Cosmic ACDC12 Скачать руководство пользователя страница 10

ELECTRICAL WORK 

 

C: Putting Nut On 

 

Remove flare nuts attached to indoor and

 

outdoor unit, then put them on pipe/tube 

 

having completed burr removal.(not possible

 

to put them on after flaring work) 

 

D: Flaring Work 

 

Firmly hold copper pipe in a die in the

 

dimension shown in the table below. 

 

Outer diam. 

A(mm) 

 

(mm) 

Max. 

Min. 

 

6.35 

1.3 

0.7 

 

9.52 

1.6 

1.0 

 

12.7 

1.8 

1.0 

 

Tightening Connection 

 

Flare nut 

 

Copper tube 

 

Fig.17 

 

Handle 

 

Bar 

Bar 

 

Yoke

 

  Cone 

 

Copper pipe

 

 

Clamp handle 

 

Red arrow mark 

 

Align the center of the pipes.

 

Sufficiently tighten the flare 

 

nut with fingers, and then tighten

 

it with a wrench and torque wrench

 

as shown in Fig.20 & 21. 

 

Outer 

Torque 

    Additional Torque 

Diam. 

Fig.18 

 

Indoor unit tubing   Flare nut 

Tube 

 

11.8 Ft. Lbs.

 

Fig.19

 

12 

 

26.55 Ft. Lbs. 

 

Caution 

 

Excessive torque can break the nut. 

 

 

Electrical Work 

 

Fig.20 

 

Electric safety regulations for the initial Installation 

 

1. If there is an unsafe power supply, the technician should refuse

 

  to install the air conditioner and explain to the client what the problem is. 

 

2. Power voltage should be in the range of 90%~110% of rated voltage. 

 

3. 

The GFCI protector and main power switch with a 1.5 times capacity of Max. Current 

  of the unit should be installed. 

4. Ensure the air conditioner is grounded well. 

 

5. Refer to the Electrical Connection Diagram located on the panel of the outdoor

 

 

unit to connect wires. 

 

6. All wiring must comply with local and national electrical codes and be installed

 

 

by licensed electricians. 

 

7. An individual branch circuit and single receptacle used only for this air conditioner must be

 

  available. See the following table for suggested wire sizes and fuse specifications: 

 

 

11.06 Ft. Lbs

18.44 Ft. Lbs.            19.18 Ft. Lbs. 

25.80 Ft. Lbs. 

1/4” 

3/8” 

1/2” 

Содержание ACDC12

Страница 1: ...installing air conditioners we recommend you hire a professional installer The person who installs the system must do all work in compliance with local building and electrical codes Are there any rest...

Страница 2: ...helpful hints on how to install and test the air conditioner properly CAUTION Contact an authorized service technician for repair or maintenance of this unit Only allow a qualified person to install t...

Страница 3: ...se installation instructions Use a dedicated circuit If electrical circuit capacity or electrical work is not proper it can cause electrical shock or fire 6 Use the specified cable and connect tightly...

Страница 4: ...awning is built over the outdoor unit it must be done in a way that does not block air flow to the unit Keep the spaces indicated by arrows from wall or other obstacles Do not place animals and plants...

Страница 5: ...tapping Screw B ST2 9X10 Optional 2 9 Remote controller holder parts 1 CAUTION Use a stud finder to locate studs to prevent unnecessary damage to the wall A minimum pipe run of 3 meters is required t...

Страница 6: ...ng points on the installation plate The installation plate is different according to the models Dimensions are in mm unless otherwise stated Drill a hole in the wall 1 Determine hole positions accordi...

Страница 7: ...Connection in REFRIGERANT PIPING CONNECTION Indoor unit installation 1 Pass the piping through the hole in the wall 2 Put the upper claw at the back of the indoor unit on the upper hook of the instal...

Страница 8: ...tallation Install the outdoor unit on a rigid base to prevent increasing noise level and vibration Determine the air outlet direction where the discharged air is not blocked In the case that the insta...

Страница 9: ...in joint Base pan hole of outdoor unit Refrigerant Tube Connection 1 Flaring work Main cause for refrigerant leakage is due to defect in the flaring work Carry out correct flaring work using the follo...

Страница 10: ...essive torque can break the nut Electrical Work Fig 20 Electric safety regulations for the initial Installation 1 If there is an unsafe power supply the technician should refuse to install the air con...

Страница 11: ...e panel Fig 23 Then lift it upward 3 Release the coupler plugs connected with the front display panel as shown in Fig 24 4 After taking down the front panel remove the electrical box cover by loosenin...

Страница 12: ...bles to the terminals as identified with their respective locations see figure 27 3 Secure the cable onto the control board with the cord clamp 4 To prevent the ingress of water form a loop of the con...

Страница 13: ...e place for future reference care and maintenance and in case of sale or disposal of the module at the end of its useful life General Installing solar photovoltaic systems may require specialized skil...

Страница 14: ...llowing paragraph Do not attempt to disassemble the module and do not remove any attached nameplates or components Fig 30 Do not apply paint or adhesive to module top surface Do not use mirrors or oth...

Страница 15: ...m the system while transporting and installing mechanical and electrical components Fig 34 Completely cover the module with a solid material like a blanket during installation to keep electricity from...

Страница 16: ...e listed in the data sheet Data sheet values are values expected at standard test conditions Accordingly during system design values of short circuit current Isc and open circuit voltage Voc marked on...

Страница 17: ...If additional wind or snow loads are considered for the installation additional mounting points are also used The support frame must be made of durable corrosion resistant and UV resistant material T...

Страница 18: ...led to prevent leaks In some cases a special support frame may be necessary The roof installation of solar modules may affect the fireproofing of the house construction so it is necessary to use an ea...

Страница 19: ...odule without using the pre drilled mounting holes in the frame please consult with the supplier Do not install in the rainy weather it may cause insulation failure due to moisture and there is a risk...

Страница 20: ...e and the capacity of connector must be selected to suit the maximum system short circuit current otherwise the cable and the connector will be overheated under large current Modules connected in para...

Страница 21: ...more than 30A The electrician must identify the positive pole and negative pole Reverse connection may cause permanent damage to the air conditioner Use qualified photovoltaic cables only The cable c...

Страница 22: ...radius of the wire Fig 55 Do not unplug the connector when the power is on Fig 56 The protecting sheath must be used on the cable if there is a possibility for animals or children to touch it Fig 57 T...

Страница 23: ...he stainless steel bolt M3 into the tab of the lug the grounding hole on the frame and finally a nut to secure the entire assembly The spring washer is required in order to prevent screw loosening and...

Страница 24: ...9 The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active phase conductors Evacuation Air and mo...

Страница 25: ...he vacuum pump to evacuate Check guage for proper vacuum After the evacuation is complete fully close the LOW valve of the manifold valve and stop the operation of the vacuum pump 5 Run evacuation for...

Страница 26: ...tor to check for leakage CAUTION A Low valve B Hi valve C and D are for indoor unit connection Testing Indoor unit check point Cover Outdoor unit check point Fig 62 D C B A Perform test operation afte...

Отзывы: