesive to module top surface Do not use mirrors or oth...

Страница 15: ...m the system while transporting and installing mechanical and electrical components Fig 34 Completely cover the module with a solid material like a blanket during installation to keep electricity from...

Страница 16: ...e listed in the data sheet Data sheet values are values expected at standard test conditions Accordingly during system design values of short circuit current Isc and open circuit voltage Voc marked on...

Страница 17: ...If additional wind or snow loads are considered for the installation additional mounting points are also used The support frame must be made of durable corrosion resistant and UV resistant material T...

Страница 18: ...led to prevent leaks In some cases a special support frame may be necessary The roof installation of solar modules may affect the fireproofing of the house construction so it is necessary to use an ea...

Страница 19: ...odule without using the pre drilled mounting holes in the frame please consult with the supplier Do not install in the rainy weather it may cause insulation failure due to moisture and there is a risk...

Страница 20: ...e and the capacity of connector must be selected to suit the maximum system short circuit current otherwise the cable and the connector will be overheated under large current Modules connected in para...

Страница 21: ...more than 30A The electrician must identify the positive pole and negative pole Reverse connection may cause permanent damage to the air conditioner Use qualified photovoltaic cables only The cable c...

Страница 22: ...radius of the wire Fig 55 Do not unplug the connector when the power is on Fig 56 The protecting sheath must be used on the cable if there is a possibility for animals or children to touch it Fig 57 T...

Страница 23: ...he stainless steel bolt M3 into the tab of the lug the grounding hole on the frame and finally a nut to secure the entire assembly The spring washer is required in order to prevent screw loosening and...

Страница 24: ...9 The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active phase conductors Evacuation Air and mo...

Страница 25: ...he vacuum pump to evacuate Check guage for proper vacuum After the evacuation is complete fully close the LOW valve of the manifold valve and stop the operation of the vacuum pump 5 Run evacuation for...

Страница 26: ...tor to check for leakage CAUTION A Low valve B Hi valve C and D are for indoor unit connection Testing Indoor unit check point Cover Outdoor unit check point Fig 62 D C B A Perform test operation afte...

Отзывы: