INSTALLATION, OPERATION AND MAINTENANCE MANUAL – COSA 9610™
Page 13 of 48
The EPV-X-Purge relief vent is separate and is mounted to the enclosure. The components
of the X-Purge control unit are listed below:
• EPCU mounted in an explosion/flameproof enclosure
• I.S. user-interface with display and cable
• I.S. termination board (does not come with ‘CK’ kit version)
• Manifold with I.S. solenoid valve (does not come with ‘CK’ kit version)
• Flush mount type 4X IP66 fitting for protective gas supply to enclosure with tube attached
• Type 4X cable glands for I.S. wiring to I.S. inputs, vents, and temperature modules
• 316L stainless steel pipe nipples for power wires
• 316L stainless steel type 4X enclosure for the X-Purge controller
The components of the EPV-6000 vent:
• EPV-6000 vent with spark arrestor screen
• 1½” sealing nut with gasket for attachment of vent to customer’s enclosure
• A 5 meter, quick disconnect cable; blue (denoting I.S.), for connection to I.S. termination
board inside X-Purge control unit
The X-Purge control unit and vent are mounted to the calorimeter enclosure. Bottom, right
side mounting can be completed with only one control unit and vent. One unit is used for
enclosure sizes up to 450 ft3 (12.7 m3).
Electronic Power Control Unit – EPCU
The EPCU houses the redundant microprocessors, enclosure power contacts, (2) auxiliary
contacts, power supply module, galvanically isolated barriers for the inputs, vent(s), and
temperature modules; all stackable and easy to remove and install into the explosion proof
enclosure that houses them.
The power supply module is available in 24 VDC or 100-240 VAC units. The enclosure power
contacts are forced-guided safety relays. The auxiliary contacts can be user configured for
different functions depending on user requirements.
User-Interface Controller - UIC
The X-Purge is user programmable for many of the configurable options available. This is
done with the intrinsically safe user-interface on the face of the unit, which can also be
remote mounted. The user-interface is a 2 x 20 LCD that is programmed through a set of
buttons on the menu driven unit. All configuration and options are programmed through
this unit. There are also (5) LEDs for easy visual indication of operation:
• Safe Pressure – This turns on (blue) when safe pressure is achieved inside the enclosure.
• Enclosure power – This is (red) when the enclosure power is off, and (green) when
enclosure power is on. The enclosure power can be on only after a successful purge and a
safe pressure is achieved. Bypass option allows power to remain on if safe pressure is lost.
• Rapid Exchange® – The Rapid Exchange or purging flow rate turns on (blue) when the
flow rate is measuring proper flow.
• System Bypass – This turns on (yellow) when the system bypass is active. This should be
used only when the area around the enclosure is known to be safe.
Содержание 9610
Страница 27: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL COSA 9610 Page 26 of 48 ...
Страница 32: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL COSA 9610 Page 31 of 48 3 3 2 Operation Menu ...
Страница 34: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL COSA 9610 Page 33 of 48 3 3 4 Output Menu ...
Страница 36: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL COSA 9610 Page 35 of 48 ...
Страница 38: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL COSA 9610 Page 37 of 48 Display Menu ...
Страница 39: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL COSA 9610 Page 38 of 48 3 3 7 Reset Alarms Menu ...
Страница 46: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL COSA 9610 Page 45 of 48 5 INSTALLATION DRAWING ...
Страница 48: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL COSA 9610 Page 46 of 48 ...
Страница 50: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL COSA 9610 Page 48 of 48 ...
Страница 51: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL COSA 9610 Page 48 of 48 ...