background image

*

This connector is different if used with option -J.Refer to Fig. 5.3 

for pin arrangements.

¡

When external power source is in the range of 4.5 - 12.5V,  cur-

rent limit resistance R is not required.  However,  when external 

power source exceeds 12.5V,  current limit resistance R must be 

connected.

To calculate the current limit resistance, use the following equa-

tion:

R [

W

] = 

Vcc- (1.1+Ri

X

0.005)  

                         0.005

Where ; 

Vcc = External Power Source

Ri = The internal resistance (780

W

)

¡

A wrong connection may damage the internal components of the 

unit.

¡

Remote ON/OFF circuit (RC (+),  RC (-) ) is isolated from input,  

output and FG.

¿

-N1

-

A type with a fi tting supporting a dedicated DIN rail.

-

Consult us external view in details.

-

A type in which terminal block screws are aligned vertically (op-

tion: -T).

¿

-W

 (It is not possible to combine with option -J)

-

-W is available for detecting low input alarm (PF),  detecting low 

output voltage (LV) and operating N+1 redundancy.

-

Alarm specifi cation is shown Table 5.2.

-

Special harness is prepared,  refer to option parts.

-

Consult us external view in details.

-

Each alarm (PF,LV) is isolated from input,  output and FG.

AC-DC Power Supplies Enclosed Type

Instruction Manual

ADA-15

ADA

Fig.5.4 Example of use remote ON/OFF

Fig. 5.5 Din Rail Attachment

Table 5.2  Explanation of alarms

Fig.5.6 PF internal circuit

Fig.5.7 LV internal circuit 

PF+

PF-

LV+

LV-

+V

 -V

R

Ri

Vcc

I=20mA max

SW

CN3*

RC (+)

RC (-)

Connector for remote ON/OFF (Optional)

1

2

External Power
Source

When line voltage is abnor-

mal (low input voltage out of 

range),  the alarm outputs from 

CN3.

If the output voltage drops be-

low the rating, the alarm signal 

is output from CN3.

Note :  

1

This becomes un-

stable in the event 

of output overcur-

rent (intermittent 

overcurrent).

2

The alarm signal is 

not output for paral-

lel operation that 

does not use OR 

diodes.

PF

LV

Open collector method

Good : Low

  

 

(0 - 0.8V,  1mA max)

Fail   : 50V max

Open collector method

Good : Low

  

 

(0 - 0.8V,  1mA max)

Fail   : 50V max

Alarm

Output of alarm

Please consult us details.

me̲ada1.indd   ADA-15

me ada1 indd ADA-15

2015/08/07   9:23:58

2015/08/07 9:23:58

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Содержание ADA1000F

Страница 1: ...ss underutilized and idle equipment along with credit for buybacks and trade ins Custom engineering so your equipment works exactly as you specify Critical and expedited services Leasing Rentals Demos...

Страница 2: ...erter Active filter Active filter Active filter A current Input 130 85 130 85 85 operation availability Series Parallel Parallel operation Yes PCB Pattern SCR Inrush protection current FR 4 Material D...

Страница 3: ...ADA 10 ADA 10 ADA 10 ADA 10 2 1 Installation method 2 2 Mounting screw 2 3 Derating 2 4 Expectancy life and warranty 2 5 Current monitor 3 Series Operation and Parallel Operation ADA 12 3 1 Series ope...

Страница 4: ...The case FAN stops or air flow is interrupted and the amount of the wind decreases If the thermal protection activates shut off input voltage remove the cause of the overheating wait for the unit to c...

Страница 5: ...nvection as shown in Fig 2 2 2Do not block the ventilation hole In case of ADA600F 24 load factor 100 means output 24V 21A at ACIN100V 24V 25A at ACIN200V In case of ADA750F 24 load factor 100 means o...

Страница 6: ...minal and V terminal or the operation may be mulfunction Please use an oscilloscope for pulse loads 3 2 Parallel operation master slave operation Parallel operation is available by connecting below As...

Страница 7: ...the output voltage fluctuates oc casionally The minimum current is different depend on the model and the number of parallel operation so please consult us at any time In parallel operation output vol...

Страница 8: ...r Supplies Enclosed Type Instruction Manual ADA 14 ADA G Fig 5 2 Part around terminal block T Fig 5 3 Option J Fig 5 1 Option F Table 5 1 Low leakage type Between RC and RC SW ON 4 5 12 5V SW OFF 0 0...

Страница 9: ...ication is shown Table 5 2 Special harness is prepared refer to option parts Consult us external view in details Each alarm PF LV is isolated from input output and FG AC DC Power Supplies Enclosed Typ...

Страница 10: ...with standard model The following electric specifications are different from standard model 5If diodes are used to configure a circuit to achieve even higher reliability use connections as in Fig 5 9...

Страница 11: ...uipment Have surplus equipment taking up shelf space We ll give it a new home Learn more Visit us at artisantg com for more info on price quotes drivers technical specifications manuals and documentat...

Отзывы: