Xtreme Ice Training Manual
TP00952
October 17, 2005
48
3. Remote condenser electrical hook-up:
A.
Connect remote condenser to a power source (208/230VAC, 60 HZ) separate from the cuber.
An external disconnect switch must be used.
B.
Make sure the electrical connections follow all local and
national codes.
C.
DO NOT turn condenser on until cuber install and refrigerant line connections are com-
plete!
D.
Never wire condenser into cuber section. The condenser is an independent electrical connec-
tion.
E.
Fan motor will not start until pressure rises to 205 PSIG [14.07 Bars] closing fan cycling switch.
F.
The condenser fan may cycle off during the harvest cycle – this would be normal.
NOTE: Installing an IMI Cornelius remote cuber with other than an IMI Cornelius remote condens-
er and line set may be reason to void the cuber warranty.
LIQUID
REFRIGERANT
LINE
DISCHARGE
LINE
CORRECT
FIGURE 23
4. Each condenser and cuber is connected with two (2) *pre-charged lines (See Figure 23).
A.
The pre-charged lines are ordered separately from the condenser to suit each individual ap-
plication (contact your service provider for more information).
B.
The pre-charged line lengths are 20 feet [6.096 meters], 35 feet [10.66 meters] and 55 feet
[16.76 meters] (contact your service provider for more information).
NOTE: Pre-charged is defined as a vapor holding charge – not a portion of the system charge.
5. Installation of line kits (see drawing). Remove the tubing from the carton. Carefully uncoil the lines so
the tubing doesn’t become kinked, and route lines to cuber and condenser.
6. Keep line-set as short as possible. Place a 3-foot service loop behind cuber to allow for rear service
should it ever be required.