background image

 

 

A15ES 

 

 

© Corroventa Avfuktning AB 

2022.05 

24 (67) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity mode

 

Indicates what 
capacity mode is 
selected 

 

Blinking 
exclamation point 
after the name 
indicates that the 
operation point of 
the machine is 
suboptimal and 
preferably 
adjusted 

SuperVision 

Visible when the 
machine is 
connected to 
SuperVision

 for 

remote monitoring 
and control. 

 

Network status 

“Master” or “Slaved” 

 

If the machine is 
connected to local 
network, this position 
indicates whether the 
machine is controlling 
the network, Master, or 
if it is controlled by 
another machine and 
thus Slaved. 

 

Timer 

 Visible when 
machine is set to 
operate on Timer. 

Slaved 

 indicates 

that the machine 
is controlled by 
another machine. 

 

Alarm  

 Machine has 
detected an error. 

 

Drying indicator 

Moving when 
drying is on-going.  

 

Fan indicator 

Moving when fan 
is running. 

 

Fan mode 

Cont

 - continuous fan.  

If not displayed, fan only 
operates when drying is 
required. 

INT 

 

intermittent fan 

operation, 5 minutes of 
every hour.  

Read further important 
information in the 
following chapter.  

 

Control mode 

Indicates how the drying 
is controlled, if it is 
continuous (MAN - 
manual) or if it operates 
to defined setpoint 
Relative Humidity, RH, 
mixing ratio, MIX or Dew 
point, DEW. It can also 
be controlled by external 
hygrostat, HYG.  

If external Relative 
Humidity and 
temperature sensor is 
used, this position reads 
E.RH, E.MIX or E.DEW. 

 

 

 

Setpoint 
adjustment

 

indicates that the 
left and right 
buttons below the 
screen are used to 
increase and 
decrease the 
setpoint which is 
displayed with 
black background. 

 

Содержание A15ES

Страница 1: ...A15ES Corroventa Avfuktning AB 2021 11 1 67 USER MANUAL ADSORPTION DEHUMIDIFIER A15ES ...

Страница 2: ...pe 11 How the dehumidifier works 12 Transport and lift 13 Delivery inspection inspection after transport lift 14 Storage 14 Installation 14 Start and stop the machine 16 Emergency stop 17 Adjusting air flow balance 18 Filter monitoring 21 Control panel menu and functions 23 Control Modes and Hysteresis 34 Alarms 35 To network machines 38 Service Reminder 38 Service and Maintenance 39 Filter replac...

Страница 3: ...A15ES Corroventa Avfuktning AB 2021 11 3 67 ...

Страница 4: ...e control panel the user can adjust and optimize the operation of the A15ES to the work to be undertaken controlling the operation of the fan and selection of proper control mode using either the built in or an external RHT sensor The A15 ES is also compatible with the SuperVision and can thus be remotely operated and controlled through use of smart phone PC or tablet The SuperVision collects and ...

Страница 5: ...s the responsibility of the buyer to inspect the product at time of delivery and before use to ensure its good function The product warranty does not cover damage resulting from use of faulty products Changes or modifications to the equipment must not be made without written consent by Corroventa Avfuktning AB The product technical data and or installation and operation instructions can be changed...

Страница 6: ...ble or explosive gases can be present neither in the ambient air nor in the air flows through the machine 9 Do not stick objects into the air outlets or intakes as this can cause damage to the machinery as well as human injury 10 Install the dehumidifier steadily and leveled so that it cannot fall over 11 Keep children animals and spectators away from the workplace while installation is undertaken...

Страница 7: ... in position The service hatch the filter hatches as well as the electronics cabinet shall be closed and locked 27 For transport and lift the machine must be appropriately secured and the risk area evacuated and continuously monitored 28 If after transport and or lift there is reason to believe the machine may have been damaged it must not be powered and used until it has been inspected by qualifi...

Страница 8: ...eneration air Filter hatch process air Lock service hatch Process air inlet Regeneration air inlet Wet air outlet Connections for future expansion modules Regeneration fan Process fläkt Electronics cabinet with control panel Regeneration heater Rotor Rotor motor ...

Страница 9: ...cassette may slide out and shift the centre of gravity which could cause the machine to fall over Inside the machine on the rotor cassette and clearly visible when the service hatch is open the below warning label is found The intent of this label is to inform and remind the user that the rotor cassette must never be extracted whilst the machine is in elevated positions an example of which is a li...

