Chassis of
 FETA series

Chassis of 
customer system

Mounting Screw

Fig.4.1  Mounting screw

Table 4.1 Max penetration length

Mounting hole

a (Max penetration length)

Bottom

6mm max

Side

4.5mm max

¡

The power supplies have a built-in forced cooling fan.  Do not 

block ventilation at the suction side and its opposite side.

¡

If you use a power supply in a dusty environment, it can give a 

cause for a failure.  Please consider taking such countermeasures 

as installing an air fi lter near the suction area of the system to pre-

vent a failure.

(a) Front side

(b) Rear side

Intake opening

Exhaust opening

Fig.4.2 Location of intake port and exhaust port

30mm min

30mm min

Fig. 4.3 Clearance of intake port and exhaust port

¡

When mounting the power supply with screws, it is recommended 

that this be done as shown in Fig.4.4.  If other methods are used, 

be sure the weight of the power supply is taken into account.

-V

+V

Input

-V

+V

-V

+V

Input

Input

(A)

(B)

(C)

Fixed screw (3 pcs.)

Fixed screw
 (3 pcs.)

Fixed screw (2 pcs.)

Fixed screw (2 pcs.)

Fig.4.4 Installation method

4.2 Derating

¡

Input Voltage Derating Curve

Input voltage derating curve is shown in Fig.4.5.

[AC V]

170

180

85

100

Load [%]

Fig.4.5 Input voltage derating curve

¡

Ambient Temperature Derating Curve

Derating curve depending on an ambient temperature is shown in 

Fig.4.6.

Specifi cations for ripple and ripple noise changes in the shaded 

area.

80

70

40

60

- 10

2

10

30

50

0

0

100

0

20

40

60

80

Load factor [%]

Ambient temperature [

C

]

Fig.4.6 Ambient temperature derating curve

4.3 Expected Life and Warranty

¡

Expected Life

Please see the following tables for expected life.

Table.4.2  Expected lifetime

Mounting

Cooling 

method

Average ambient 

temperature

Expected lifetime

[years]

Io = 50%

Io = 100%

All 

direction

Forced air cooling

(internal fan)

Ta = 35

C

 or less

6

5

Ta = 50

C

4

3

Ta = 70

C

2

-

This lifetime includes a built-in fan lifetime.

AC-DC Power Supplies Enclosed type

Instruction Manual

FETA-11

FETA

me̲feta1.indd   11

me feta1 indd 11

2013/09/09   14:28:40

2013/09/09 14:28:40

Содержание FETA2500B

Страница 1: ...nput fuse Inrush current protection circuit PCB Pattern Series Parallel operation availability Material Single sided Double sided Series operation Parallel operation FETA2500B Active filter 47 13 8 25...

Страница 2: ...9 4 Assembling and Installation Method FETA 10 FETA 6 FETA 6 FETA 6 FETA 6 FETA 6 FETA 7 FETA 7 FETA 7 FETA 7 FETA 8 FETA 8 FETA 9 3 1 Series Operation 3 2 Parallel Operation Master slave Operation 3...

Страница 3: ...d to use a switch on the input side please select one that can withstand an input inrush current Relay technique is used in the inrush current limiting circuit When you turn the power ON OFF repeatedl...

Страница 4: ...ectrolytic capacitor 22 F Fig 2 1 Measuring method of Ripple and Ripple Noise Remarks When GND cable of probe with flux of magnetic force from power supply are crossing ripple and ripple noise might n...

Страница 5: ...ult condition refer to Table 2 5 OFF Table 2 4 Description of the Warnings WRN signal Warning Output of Warning WRN The WRN signals are Low when the power supply oper ates normally The signals turn Hi...

Страница 6: ...eration 3 1 Series Operation It is possible to connect multiple output voltages in series in order to obtain higher output voltage However care should be taken as follows Notes of a and b 1 Please not...

Страница 7: ...edundancy operation for improved system reli ability N 1 redundancy operation is possible by connecting units as shown in Fig 3 3 VB CB and COM are also connected together between all units in paralle...

Страница 8: ...of the power supply is taken into account V V Input V V V V Input Input A B C Fixed screw 3 pcs Fixed screw 3 pcs Fixed screw 2 pcs Fixed screw 2 pcs Fig 4 4 Installation method 4 2 Derating Input Vol...

Страница 9: ...ument which has 500kW input impedance or more Do not short between CB and COM because of possibility of fail ure 5 2 Auxiliary Power AUX The power supplies can generate an auxiliary power AUX 12V 0 15...

Отзывы: