1.1 Input voltage range

 

¡

The range is from AC85V to AC132V.

¡A

C input voltage must have a range from AC85V to AC132V for 

normal operation. If the wrong input is applied, the unit will not op-

erate properly and/or may be damaged.

¡

In cases that conform with safety standard, input voltage range is 

AC100-AC120V(50/60Hz).

1.2 Inrush current limiting

¡

Inrush current limiting is built-in.

¡

If a switch is being used for input, ensure that it is confi gured  to 

handle the input inrush current.

¿ 

LGA50A, LGA75A

¡

If the unit is shut down, recycling AC line has to be done after 

cooling down the unit since thermistor is used for the protection 

from the inrush current.

¿ 

LGA100A, LGA150A, LGA240A

¡

The SCR is used for protection from inrush current. When power 

is turned ON/OFF repeatedly within a short period of time, it is 

necessary to have enough time between power ON and OFF to 

operate resistance circuit for inrush current.

1.3 Overcurrent protection

¡

Overcurrent protection is built-in and comes into effect at over 

105%(-H is 101% or more of the peak current) of the rated cur-

rent. Overcurrent protection prevents the unit from short circuit 

and overcurrent condition of less than 15 seconds. The unit auto-

matically recovers when the fault condition is cleared.

¿ 

LGA50A-3R3-Y, LGA50A-5, LGA75A-3R3-Y, 
LGA75A-5, LGA100A-3R3-Y, LGA100A-5-Y, 
LGA150A-3R3-Y, LGA150A-5-Y

¡

Intermittent current characteristics.

¡

When the output voltage drops at overcurrent, the average output 

current is reduced by intermittent operation of power supply.

1.4 Overvoltage protection

¡

An overvoltage protection circuit is built-in. The AC input should 

be shut down if overvoltage protection is in operation. The mini-

mum interval of AC recycling for recovery is 1.5 minutes (LGA240A 

is 3minutes).

*

The recovery time varies depending on input voltage.

¡

Series operation is available by connecting the outputs of two or 

more power supplies with the same output voltage, as shown be-

low. Output current in series connection should be lower than the 

lowest rated current in each unit.

¡

Parallel operation is not possible.

¡

Redundancy operation is available by wiring as shown below.

¡

Even a slight difference in output voltage can affect the balance 

between the values of I

1

 and I

2

.

Please make sure that the value of I

3

 does not exceed the rated 

current of a power supply.

I

3

 

[

 the rated current value

1 Function

Remarks:

Please avoid applying the over-rated voltage to the output termi-

nal. Power supply may operate incorrectly or fail.In case of oper-

ating a motor etc. , please install an external diode on the output 

terminal to protect the unit.

1.5 Output voltage adjustment range

¡

Adjustment of output voltage is possible by using potentiometer. 

Please refer to instruction manual 5.1.

¡

Option ”-Y” is recommended which can adjust the output voltatge.

1.6 Isolation

¡

For a receiving inspection, such as Hi-Pot test, gradually increase 

(decrease) the voltage for the start (shut down). Avoid using Hi-

Pot tester with the timer because it may generate voltage a few 

times higher than the applied voltage, at ON/OFF of a timer.

2  

Series Operation and 
Parallel Operation

AC-DC Power Supplies Open Frame/ Enclosed Type

Instruction Manual

LGA-14

LGA

I

2

I

1

I

3

-

+

+

-

Load

Power
Supply

Power
Supply

Load

(a)

(b)

Load

Load

Power 
Supply

+

-

Power 
Supply

+

-

Power 
Supply

+

-

+

-

Power 
Supply

Fig.2.1 Examples of connecting in series operation

Fig.2.2 Example of redundancy operation

me̲lga1.indd   LGA-14

me lga1 indd LGA-14

2015/06/19   14:42:25

2015/06/19 14:42:25

Содержание LGA100A

Страница 1: ...ethod Forward Converter Forward Converter Forward Converter 1 A 3 6 2 4 1 7 1 3 current Input 130 operation availability 2 Series Parallel Parallel operation SCR CEM 3 Yes Yes PCB Pattern SCR SCR Ther...

Страница 2: ...Series Operation and Parallel Operation LGA 14 1 1 Input voltage range 1 2 Inrush current limiting 1 3 Overcurrent protection 1 4 Overvoltage protection 1 5 Output voltage adjustment range 1 6 Isolat...

Страница 3: ...input should be shut down if overvoltage protection is in operation The mini mum interval of AC recycling for recovery is 1 5 minutes LGA240A is 3minutes The recovery time varies depending on input v...

Страница 4: ...ing E mounting A F mounting 1 1 A mounting B C mounting 10 70 60 50 40 30 2 2 1Convection 80 100 60 40 20 0 20 10 0 Load factor C Ambient temperature A F mounting Forced air 0 5m3 min 1 1 D mounting E...

Страница 5: ...ounting AC DC Power Supplies Open Frame Enclosed Type Instruction Manual LGA 16 LGA F mounting should be operated by Forced air Fig 3 14 Derating curve depending on input voltage Fig 3 9 Ambient tempe...

Страница 6: ...66 77 Io 40 75 81 A B C D E F Forced air 70 Io 100 85 80 Io 70 80 75 Table 3 4 Temperatures of Point A Point B LGA100A O Mounting Method Cooling Method Load factor Max temperature Point A C Point B C...

Страница 7: ...50C 5years 3years Warranty Table 3 13 Warranty LGA50A 3R3 Y 5 12 15 Mounting Method Cooling Method Average ambient temperature year Load factor Io 75 75 Io 100 A Convection Ta 40C or less 5years 5yea...

Страница 8: ...able 3 18 Warranty LGA240A O Mounting Method Cooling Method Average ambient temperature year Load factor Io 75 75 Io 100 A Convection Ta 30C or less 5years 5years Ta 40C 5years 3years B C Convection T...

Страница 9: ...se the output voltage turn a built in potentiometer clockwise To decrease the output voltage turn it counterclockwise Please take care when you adjust output voltage by potentiometer because there is...

Отзывы: