vi
166240001
INTERMEDIATE
SEAL
PARENT
METAL
SEAL
SCHRADER
VALVE
8. Connection of Line Set
A.
Remove the plastic caps from the line set, the condenser, and the ice machine.
B.
Apply refrigeration oil to the threads on the quick connect couplers before connecting them to the con-
denser.
C.
Carefully thread the female fitting onto the condenser or ice machine by hand.
D.
Using the proper size wrench, tighten the couplings until they bottom out. Turn an additional 1/4 turn
to ensure proper brass-to-brass seating.
E.
Check all fittings for leaks.
9. Final Installation:
A.
Remove grill from the right hand side panel of cuber.
B.
Turn service port on receiver tank to open position releasing refrigerant to the balance of the system.
C.
Leak check line set connections at cuber and condenser.
D.
Replace grill.
E.
Connect cuber to power source.
F.
Make sure electrical connections follow all local and national codes.
10. Start Up:
A.
Use standard procedures from cuber installation instructions.
B.
After the cuber is running, check the remote condenser and verify that the condenser fan is running.
CAUTION: Once the refrigerant lines are connected, the seal is broken in the fittings. If the
line are removed or loosened from the cuber or remote condenser, the refrigerant charge
will be discharges to the atmosphere. DISCHARGING TO THE ATMOSPHERE IS IN
VIOLATION OF THE CLEAN AIR ACT OF JULY, 1992.