Страница 10: ...warning symbol intended to remind the user of the above warning in case lighting conditions or other circumstances blocks it from view or if it has been forgotten In addition to the warning labels inlets and outlets as well as filter hatches are marked with their respective functions so as to simplify installation and prevent mistakes ...

Страница 11: ...ge of a lower ambient temperature dependency Adsorption functions even well below the freezing point while the capacity of a condensation dehumidifier inevitably decreases rapidly with falling temperature something that is depicted in the diagram below to the left As a rule of thumb a general aid in the selection of type it can be said that adsorption is the primary choice for drying of unheated s...

Страница 12: ...h the process fan and is pushed out through the dry air outlet ready to be distributed to where it is needed In parallel with the drying process to prevent the rotor from being saturated at which point the dehumidification would have stopped the rotor is continuously regenerated through use of a completely separated air flow that functions as follows Regeneration air is drawn into the machine thro...

Страница 13: ...he service hatch the filter hatches and the electronics cabinet hatch are all closed and locked The below label intended to remind the user of this is found at the bottom of the service hatch The forks of the lifting equipment e g forklift pallet lifter are long big enough for the entire machine to rest securely on them That the machine is secured in the manor appropriate to its weight and to the ...

Страница 14: ...ps decreasing the capacities of the respective fans and thus also the dehumidification capacity and energy efficiency As a guideline to the installation planning observe the following Plan the installation and position the machine in such a way that the required ducting is as short as possible Use the same and as big dimensions as possible of hoses pipes for regeneration air and wet air and respec...

Страница 15: ...of the machine hatch is preferably of the same height as that of the floor on which the machine is positioned The reason is that the extractable rotor cassette is provided a support to prevent the machine from falling over due to the shifted centre of gravity An elevated position of the machine will prevent the support from reaching the floor and thus the support will no longer prevent accidents I...

Страница 16: ...s provided in chapter Filter monitoring Start and stop the machine The machine is equipped with a mains power switch positioned in the lower left corner of the electronics cabinet hatch To start the machine 1 Turn the mains power switch clockwise to position 1 2 Await the control panel start up 3 Once the default view is presented on the control panel there are two alternatives presented Start to ...

Страница 17: ...e completed 3 The machine is now in standby For complete shut down proceed by turning mains power switch anti clockwise to position 0 Emergency stop The emergency stop button is positioned next to the mains power switch on the electronics cabinet hatch and it is engaged by a push To reset the emergency stop first turn the emergency stop anti clockwise and then push the reset button located to the ...

Страница 18: ... can be increased while still maintaining proper and correct pressure balance between the air flows Before adjustment is undertaken ensure that the machine has been allowed to operate with intended capacity mode for at least 10 minutes preferably more so that it has warmed up and the power consumption of the machine has stabilized The regeneration heaters of the machine are of PTC type which means...

Страница 19: ...buttons The minus button lowering the speed of the fan will move the current actual to the left while increasing the speed will move it to the right Make small incremental adjustments wait for the machine to stabilize and then re evaluate Whenever the machine detects rapid and big changes it will present the text Stabilizing please wait The power developed by the PTC heaters is as previously descr...

Страница 20: ...ios reflecting a machine with limited ducting 2 When capacity mode is changed the adjustment will have to be repeated If the machine has temporarily been put in standby select Resume to start it again with previous settings and adjustment The other option Start makes the machine forget previous settings including adjustment and brings operation in MAX mode with continuous dehumidification control ...

Страница 21: ...unction of the air flow has the appearance depicted below The pressure drop over the increasingly more dirty filter will increase more rapidly with an increase of the air flow as seen by the increasingly steep slope of the curve To get the alarms to trigger at the correct point in time with given installation will thus often require the pressure drop settings to be changed Installations with long ...

Страница 22: ...e The difference is that that the last row max pressure presents the pressure level that if exceeded at given current actual fan speed will trigger the alarm A quick comparison of this value 240 Pa in the example and the current actual pressure drop of 180 Pa will give an indication of the filter status Push of Change in the above screen will at first present the user with the possibility of switc...

Страница 23: ...nctions are always presented in text and the bottom of the screen At the top level menus the left of these buttons is named Home and a push on this button will immediately lead back to the default view In many of the views there is an Info button which presents information that may be of use to the inexperienced user If the backlight of the display has timed out the first button push serves only t...

Страница 24: ...d by another machine Alarm Machine has detected an error Drying indicator Moving when drying is on going Fan indicator Moving when fan is running Fan mode Cont continuous fan If not displayed fan only operates when drying is required INT intermittent fan operation 5 minutes of every hour Read further important information in the following chapter Control mode Indicates how the drying is controlled...

