In the event of one power supply failing and ceasing output of 

power, use of N+1 parallel redundancy means that output voltage 

is guaranteed through a backup; therefore, the system can con-

tinue with normal operation.

However,  please consider the following condition.

1

5% or less of the output voltage decrease when one power sup-

ply stops.

2

Even if one or several power supplies stop, output current that 

meets the following formula is required from the remaining nor-

mally operating power supplies.

In parallel operation,  the maximum operative number of units is 

5.

3

Please detach or exchange the broke down power supply after 

intercepting the input voltage (impossible hot swap).

4

The broke down power supply is detached or exchanged,  and 

after output voltage of new one is adjusted alone,  the power 

supply should be connected load (your system).

*

Parallel operation cannot be done with standard model.

The following electric specifi cations are different from standard 

model.

5

If diodes are used to confi gure a circuit to achieve even higher 

reliability, use connections as in Fig. 5.9.

Please  connect the diode with +V.

Please  do not connect VB of the power supply mutually.

 

In this case, master-slave operation cannot be done.

Please adjust to become 100mV or less the difference of setting 

VB voltage of each power supply by the potentiometer for the 

output voltage setting to suppress the change of the output volt-

age to about 5% or less when one stops. 

AC-DC Power Supplies Enclosed Type

Instruction Manual

ADA-16

ADA

The rated 

current per unit

                              

X

 (Number of unit) 

X

0.9

Output current in 

parallel operation

Fig.5.8 N+1 redundant operation

Output Voltage(V)

ADA600F

Load

Regulation

(mV)

ADA750F

240 max

300 max

360 max

480 max

ADA1000F

24

30

36

48

Load

+

-

-

+

CB VB

-

+

CB VB

-

+

CB VB

-

+

CB VB

-

+

CB VB

Load

+

-

-

+

CB VB

-

+

CB VB

-

+

CB VB

-

+

CB VB

-

+

CB VB

Fig.5.9 N+1 redundant operation which uses diode

me̲ada1.indd   ADA-16

me ada1 indd ADA-16

2015/08/07   9:23:59

2015/08/07 9:23:59

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Содержание ADA1000F

Страница 1: ...ss underutilized and idle equipment along with credit for buybacks and trade ins Custom engineering so your equipment works exactly as you specify Critical and expedited services Leasing Rentals Demos...

Страница 2: ...erter Active filter Active filter Active filter A current Input 130 85 130 85 85 operation availability Series Parallel Parallel operation Yes PCB Pattern SCR Inrush protection current FR 4 Material D...

Страница 3: ...ADA 10 ADA 10 ADA 10 ADA 10 2 1 Installation method 2 2 Mounting screw 2 3 Derating 2 4 Expectancy life and warranty 2 5 Current monitor 3 Series Operation and Parallel Operation ADA 12 3 1 Series ope...

Страница 4: ...The case FAN stops or air flow is interrupted and the amount of the wind decreases If the thermal protection activates shut off input voltage remove the cause of the overheating wait for the unit to c...

Страница 5: ...nvection as shown in Fig 2 2 2Do not block the ventilation hole In case of ADA600F 24 load factor 100 means output 24V 21A at ACIN100V 24V 25A at ACIN200V In case of ADA750F 24 load factor 100 means o...

Страница 6: ...minal and V terminal or the operation may be mulfunction Please use an oscilloscope for pulse loads 3 2 Parallel operation master slave operation Parallel operation is available by connecting below As...

Страница 7: ...the output voltage fluctuates oc casionally The minimum current is different depend on the model and the number of parallel operation so please consult us at any time In parallel operation output vol...

Страница 8: ...r Supplies Enclosed Type Instruction Manual ADA 14 ADA G Fig 5 2 Part around terminal block T Fig 5 3 Option J Fig 5 1 Option F Table 5 1 Low leakage type Between RC and RC SW ON 4 5 12 5V SW OFF 0 0...

Страница 9: ...ication is shown Table 5 2 Special harness is prepared refer to option parts Consult us external view in details Each alarm PF LV is isolated from input output and FG AC DC Power Supplies Enclosed Typ...

Страница 10: ...with standard model The following electric specifications are different from standard model 5If diodes are used to configure a circuit to achieve even higher reliability use connections as in Fig 5 9...

Страница 11: ...uipment Have surplus equipment taking up shelf space We ll give it a new home Learn more Visit us at artisantg com for more info on price quotes drivers technical specifications manuals and documentat...

Отзывы: