Multiple available functions
•
Monitoring with Modbus RS485
1 x screened signal cable of class A is connected to the control unit for monitoring via the
property system.
•
External alarm
Connection of external alarm function e.g. flashing light made via auxiliary control relay.
Alarm signal from VentoVind control unit activates control relay.
Starting and test operation
Connect the wireless control panel with the control unit via the menu in the control panel. The
following settings are made via the control panel.
•
Time & Date
Set the correct time and date to obtain the correct date stamp in the log.
•
Set the correct type of fan
Check that the correct fan type, AC or EC, is set. NOTE! If the incorrect fan is selected, the
ventilation will not work.
•
Test operate fan and dampers
Test operate fan and dampers according to the manual. It is important to check that the air is
transported from the fan, through the entire area and out through the exhaust air damper.
•
Activate speed monitoring, TACHO-signal
Activate Tacho signal to obtain feedback of the fan speed and thus get an alarm in the event
of operational interruption of the fan.
Note!
in the event of multiple fan installation,
monitoring of Tacho-signal may only occur on one fan.
Check the function
After completed installation, check the Ventovind system's function and settings as per protocol
Commissioning and Warranty documentation, that can be found in the manual for VentoVind PRO
special or on Corroventa's website.
www.corroventa.com/documentation/.
See section Living
Environment.
A condition for the machine warranty to apply is that the protocol for commissioning and Warranty