Страница 25: ...p for a given task Start Starts the machine with default settings continuous operation with maximum capacity Previous settings made such as the use of sensor control Timer etc If last time it was used the user never pushed stop before the power was cut the machine will automatically resume operation when the countdown has reached zero A push of Pause button will stop the countdown and the machine ...

Страница 26: ... operate only when required as determined by the ambient climate The selected control mode is displayed in the lower left corner of the default view The Control Mode selection screen is reached by one push of the upper right button The following basic control modes are available MAN Manual continuous drying RH Drying down to selectable Relative humidity MIX Drying down to selectable mixing ratio g...

Страница 27: ... and alternative All is selected rather than one unique sensor e g RHT61 the machine applies worst case and operates as long as any one of the sensors read a humidity above the setpoint When selecting mode other than MAN the machine presents the user with the possibility of determining the setpoint When reaching the setpoint level the drying automatically stops Should the humidity later rise above...

Страница 28: ...ature and relative humidity If by these measurements dehumidification is again required the machine will resume dehumidification If on the other hand the measurements give that dehumidification is still not required the fans will stop and the machine will again remain idle for 55 minutes Intermittent fan mode does thus have a potential to save energy in situations where ducting and positioning of ...

Страница 29: ...e changed machines equipped with air flow balancing function are preferably re adjusted to ensure optimal performance Note that as described in the chapter on air flow balancing the adjustments are to be made when all ducting is installed and the machine has been allowed time to stabilize Early adjustments will inevitably result in suboptimal performance The A15ES has built in timer functionality ...

Страница 30: ...cables before powering up the machines The A15 has networking capabilities allowing it to be remotely monitored and controlled through SuperVision Once established in the network menu the presentation will toggle between the slave units which are referred to with type for instance A4 and address on the bus for instance 101 To change the settings of a slave unit press Edit and the select the given ...

Страница 31: ...the more advanced functions are removed from the menu system Keypad lock Possibility to activate deactivate the key pad lock RH Hysteresis Possibility to adjust the hysteresis settings for RH Control Mode The position of the setpoint in the operation span can be set as well as the hysteresis value Dew point Hysteresis Possibility to adjust the hysteresis settings for Dew point DEW Control Mode The...

Страница 32: ...th the regeneration air inlet and the wet air outlet are presented In a separate view is also presented the values provided by the temperature and relative humidity sensor by the process air inlet Counters This screen presents the hour and energy counters At the top the resettable work counters are presented followed by the date at which the counters were reset After the date the number of hours e...

Страница 33: ...ied this is also presented as a pop up screen Furthermore as long as the error condition remains in the top right corner of the default view there is a warning symbol The alarms presented need not be erased by the user Instead as soon as the machine detects that the functionality is again in place the alarm will disappear automatically ...

Страница 34: ...trolled hysteresis to make the operation of the machine stable and prevent excessive on and off switching The table below presents the default settings of the machine If changes are required these can be made under the Setup and Maintenance menu Control mode Hysteresis Setpoint position RH 4 Bottom Dewpoint 2 C Top Mix 0 5 g kg Bottom The below illustrations describe the different hysteresis setti...

Страница 35: ... contact with the external RHT sensor s Please check that the cables are correctly mounted When losing the external sensors the machine automatically reverts to using the built in RHT sensor One or more slaves are not responding This alarm is presented when the machine used as Master on a network has lost connection with one or more of its slave machines If it is presented check all the system cab...

Страница 36: ...ration and without apparent or known reason the machine shall be checked by service technician before it is put back in operation The overheat protection is mounted behind rubber grommet in the rotor cassette and is found above the rotor within easy reach when the service hatch is opened Please note that the mains power to the machine must be cut before the machine is opened Heater failure The mac...

Страница 37: ...ers have been turned off Process air filter not installed Stop the machine and replace the filter If the alarm appears incorrect check and if necessary adjust the alarm settings available in the Filter settings menu under Setup and maintenance See chapter Filter monitoring Dirty process air filter Stop the machine and replace the filter If the alarm appears incorrect check and if necessary adjust ...

Страница 38: ...etwork 5 When the network is created at the top of the screen the presentation will toggle between the different slaves If SuperVision is connected the text SuperVision will be presented at the bottom of the screen although it can take up to a minute before this is shown After having followed the steps above all the slave machines are now controlled by the Master This means that they will all be s...

