Instruction Manual

4.1 Connection method

4.2 Sequence unit

n

n

Pay attention to these points when connecting a DBS series unit

to the STA5000T.

STA5000T can optionally be equipped with a sequence unit for

controlling the DBS series units' remote control circuits ON/OFF

with a particular timing.

Employing this sequence unit enables starting and stopping of up

to 4 DBS systems at differential times.

The sequence unit operates by shorting the SYSTEM ON/OFF

terminals to change the status of the REMOTE SIGNAL 1 - 4

ON/OFF terminals from H to L.

Under the following situations, however, the signal from the

REMOTE SIGNAL 1 - 4 ON/OFF terminals will change from L to H.

1) 1 of the 3 phases is missing, due to equipment failure, etc.

2) Activation of the thermal detection.

Power units equipped with a sequence unit have the model name

STA5000T-R”.

REMOTE SIGNAL 1-4 signal might be H level if voltage drop

would happen when load is light.

For detailed information on how to use the sequence unit, please

consult our sales or engineering departments.

1 For some users, noise regulation requirements may make a

noise filter necessary.

Users are recommended to install a noise filter to reduce radi-

ation noise from the cabling, especially in cases where the ca-

bling is long.

2 Be sure to connect up the REMOTE ON/OFF terminals (or the

REMOTE SIGNAL ON/OFF terminals in a STA5000T-R) before

running the DBS.

Using the DBS without those terminals connected could dam-

age the STA5000T.

Unit type

A-131

4 Connecting the unit

to a DBS series unit

3.2 Mounting screw

n

Keep isolation distance between screw and internal components

as below chart.

3.1 Cooling

3 Assembling and

Installation Method

Mounting screw

Chassis

Unit

8mm max

M4

STA5000T

AC(R)

AC IN
3
200V

AC(S)

AC(T)

2

REMOTE ON/OFF (+)
REMOTE ON/OFF (-)

1

DBS

DBS

+V

-V

+VIN

-VIN

RC1

+VOUT

-VOUT

-VIN

RC1

-VOUT

-S

-S

-VIN

+VOUT

+S

+S

RC3 RC2

AUX

-S

RC3 RC2

AUX

-S

Load

Load

STA

n

The power unit is designed for use with forced cooling by external

fans. When the power unit is used, the temperature of part A of

the unit should be below 75 degree by flowing cooling-air inside

of unit uniformly.

AIR

AIR

20

A

SS3

FAN

FAN

55

Radiator Plate