Страница 39: ...schedule approximate equivalent and corresponding operation hours has been added for reference only Every 6 months 4750 hours 1 Inspection of and if required replacement of filters 2 Control of function 3 Zeroing of differential pressure sensors Every 12 months 9500 hours 1 Inspection of and if required replacement of filters 2 Inspection and cleaning of machine interior including rotor 3 Control ...

Страница 40: ...t the operation is normal and that there are no alarms presented on the control panel Service and repair work including cleaning For service and repair at all times the power must be disconnected from the machine Stop the machine and let it cool down Proceed by turning off the mains power switch and remove the power cable from the power intake Ensure that no other personnel reconnect power to the ...

Страница 41: ...osition using a screw driver The rotor tensioner is visible under the actual rotor between the rotor plates 1 Push down on the inner part of the rotor tensioner 2 Insert a screw driver through the hole in the left rotor plate to lock the rotor tensioner in released position 3 Clean the rotor 4 IMPORTANT Remove the screwdriver to let the tensioner back in intended position as soon as the cleaning i...

Страница 42: ...following are consumables and examples of accessories available for the A15ES Article number Name 6000733 Filter process air 1004717 Filter regeneration air 1002749 System cable 0 5 m 1002748 System cable 5 m 1002816 Adapter cable hygrostat 1002817 External RHT sensor ES series ...

Страница 43: ...xternal hygrostat is connected and used HYG mode check the setting of the hygrostat If RH DEW or MIX control mode is used check the setpoint highlighted at the center of the display and adjust as required Verify that the water symbol starts moving If the control mode and its settings was not the problem continue by checking the capacity mode presented in the top right corner of the default view Fo...

Страница 44: ...A15ES Corroventa Avfuktning AB 2022 05 44 67 The machine is operating on timer and currently in stand by If applicable adjust the set point of the humidistat ...

Страница 45: ...450 requires air flow balancing function Duct connections Regeneration and wet air diameter mm 160 Process and dry air diameter mm 250 Air filters Filter class regeneration process ISOePM1 55 F7 ISOePM1 55 F7 Power consumption Regeneration W 9300 Motors W 700 Rated power W 10000 Power connection Intake EC CEE 5P 16A 3N 400V 50hz Cable area power cable minimum mm2 2 5 Dimensions Length width height...

Страница 46: ...A15ES Corroventa Avfuktning AB 2022 05 46 67 APPENDIX 1 WIRING DIAGRAM ...

Страница 47: ...A15ES Corroventa Avfuktning AB 2022 05 47 67 ...

Страница 48: ...A15ES Corroventa Avfuktning AB 2022 05 48 67 ...

Страница 49: ...A15ES Corroventa Avfuktning AB 2022 05 49 67 ...

Страница 50: ...A15ES Corroventa Avfuktning AB 2022 05 50 67 ...

Страница 51: ...A15ES Corroventa Avfuktning AB 2022 05 51 67 ...

Страница 52: ...A15ES Corroventa Avfuktning AB 2022 05 52 67 ...

Страница 53: ...A15ES Corroventa Avfuktning AB 2022 05 53 67 ...

Страница 54: ...A15ES Corroventa Avfuktning AB 2022 05 54 67 ...

Страница 55: ...A15ES Corroventa Avfuktning AB 2022 05 55 67 ...

Страница 56: ...A15ES Corroventa Avfuktning AB 2022 05 56 67 ...

Страница 57: ...A15ES Corroventa Avfuktning AB 2022 05 57 67 ...

Страница 58: ...A15ES Corroventa Avfuktning AB 2022 05 58 67 ...

Страница 59: ...A15ES Corroventa Avfuktning AB 2022 05 59 67 ...

Страница 60: ...A15ES Corroventa Avfuktning AB 2022 05 60 67 ...

Страница 61: ...A15ES Corroventa Avfuktning AB 2022 05 61 67 ...

Страница 62: ...A15ES Corroventa Avfuktning AB 2022 05 62 67 ...

Страница 63: ...A15ES Corroventa Avfuktning AB 2022 05 63 67 ...

Страница 64: ...A15ES Corroventa Avfuktning AB 2022 05 64 67 ...

Страница 65: ...A15ES Corroventa Avfuktning AB 2022 05 65 67 ...

Страница 66: ...A15ES Corroventa Avfuktning AB 2022 05 66 67 ...

Страница 67: ...A15ES Corroventa Avfuktning AB 2022 05 67 67 ...

Отзывы: